Komfovent BACnet Instrukcja instalacji

Typ
Instrukcja instalacji
BACnet
connection C6
EN Installation and service Manual
EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C6_22-09
2
BACNET CONNECTION AND SETTINGS
BACnet is a standard communication protocol for Building Automation and Control (BAC) networks that can be used
to monitor and control Komfovent air handling units with C6 controller. The supported Data Link Layer is BACnet / IP.
BACnet protocol works via Ethernet interface, connection is provided to RJ-45 socket (Pic.1) on the C6 controller
(CAT5 cable is recommended):
A
B
0..10V
Modbus RTU
GND
+24V
Hot water mixing
valve actuator
GND
+24V
Air damper
actuator
Max. load 15W
Supply air
temp. sensor
Return water
temp. sensor
Override
Fire alarm
Kitchen hood
Fireplace
N
NO
NO
NO
NC
C
C
Cold water mixing
valve actuator
+24V
GND
GND
+24V
Supply air
VAV sensor
Exhaust air
VAV sensor
C
NO
NO
Air quality
sensor
NO
~230V
N
Air humidity
sensor
+24V
GND
+24V
GND
+24V
GND
0-10V output
NTC
10k
NTC
10k
Alarm
Hot water pump
Max. load 100W
0..10V
0..10V
0..10V
0..10V
0..10V
0..10V
Common
Common
TG1 TG2 B1 B5 OUTPUTSAUX
B6 B7 B8 B9
INPUTS
212019181716151413121110987654321
424140393837363534333231302928272625242322
S1
FG1
~230V
RS485
Cooling
Heating
Common
Total power of 24V source may not exceed 30W
Ethernet RJ45, 10Mbit
Picture 1. C6 controller board
Below is default network settings of the C6 controller. These can be changed according to the building network
software requirements. To do so, it is needed to connect a laptop to the integrated webserver of C6 controller:
CONNECTIVITY
DHCP
IP address
Subnet mask
Gateway
BACnet ID
Modbus ID
RS-485
Off On
192 168 0 60
255 255 255 0
192 168 0 1
60
254
19200 baud 8E1
Picture 2. Connectivity settings
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C6_22-09 3
C6 controller IP can also be viewed and changed on the control panel – from Main menu go to Advanced settings-
>Connectivity:
16:30
NORMAL
ECO AUTO TURN OFF
Settings
Scheduling
Overview
Menu
5s
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1 / 2
DHCP
IP address
192.168.0.60
Gateway
192.168.0.1
BACnet ID
60
Subnet mask
255.255.255.0
Connectivity
Picture 3. Connectivity settings on C6.1 control panel display
BACnet Interoperability Building Blocks Supported
Data sharing
DS-RP-B Read Property
DS-RPM-B Read Property Multiple
DS-WP-B Write Property
Device management
DM-DCC-B Device Communication Control
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-TS-B Time Synchronization
Standard Object Types Supported:
Object type Properties
Device Object_Identier, Object_Name, Object_Type, System_Status, Vendor_Name, Vendor_Identier,
Model_Name, Firmware_Revision, Application_Software_Version, Protocol_Version, Protocol_Revision,
Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_APDU_Length_
Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_
Binding, Database_Revision, Property_List; Description, Local_Date, Local_Time
Analog value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_
Service, Units, Property_List; Reliability
Binary value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_
Service, Property_List; Incative_Text, Active_Text
Date value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Property_List
Multi-state value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_
Service, Number_Of_States, Property_List; State_Text
Positive integer value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Units, Property_List;
Reliability
Time value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Property_List
Objects:
Analog value
Object name Object
instance
Present value
Range/values/units Access
AWAY: setpoint 0 5.0 – 40.0 [°C] W
NORMAL: setpoint 1 5.0 – 40.0 [°C] W
INTENSIVE: setpoint 2 5.0 – 40.0 [°C] W
BOOST: setpoint 3 5.0 – 40.0 [°C] W
KITCHEN: setpoint 4 5.0 – 40.0 [°C] W
EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C6_22-09
4
Analog value
Object name Object
instance
Present value
Range/values/units Access
FIREPLACE: setpoint 5 5.0 – 40.0 [°C] W
OVERRIDE: setpoint 6 5.0 – 40.0 [°C] W
HOLIDAYS: setpoint 7 5.0 – 40.0 [°C] W
ECO: minimum supply air temperature 8 5.0 – 40.0 [°C] W
ECO: maximum supply air temperature 9 5.0 – 40.0 [°C] W
AIR QUALITY: temperature setpoint 10 5.0 – 40.0 [°C] W
INFO: supply temperature 11 [°C] R
INFO: extract temperature 12 [°C] R
INFO: outdoor temperature 13 [°C] R
INFO: water temperature 14 [°C] R
INFO: panel 1 temperature 15 [°C] R
INFO: panel 2 temperature 16 [°C] R
INFO: current supply fan intensivity 17 [°C] R
INFO: current extract fan intensivity 18 [°C] R
INFO: heat exchanger 19 [°C] R
INFO: electric heater 20 [°C] R
INFO: water heater 21 [°C] R
INFO: water cooler 22 [°C] R
INFO: DX unit 23 [°C] R
EFFICIENCY/STATUS: SPI 24 [W/(m3/h)] R
EFFICIENCY/STATUS: SPI (day) 25 [W/(m3/h)] R
Binary value
Object name Object
instance
Present value
Range/values/units Access
CONTROL: ON/OFF status 0 0 – o 1 – on W
CONTROL: ECO mode 1 0 – o 1 – on W
CONTROL: AUTO mode 2 0 – o 1 – on W
AWAY: heating 3 0 – o 1 – on W
NORMAL: heating 4 0 – o 1 – on W
INTENSIVE: heating 5 0 – o 1 – on W
BOOST: heating 6 0 – o 1 – on W
KITCHEN: heating 7 0 – o 1 – on W
FIREPLACE: heating 8 0 – o 1 – on W
OVERRIDE: heating 9 0 – o 1 – on W
HOLIDAYS: heating 10 0 – o 1 – on W
ECO: free heating/cooling 11 0 – o 1 – on W
ECO: heating enable denied 12 0 – o 1 – on W
ECO: cooling enable denied 13 0 – o 1 – on W
AIR QUALITY: enabled 14 0 – disabled 1 – enabled W
AIR QUALITY: heating 15 0 – o 1 – on W
ALARMS: low supply air ow 16 0 – no 1 – yes R
ALARMS: low extract air ow 17 0 – no 1 – yes R
ALARMS: return water temperature low 18 0 – no 1 – yes R
ALARMS: low supply air temperature 19 0 – no 1 – yes R
ALARMS: high supply air temperature 20 0 – no 1 – yes R
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C6_22-09 5
Binary value
Object name Object
instance
Present value
Range/values/units Access
ALARMS: electric heater overheat 21 0 – no 1 – yes R
ALARMS: heat exchanger failure 22 0 – no 1 – yes R
ALARMS: heat exchanger icing 23 0 – no 1 – yes R
ALARMS: internal re alarm 24 0 – no 1 – yes R
ALARMS: external re alarm 25 0 – no 1 – yes R
ALARMS: temperature sensor failure 26 0 – no 1 – yes R
ALARMS: controller failure 27 0 – no 1 – yes R
ALARMS: service mode 28 0 – no 1 – yes R
ALARMS: clogged air lters 29 0 – no 1 – yes R
ALARMS: heat exchanger low eciency 30 0 – no 1 – yes R
ALARMS: air ow sensor failure 31 0 – no 1 – yes R
INFO: alarm 32 0 – o 1 – on R
INFO: heating 33 0 – o 1 – on R
INFO: cooling 34 0 – o 1 – on R
CLEAN FILTERS CALIBRATION 35 0 – no 1 – yes W
Date value
Object name Object
instance
Present value
Range/values/units Access
HOLIDAYS: from 02017-01-01 – 2035-12-31 W
HOLIDAYS: till 12017-01-01 – 2035-12-31 W
Multi-state value
Object name Object
instance
Present value
Range/values/units Access
CONTROL: auto mode control 0 1 – scheduling 2 – air quality R
CONTROL: current mode 1
1 – standby
2 – away
3 – normal
4 – intensive
5 – boost
6 – kitchen
7 – replace
8 – override
9 – holiday
10 – auto
11 – o
W
[2-5]
SCHEDULER: operation program 21 – stay at home
2 – working week
3 – oce
4 – custom W
SCHEDULER: next mode 3
1 – standby
2 – away
3 – normal
4 – intensive
5 – boost R
SCHEDULER: next mode weekday 4
1 – today
2 – mo
3 – tu
4 – we
5 – th
6 – fr
7 – sa
8 – su
R
CONTROL: temperature control 51 – supply
2 – extract
3 – room
4 – balance W
CONTROL: ow control 61 – CAV
2 – VAV 3 – DCV W
CONTROL SEQEUENCE: stage 1 7
1 – none
2 – external coil
3 – electric heater
4 – external DX unit
W
CONTROL SEQEUENCE: stage 2 8 W
CONTROL SEQEUENCE: stage 3 9 W
SETTINGS: coil type 10 1 – hot water 2 – cold water W
EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C6_22-09
6
Multi-state value
Object name Object
instance
Present value
Range/values/units Access
SETTINGS: language 11
1 – en
2 – lt
3 – ru
4 – pl
5 – sk
6 – de
7 – fr
8 – hu
9 – it
10 – ee
11 – nl
12 – lv
13 – pt
14 – se
15 – 
16 – hr
W
SETTINGS: ow units 12 1 – m3/h 2 – l/s W
OVERRIDE: mode 13 1 – all time
2 – if on 3 – if o W
HOLIDAYS: microventilation 14 1 – 1 t. per day
2 – 2 t. per day
3 – 3 t. per day
4 – 4 t. per day W
AIR QUALITY: sensor type B8 15 1 – none
2 – CO2
3 – VOC
4 – RH
W
AIR QUALITY: sensor type B9 16 W
RESET SETTINGS 17
1 – none
2 – “away
3 – “normal
4 – “intensive”
5 – “boost
6 – “holidays”
7 – “override”
8 – “kitchen”
9 – “replace
10 – air quality
11 – eco
12 – advanced
W
ECO: heat recovery control 18 1 – Auto
2 – Constant 3 – Non stop W
Positive integer value
Object name Object
instance
Present value
Range/values/units Access
CONTROL: maximum supply ow 0[m3/h, l/s] R
CONTROL: maximum extract ow 1 [m3/h, l/s] R
CONTROL: maximum supply pressure 2 0 – 1000 [Pa] W
CONTROL: maximum extract pressure 3 0 – 1000 [Pa] W
CONNECTIVITY: IP address 4 0 – 4294967295 W
CONNECTIVITY: mask 5 0 – 4294967295 W
AWAY: supply ow 6 0.2 max – max [m3/h, l/s, Pa] W
AWAY: extract ow 7 0.2 max – max [m3/h, l/s, Pa] W
NORMAL: supply ow 8 0.2 max – max [m3/h, l/s, Pa] W
NORMAL: extract ow 9 0.2 max – max [m3/h, l/s, Pa] W
INTENSIVE: supply ow 10 0.2 max – max [m3/h, l/s, Pa] W
INTENSIVE: extract ow 11 0.2 max – max [m3/h, l/s, Pa] W
BOOST: supply ow 12 0.2 max – max [m3/h, l/s, Pa] W
BOOST: extract ow 13 0.2 max – max [m3/h, l/s, Pa] W
KITCHEN: supply ow 14 0.2 max – max [m3/h, l/s] W
KITCHEN: extract ow 15 0.2 max – max [m3/h, l/s] W
FIREPLACE: supply ow 16 0.2 max – max [m3/h, l/s] W
FIREPLACE: extract ow 17 0.2 max – max [m3/h, l/s] W
OVERRIDE: supply ow 18 0.2 max – max [m3/h, l/s] W
OVERRIDE: extract ow 19 0.2 max – max [m3/h, l/s] W
KITCHEN: timer 20 0 – 300 [min] W
FIREPLACE: timer 21 0 – 300 [min] W
OVERRIDE: timer 22 0 – 300 [min] W
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C6_22-09 7
Positive integer value
Object name Object
instance
Present value
Range/values/units Access
AIR QUALITY: air quality setpoint 23 0 – 2000 [ppm]
0 – 100 [%] W
AIR QUALITY: humidity setpoint 24 0 – 100 [%] W
AIR QUALITY: minimum intensivity 25 0, 20 – 100 [%] W
AIR QUALITY: maximum intensivity 26 0, 20 – 100 [%] W
AIR QUALITY: check period 27 1 – 24 [h] W
ALARMS: active alarms count 28 0 – 10
W
[39366
resets
alarms]
ALARMS: alarm history count 29 0 – 50 R
INFO: current supply ow 30 [m3/h, l/s] R
INFO: current extract ow 31 [m3/h, l/s] R
INFO: lters impurity 32 [%] R
INFO: air dampers 33 [%] R
INFO: supply pressure 34 [Pa] R
INFO: extract pressure 35 [Pa] R
INFO: air quality/humidity sensor 1 36 [ppm, %] R
INFO: air quality/humidity sensor 2 37 [ppm, %] R
INFO: panel 1 humidity 38 [%] R
INFO: panel 2 humidity 39 [%] R
INFO: panel 1 air quality 40 [ppm] R
INFO: panel 2 air quality 41 [ppm] R
EFFICIENCY/STATUS: power consumption 42 [W] R
EFFICIENCY/STATUS: heater power 43 [W] R
EFFICIENCY/STATUS: heat exchanger recovery 44 [W] R
EFFICIENCY/STATUS: heat exchanger eciency 45 [%] R
EFFICIENCY/STATUS: energy saving 46 [%] R
EFFICIENCY/STATUS: recovered energy (day) 47 [Wh] R
EFFICIENCY/STATUS: recovered energy (month) 48 [Wh] R
EFFICIENCY/STATUS: recovered energy (total) 49 [Wh] R
CONSUMPTION: AHU (day) 50 [Wh] R
CONSUMPTION: AHU (month) 51 [Wh] R
CONSUMPTION: AHU (total) 52 [Wh] R
CONSUMPTION: add. air heater (day) 53 [Wh] R
CONSUMPTION: add. air heater (month) 54 [Wh] R
CONSUMPTION: add. air heater (total) 55 [Wh] R
Time value
Object name Object
instance
Present value
Range/values/units Access
SCHEDULER: next mode start time 0 00:00 – 24:00 R
BACnet-C6_22-09
PARTNERS
AT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at
BE Ventilair group www.ventilairgroup.com
ACB Airconditioning www.acbairco.be
CZ REKUVENT s.r.o. www.rekuvent.cz
CH WESCO AG www.wesco.ch
SUDCLIMATAIR SA www.sudclimatair.ch
CH / LI CLIMAIR GmbH www.climair.ch
Trivent AG www.trivent.com
DK Øland A/S www.oeland.dk
EE BVT Partners www.bvtpartners.ee
FR ATIB www.atib.fr
HR Microclima www.microclima.hr
HU
AIRVENT Légtechnikai Zrt. www.airvent.hu
Gevent Magyarország Kft. www.gevent.hu
Merkapt www.merkapt.hu
IR Fantech Ventilation Ltd www.fantech.ie
IS Blikk & Tækniþjónustan ehf www.bogt.is
Hitataekni ehf www.hitataekni.is
IT Icaria srl www.icariavmc.it
NL
Ventilair group www.ventilairgroup.com
DECIPOL-Vortvent www.vortvent.nl
CLIMA DIRECT BV www.climadirect.com
NO
Ventilution AS www.ventilution.no
Ventistål AS www.ventistal.no
Thermo Control AS www.thermocontrol.no
PL Ventia Sp. z o.o. www.ventia.pl
SE Nordisk Ventilator AB www.nordiskventilator.se
SI Agregat d.o.o www.agregat.si
SK TZB produkt, s.r.o. www.tzbprodukt.sk
UAB KOMFOVENT
SERVICE AND SUPPORT
Phone: +370 5 200 8000
service@komfovent.com
Komfovent AB
Ögärdesvägen 12B
433 30 Partille, Sverige
Phone: +46 31 487 752
www.komfovent.se
Komfovent Oy
Muuntotie 1 C1
FI-01 510 VANTAA
Phone: +358 20 730 6190
toimisto@komfovent.com
www.komfovent.com
Komfovent GmbH
Konrad-Zuse-Str. 2a, 42551 Velbert,
Deutschland
Phone: +49 0 2051 6051180
www.komfovent.de
SIA Komfovent
Bukaišu iela 1, LV-1004 Riga
Phone: +371 24 664433
www.komfovent.lv
Vidzemes liāle
Alejas iela 12A, LV-4219 Valmiermuiža,
Valmieras pagasts, Burtnieku novads
Phone: +371 29 358 145