Komfovent BACNET connection C8 Instrukcja obsługi

Typ
Instrukcja obsługi
BACnet
connection C8
EN Installation and service Manual
EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C8_23-03
2
BACNET CONNECTION AND SETTINGS
BACnet is a standard communication protocol for Building Automation and Control (BAC) networks that can be used
to monitor and control Komfovent air handling units with C8 controller. The supported Data Link Layer is BACnet / IP.
BACnet protocol works via Ethernet interface, connection is provided to RJ-45 socket (Pic.1) on the C8 controller
(CAT5 cable is recommended):
Ethernet RJ45, 10Mbit
Picture 1. C8 controller board
Below is default network settings of the C8 controller. These can be changed according to the building network
software requirements. To do so, it is needed to connect a laptop to the integrated webserver of C8 controller:
CONNECTIVITY
DHCP
IP address
Subnet mask
Gateway
BACnet ID
Modbus ID
RS-485
Off On
192 168 0 60
255 255 255 0
192 168 0 1
60
254
19200 baud 8E1
Picture 2. Connectivity settings
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C8_23-03 3
C8 controller IP can also be viewed and changed on the control panel – from Main menu go to Advanced settings-
>Connectivity:
16:30
NORMAL
ECO AUTO TURN OFF
Settings
Scheduling
Overview
Menu
5s
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1 / 2
DHCP
IP address
192.168.0.60
Gateway
192.168.0.1
BACnet ID
60
Subnet mask
255.255.255.0
Connectivity
Picture 3. Connectivity settings on C6.1 control panel display
BACnet Interoperability Building Blocks Supported
Data sharing
DS-RP-B Read Property
DS-RPM-B Read Property Multiple
DS-WP-B Write Property
Device management
DM-DCC-B Device Communication Control
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-TS-B Time Synchronization
Standard Object Types Supported:
Object type Properties
Device
Object_Identier, Object_Name, Object_Type, System_Status, Vendor_Name, Vendor_Identier,
Model_Name, Firmware_Revision, Application_Software_Version, Protocol_Version, Protocol_Revision,
Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_APDU_Length_
Accepted, Segmentation_Supported, APDU_Timeout, Number_Of_APDU_Retries, Device_Address_
Binding, Database_Revision, Property_List; Description, Local_Date, Local_Time
Analog value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_
Service, Units, Property_List; Reliability
Binary value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_
Service, Property_List; Incative_Text, Active_Text
Date value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Property_List
Multi-state value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Event_State, Out_Of_
Service, Number_Of_States, Property_List; State_Text
Positive integer value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Units, Property_List;
Reliability
Time value Object_Identier, Object_Name, Object_Type, Present_Value, Status_Flags, Property_List
Objects:
Analog value
Object name Object
instance
Present value
Range/values/units Access
AWAY: setpoint 0 5.0 – 40.0 [°C] W
NORMAL: setpoint 1 5.0 – 40.0 [°C] W
INTENSIVE: setpoint 2 5.0 – 40.0 [°C] W
BOOST: setpoint 3 5.0 – 40.0 [°C] W
KITCHEN: setpoint 4 5.0 – 40.0 [°C] W
EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C8_23-03
4
Analog value
Object name Object
instance
Present value
Range/values/units Access
FIREPLACE: setpoint 5 5.0 – 40.0 [°C] W
OVERRIDE: setpoint 6 5.0 – 40.0 [°C] W
HOLIDAYS: setpoint 7 5.0 – 40.0 [°C] W
ECO: minimum supply air temperature 8 5.0 – 40.0 [°C] W
ECO: maximum supply air temperature 9 5.0 – 40.0 [°C] W
AIR QUALITY: temperature setpoint 10 5.0 – 40.0 [°C] W
INFO: supply temperature 11 [°C] R
INFO: extract temperature 12 [°C] R
INFO: outdoor temperature 13 [°C] R
INFO: water temperature 14 [°C] R
INFO: panel 1 temperature 15 [°C] R
INFO: panel 2 temperature 16 [°C] R
INFO: current supply fan intensity 17 [%] R
INFO: current extract fan intensity 18 [%] R
INFO: heat exchanger 19 [%] R
INFO: electric heater 20 [%] R
INFO: analog output 0-10V 21 [%] R
INFO: DX unit 22 [%] R
Binary value
Object name Object
instance
Present value
Range/values/units Access
CONTROL: ON/OFF status 0 0 – o 1 – on W
CONTROL: ECO mode 1 0 – o 1 – on W
CONTROL: AUTO mode 2 0 – o 1 – on W
AWAY: heating 3 0 – o 1 – on W
NORMAL: heating 4 0 – o 1 – on W
INTENSIVE: heating 5 0 – o 1 – on W
BOOST: heating 6 0 – o 1 – on W
KITCHEN: heating 7 0 – o 1 – on W
FIREPLACE: heating 8 0 – o 1 – on W
OVERRIDE: heating 9 0 – o 1 – on W
HOLIDAYS: heating 10 0 – o 1 – on W
ECO: free heating/cooling 11 0 – o 1 – on W
ECO: heating enable denied 12 0 – o 1 – on W
ECO: cooling enable denied 13 0 – o 1 – on W
ECO: non stop recuperation 14 0 – o 1 – on W
AIR QUALITY: enabled 15 0 – disabled 1 – enabled W
AIR QUALITY: heating 16 0 – o 1 – on W
ALARMS: return water temperature low 17 0 – no 1 – yes R
ALARMS: low supply air temperature 18 0 – no 1 – yes R
ALARMS: high supply air temperature 19 0 – no 1 – yes R
ALARMS: electric heater overheat 20 0 – no 1 – yes R
ALARMS: heat exchanger failure 21 0 – no 1 – yes R
ALARMS: heat exchanger icing 22 0 – no 1 – yes R
ALARMS: internal re alarm 23 0 – no 1 – yes R
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C8_23-03 5
Binary value
Object name Object
instance
Present value
Range/values/units Access
ALARMS: external re alarm 24 0 – no 1 – yes R
ALARMS: temperature sensor failure 25 0 – no 1 – yes R
ALARMS: controller failure 26 0 – no 1 – yes R
ALARMS: service mode 27 0 – no 1 – yes R
ALARMS: clogged air lters 28 0 – no 1 – yes R
ALARMS: heat exchanger low eciency 29 0 – no 1 – yes R
ALARMS: re dampers communication error 30 0 – no 1 – yes R
ALARMS: re dampers failure 31 0 – no 1 – yes R
INFO: heating 32 0 – o 1 – on R
INFO: cooling 33 0 – o 1 – on R
CLEAN FILTERS CALIBRATION 34 0 – no 1 – yes W
Date value
Object name Object
instance
Present value
Range/values/units Access
HOLIDAYS: from 02017-01-01 – 2035-12-31 W
HOLIDAYS: till 12017-01-01 – 2035-12-31 W
Multi-state value
Object name Object
instance
Present value
Range/values/units Access
CONTROL: auto mode control 0 1 – scheduling 2 – air quality R
CONTROL: current mode 1
1 – standby
2 – away
3 – normal
4 – intensive
5 – boost
6 – kitchen
7 – replace
8 – override
9 – holiday
10 – auto
11 – o
W
[2-5]
SCHEDULER: operation program 21 – stay at home
2 – working week
3 – oce
4 – custom W
SCHEDULER: next mode 3
1 – standby
2 – away
3 – normal
4 – intensive
5 – boost R
SCHEDULER: next mode weekday 4
1 – today
2 – mo
3 – tu
4 – we
5 – th
6 – fr
7 – sa
8 – su
R
CONTROL: temperature control 51 – supply
2 – extract
3 – room
4 – balance W
CONTROL SEQEUENCE: stage 1 6
1 – none
2 – external coil
3 – electric heater
4 – external DX unit
W
CONTROL SEQEUENCE: stage 2 7 W
CONTROL SEQEUENCE: stage 3 8 W
SETTINGS: coil type 9 1 – hot water 2 – cold water W
EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C8_23-03
6
Multi-state value
Object name Object
instance
Present value
Range/values/units Access
SETTINGS: language 10
1 – en
2 – lt
3 – ru
4 – pl
5 – sk
6 – de
7 – fr
8 – hu
9 – it
10 – ee
11 – nl
12 – lv
13 – pt
14 – se
15 – 
16 – hr
17 – sl
18 – cz
19 – dk
W
OVERRIDE: mode 11 1 – all time
2 – if on
3 – if o W
HOLIDAYS: microventilation 12 1 – 1 t. per day
2 – 2 t. per day
3 – 3 t. per day
4 – 4 t. per day W
AIR QUALITY: sensor type B8 13 1 – none
2 – CO2
3 – VOC
4 – RH W
RESET SETTINGS 14
1 – none
2 – “away
3 – “normal
4 – “intensive
5 – “boost
6 – “holidays
7 – “override”
8 – “kitchen”
9 – “replace
10 – air quality
11 – eco
12 – advanced
W
Positive integer value
Object name Object
instance
Present value
Range/values/units Access
CONNECTIVITY: IP address 0 0 – 4294967295 W
CONNECTIVITY: mask 1 0 – 4294967295 W
AWAY: supply ow 2 20 – 100 [%] W
AWAY: extract ow 3 20 – 100 [%] W
NORMAL: supply ow 4 20 – 100 [%] W
NORMAL: extract ow 5 20 – 100 [%] W
INTENSIVE: supply ow 6 20 – 100 [%] W
INTENSIVE: extract ow 7 20 – 100 [%] W
BOOST: supply ow 8 20 – 100 [%] W
BOOST: extract ow 9 20 – 100 [%] W
KITCHEN: supply ow 10 20 – 100 [%] W
KITCHEN: extract ow 11 20 – 100 [%] W
FIREPLACE: supply ow 12 20 – 100 [%] W
FIREPLACE: extract ow 13 20 – 100 [%] W
OVERRIDE: supply ow 14 20 – 100 [%] W
OVERRIDE: extract ow 15 20 – 100 [%] W
KITCHEN: timer 16 0 – 300 [min] W
FIREPLACE: timer 17 0 – 300 [min] W
OVERRIDE: timer 18 0 – 300 [min] W
AIR QUALITY: air quality setpoint 19 0 – 2000 [ppm]
0 – 100 [%] W
AIR QUALITY: humidity setpoint 20 0 – 100 [%] W
AIR QUALITY: minimum intensity 21 0, 20 – 100 [%] W
AIR QUALITY: maximum intensity 22 0, 20 – 100 [%] W
AIR QUALITY: check period 23 1 – 24 [h] W
UAB KOMFOVENT we reserve the right to make changes without prior notice
BACnet-C8_23-03 7
Positive integer value
Object name Object
instance
Present value
Range/values/units Access
ALARMS: active alarms count 24 0 – 10
W
[39366
resets
alarms]
ALARMS: alarm history count 25 0 – 50 R
INFO: current supply ow 26 [%] R
INFO: current extract ow 27 [%] R
INFO: lters impurity 28 [%] R
INFO: air dampers 29 [%] R
INFO: air quality/humidity sensor 30 [ppm, %] R
INFO: panel 1 humidity 31 [%] R
INFO: panel 2 humidity 32 [%] R
INFO: panel 1 air quality 33 [ppm] R
INFO: panel 2 air quality 34 [ppm] R
EFFICIENCY/STATUS: heater power 35 [W] R
OPERATION COUNTERS: supply air fan (day) 36 [h] R
OPERATION COUNTERS: supply air fan (month) 37 [h] R
OPERATION COUNTERS: supply air fan (total) 38 [h] R
OPERATION COUNTERS: exhaust air fan (day) 39 [h] R
OPERATION COUNTERS: exhaust air fan (month) 40 [h] R
OPERATION COUNTERS: exhaust air fan (total) 41 [h] R
OPERATION COUNTERS: electric heater (day) 42 [h] R
OPERATION COUNTERS: electric heater (month) 43 [h] R
OPERATION COUNTERS: electric heater (total) 44 [h] R
OPERATION COUNTERS: heat exchanger (day) 45 [h] R
OPERATION COUNTERS: heat exchanger (month) 46 [h] R
OPERATION COUNTERS: heat exchanger (total) 47 [h] R
Time value
Object name Object
instance
Present value
Range/values/units Access
SCHEDULER: next mode start time 0 00:00 – 24:00 R
BACnet-C8_23-03
PARTNERS
AT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at
BE Ventilair group www.ventilairgroup.com
ACB Airconditioning www.acbairco.be
CZ REKUVENT s.r.o. www.rekuvent.cz
CH WESCO AG www.wesco.ch
SUDCLIMATAIR SA www.sudclimatair.ch
CH / LI CLIMAIR GmbH www.climair.ch
Trivent AG www.trivent.com
DK Øland A/S www.oeland.dk
EE BVT Partners www.bvtpartners.ee
FR ATIB www.atib.fr
HR Microclima www.microclima.hr
HU
AIRVENT Légtechnikai Zrt. www.airvent.hu
Gevent Magyarország Kft. www.gevent.hu
Merkapt www.merkapt.hu
IR Fantech Ventilation Ltd www.fantech.ie
IS Blikk & Tækniþjónustan ehf www.bogt.is
Hitataekni ehf www.hitataekni.is
IT Icaria srl www.icariavmc.it
NL
Ventilair group www.ventilairgroup.com
DECIPOL-Vortvent www.vortvent.nl
CLIMA DIRECT BV www.climadirect.com
NO
Ventilution AS www.ventilution.no
Ventistål AS www.ventistal.no
Thermo Control AS www.thermocontrol.no
PL Ventia Sp. z o.o. www.ventia.pl
SE Nordisk Ventilator AB www.nordiskventilator.se
SI Agregat d.o.o www.agregat.si
SK TZB produkt, s.r.o. www.tzbprodukt.sk
UA TD VECON LLC www.vecon.ua
UAB KOMFOVENT
SERVICE AND SUPPORT
Phone: +370 5 200 8000
service@komfovent.com
Komfovent AB
Ögärdesvägen 12A
433 30 Partille, Sverige
Phone: +46 31 487 752
www.komfovent.se
Komfovent Oy
Muuntotie 1 C1
FI-01 510 VANTAA
Phone: +358 20 730 6190
toimisto@komfovent.com
www.komfovent.com
Komfovent GmbH
Konrad-Zuse-Str. 2a, 42551 Velbert,
Deutschland
Phone: +49 0 2051 6051180
www.komfovent.de
SIA Komfovent
Bukaišu iela 1, LV-1004 Riga
Phone: +371 24 664433
www.komfovent.lv
Vidzemes liāle
Alejas iela 12A, LV-4219 Valmiermuiža,
Valmieras pagasts, Burtnieku novads
Phone: +371 29 358 145
www.komfovent.lv
www.komfovent.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8