Clint CHA IK 18÷31 Instrukcja obsługi

Typ
Instrukcja obsługi
INSTALLATION,
USE AND
MANTEINANCE
MANUAL
Seria / Series
Wydanie / Issue Zastępuje / Replaces
Katalog / Manual
CHA/IK 18÷31
05.08 ---
CLM 110 ab
POLSKI / ENGLISH
INSTRUKCJA
MONTAŻU,
OBSŁUGI
I KONSERWACJI
2
CHA/IK
0. LIST OF ATTACHMENTS
List of documents supplied with the unit and forming
an integral part of this manual.
- Technical book
- Microprocessor manual
- Certificate of guarantee
0. LISTA ZAŁĄCZNIKÓW
Lista dokumentów dostarczonych z urządzeniami i sta-
nowiących integralną część z niniejszą instrukcją:
- Opis techniczny
- Instrukcja sterownika
- Gwarancja
3
CHA/IK
CONTENTS
LIST OF ATTACHMENTS
INTRODUCTION
General information
Attachments
Warnings
UNIT DESCRIPTION
Identification
Identification
Intended use
Contraindications
General description
SAFETY
Definition
General safety regulations
Symbols
Location of safety signs
Safety signs
Emergency and safety devices
Description of residue risks
Residue risks near the unit
Measures to take in case of leaking refrige-
rant gas
Operations with the panels removed
INSPECTION AND TRANSPORT
Inspection
Storage
Lifting and transport
Unpacking
INSTALLATION
Choosing the installation site
Water connections
General
0
1
1.1
1.2
1.3
2
2.1
2.1.1
2.2
2.3
2.4
3
3.1
3.2
3.3
3.3.1
3.3.2
3.4
3.5
3.5.1
3.5.2
3.5.3
4
4.1
4.2
4.3
4.4
5
5.1
5.2
5.2.1
SPIS TREŚCI
LISTA ZAŁĄCZNIKÓW
WSTĘP
Informacje ogólne
Załączniki
Ostrzeżenia
OPIS URZĄDZEŃ
Identyfikacja
Identyfikacja urządzenia
Zakres zastosowań
Przeciwwskazania
Opis ogólny
BEZPIECZEŃSTWO
Definicje
Ogólne zasady bezpieczeństwa
Oznaczenia
Rozmieszczenie etykiet ostrzegawczych
Etykiety ostrzegawcze
Zabezpieczenia i urządzenia awaryjne
Opis pozostałych zagrożeń
Pozostałe zagrożenia w pobliżu jednostki
Środki ostrożności w przypadku wycieku
czynnika
Prace przy zdjętych panelach
KONTROLA I TRANSPORT
Kontrola
Przechowywanie
Unoszenie i transport
Rozpakowanie
MONTAŻ
Wybór miejsca montażu
Przyłącza wodne
Ogólne wytyczne
0
1
1.1
1.2
1.3
2
2.1
2.1.1
2.2
2.3
2.4
3
3.1
3.2
3.3
3.3.1
3.3.2
3.4
3.5
3.5.1
3.5.2
3.5.3
4
4.1
4.2
4.3
4.4
5
5.1
5.2
5.2.1
4
CHA/IK
5.3
5.3.1
5.3.2
6
Evaporator
Electrical connections
General
External signals
START UP
Preliminary controls
Start up
Checks during unit operation
General
Defrosting
(Only heat pump units)
Stopping the unit
OPERATION
General
Seasonal shut down
TROUBLE SHOOTING
ROUTINE MAINTENANCE AND
CONTROLS
Warnings
General
Monthly controls
Four-monthly controls
Repairing the refrigerant circuit
Topping up the refrigerant liquid
SHUT DOWN AND DISPOSAL
5.2.2
5.3
5.3.1
5.3.2
6
6.1
6.2
6.3
6.3.1
6.3.2
6.4
7
7.1
7.2
8
9
9.1
9.1.1
9.1.2
9.2
9.3
10
Parownik
Instalacja elektryczna
Ogólne wytyczne
Sygnały zewnętrzne
ROZRUCH
Wstępne sprawdzenie
Rozruch
Kontrola w trakcie pracy urządzenia
Ogólne wytyczne
Odszranianie
(tylko dla jednostek typu pompa ciepła)
Zatrzymanie pracy jednostki
PRACA
Ogólne wytyczne
Sezonowa przerwa w pracy
USUWANIE USTEREK
RUTYNOWE CZYNNOŚCI KONSERWACYJNE
I PRZEGLĄDY
Ostrzeżenia
Ogólne wytyczne
Przeglądy comiesięczne
Przeglądy raz na cztery miesiące
Naprawa obiegu chłodniczego
Uzupełnianie czynnika
UTYLIZACJA URZĄDZENIA
5.2.2
6.1
6.2
6.3
6.3.1
6.3.2
6.4
7
7.1
7.2
8
9
9.1
9.1.1
9.1.2
9.2
9.3
10
5
CHA/IK
1. INTRODUCTION
1.1 GENERAL INFORMATION
This manual contains the installation, use and mainte -
nance instructions for the CHA/IK chillers, and highlights
all connected risks and perils. It has been expressly
prepared and written to allow authorised users to use
the CHA/IK water chillers in complete safety and with
the greatest of ease. Please read the whole of this
manual with care, paying special attention to the sec -
tions marked with
as non-compliance may cause harm to people, dete -
riorate the environment and/or damage the unit.
The company declines all responsibility for any improper
use of the unit, unauthorised modifications or non-com -
pliance with the instructions contained in this manual.
Please keep this manual in a safe place and make it
available to chiller operators and maintenance men.
1.2 ATTACHMENTS
The documents shown on page 2 form an integral part
of this manual.
1.3 WARNINGS
The CHA/IK units have been designed and built to
ensure long-term operating reliability and maximum
safety; for this reason and thanks to the company’s
design and construction policy, the company is able
to guarantee that this product totally complies with EC
safety standards.
A further guarantee of this is provided by the factory
tests carried out on the unit.
The user, therefore, must only ensure the unit is properly
used and that maintenance operations are carried out
according to the indications contained in this manual.
The unit should not be touched until the whole
of this manual has been carefully read.
1. WSTĘP
1.1 INFORMACJE OGÓLNE
1.2 ZAŁĄCZNIKI
Dokumenty wymienione na stronie 2 stanow integralną
część niniejszej instrukcji.
1.3 OSTRZEŻENIA
Nie należy dotykać urządzenia przed zapo-
znaniem się z niniejszą instrukcją.
Niniejsza instrukcja zawiera wytyczne dotyczące
montażu, obsługi i konserwacji agregatów CHA/IK oraz
opisuje wszystkie zagrożenia i niebezpieczeństwa
związane z tymi pracami. Została przygotowana i napi-
sana w sposób wyraźny, umożliwiając upoważnionym
użytkownikom bezpieczne i maksymalnie proste użytko-
wanie agregatów CHA/IK. Należy dokładnie zapoznać
się z całoścniniejszej instrukcji, zwracając szczególną
uwagę na fragmenty oznaczone symbolem
ponieważ nie stosowanie się do zawartych w nich
uwag może być przyczyną szkód, obrażeń ciała, mieć
negatywny wpływ na środowisko naturalne, a także
spowodować uszkodzenie urządzenia.
Producent nie ponosi odpowiedzialności za nieprawi-
dłowe użytkowanie agregatu, nieautoryzowane modyfi-
kacje lub postępowanie niezgodne z wytycznymi
zawartymi w niniejszej instrukcji. Instrukcję należy
przechowywać w bezpiecznym miejscu, dostępnym dla
operatorów i konserwatorów agregatu.
Agregaty CHA/IK zostały zaprojektowane i wykonane
dla zapewnienia długiej niezawodności eksploatacyjnej
i maksymalnego bezpieczeństwa; z tego powodu i dzięki
polityce projektowej i konstrukcyjnej producenta, gwa-
rantuje on, że produkt ten całkowicie spełnia wymogi
norm Unii Europejskiej. Ponadto dodatkową gwarancją
są fabryczne testy urządzeń.
Użytkownik musi zatem jedynie zagwarantować
prawidłowe użytkowanie urządzenia oraz dopilnować aby
czynności konserwatorskie przeprowadzane były zgod-
nie ze wskazówkami zawartymi w niniejszej instrukcji.
6
CHA/IK
This installation, use and maintenance man-
ual must always be kept within easy reach
of authorised staff who are obliged to read
it before carrying out any operations on the
unit.
Niniejsza instrukcja montażu, obsługi i kon-
serwacji musi być zawsze przechowywana
w miejscu łatwo dostępnym dla upownione-
go personelu, zobowiązanego do zapoznania
się z nią przed przyspieniem do wykonywania
jakichkolwiek prac związanych z urządzeniem.
Dalsze informacje oraz wyjaśnienia można uzyskać
kontaktując się z dystrybutorem:
KLIMA-THERM Sp. z o.o.
ul. Budowlanych 48, 80-298 Gdańsk
Tel. (58) 768 03 33; Fax. (58) 768 03 00
ul. Ostrobramska 101A, 04-041 Warszawa
Tel. (22) 517 36 00; Fax. (22) 879 99 07
e-mail: klimatyzacja@klima-therm.pl
www.klima-therm.pl
For any further information or explanations please contact
our distributor at the following address:
KLIMA-THERM Sp. z o.o.
ul. Budowlanych 48, 80-298 Gdańsk
Tel. (58) 768 03 33; Fax. (58) 768 03 00
ul. Ostrobramska 101A, 04-041 Warszawa
Tel. (22) 517 36 00; Fax. (22) 879 99 07
e-mail: klimatyzacja@klima-therm.pl
www.klima-therm.pl
7
CHA/IK
2 UNIT DESCRIPTION
This chapter contains a general description of the main
unit characteristics, together with those of its principal
standard and optional components.
2.1 IDENTIFICATION
2.1.1 Unit identification
The unit can be identified throug the plats attached on
the frame and in the electrical box. This label contains
the following information:
- Manufacturer’s name
- Manufacturer’s address
- Description of the series and type of unit
- Series number
- Year of construction
- Type and quantity of refrigerant liquid
- Max. Allowable pressure
- Pressure switch set point
- EC certification symbol
- Electrical characteristics
- Wiring diagram identification
G.I. HOLDING S.p.A
Via Max Piccini, 11/13
33050 RIVIGNANO (UD) - ITALY
Manufactured by BV.ITA.40.02.1230
Modello/Model Matricola/Serial number
Modell/Modèle Matrikelnr/Matricule
G.I. HOLDING S.p.A
Via Max Piccini 11/13
Tensioni-Fasi-Frequenza Tensioni circuiti ausiliari
33050 RIVIGNANO (UD)
Voltage-Phases-Frequency Auxiliary circuit voltage
ITALY
Spannung-Phasen-Frequenz Hilfstromkreisspannung Tel. +39 0432 773220
Tension-Phases-Fréquence Tension circuits auxiliaires Fax. +39 0432 773855
Corrente massima assorbita Corrente massima di spunto Web: www.clint.it
Max absorbed current Max starting current Manufactured by BV.ITA.40.02.1230
Maximale Stromaufnahme Max Anlaufstrom DIRETTIVA 97/23/CE del 29 maggio 1997 (P.E.D.) cat I
Courant maxi absorbée Courant maxi de démarrage
A A Modello/Model
Tipo di refrigerante Carica refrigerante per circuito Modell/Modèle
Refrigerant type Refrigerant charge per circuit
Kältemittel Typ Kältemittelfüllung pro Kreislauf Matricola/Serial number
Type de réfrigerant Charge de réfrigerant chaque circuit Matrikelnr/Matricule
kg
Taratura pressostato di alta Press. massima circuito idraulico Anno di costruzione
High pressure switch setting Max hydraulic circuit pressure Construction year
HD-Wächter Einstellung Max. Druck im hydraul. Kreislauf Baujahr
Préssion maxi refrigerant Préssion maxi circuit hydraulique Année de fabrication
Bar Bar
Gruppo del fluido frigorifero Data di produzione PS Max.Press.ammissibile
Group of the refrigerant fluid Manufacturing date Max Working press.Refrig.side
Kältemittel Klasse Herstellungsdatum Max Betriebsdruck Kältemittelseitug
Groupe de fluide frigorifique Date de fabrication Press.max.de travail cute refrigerant
28 bar
20 bar
ALTA
HIGH PRESS.
HOCHDUCK
HAUTE
BASSA
LOW PRESS.
NIEDERDUCK
BASSE
28 bar
20 bar
ALTA
HIGH PRESS.
HOCHDUCK
HAUTE
BASSA
LOW PRESS.
NIEDERDUCK
BASSE
28 bar
20 bar
ALTA
HIGH PRESS.
HOCHDUCK
HAUTE
BASSA
LOW PRESS.
NIEDERDUCK
BASSE
28 bar
20 bar
ALTA
HIGH PRESS.
HOCHDUCK
HAUTE
BASSA
LOW PRESS.
NIEDERDUCK
BASSE
bar
bar
ALTA
HIGH PRESS.
HOCHDUCK
HAUTE
BASSA
LOW PRESS.
NIEDERDUCK
BASSE
2 OPIS URZĄDZENIA
Rozdział ten zawiera ogólny opis głównych charakterystyk
urdzenia, oraz podstawowego wyposażenia standardo-
wego i akcesoriów opcjonalnych.
2.1 IDENTYFIKACJA
2.1.1 Identyfikacja urządzenia
Jednostkę można zidentyfikować na podstawie tabliczek
znamionowych zamocowanych na ramie urządzenia
i w rozdzielnicy elektrycznej. Tabliczka zawiera następu-
jące informacje:
- Nazwa producenta
- Adres producenta
- Opis serii i typu urządzenia
- Numer seryjny
- Rok produkcji
- Typ i ilość czynnika chłodniczego
- Maksymalne dopuszczalne ciśnienie
- Parametry presostatów
- Symbol certyfikacji CE
- Charakterystyki elektryczne
- Schemat połączeń
8
CHA/IK
2.2 INTENDED USE
The CHA/IK series of air condensation chillers have been
designed to cool water (possibly containing inhibited
ethylene glycol) circulating in a closed circuit. The heat
pump units (CHA/IK/WP) can cool or heat the water in
the closed circuit depending on which operating cycle
is chosen.
The heat or cold produced can be used for air-condi -
tioning systems.
2.3 CONTRAINDICATIONS
Do not use inflammable products near the
unit.
Do not use substances that can form ex-
plosive mixtures near the unit.
Do not use the unit in conditions that could
be harmful for the environment (see point
3.5 on page 13).
2.4 GENERAL DESCRIPTION
All the unit structures are made from peraluman. The
structure is free standing and the panels are easy to
remove in order to allow access to the inside of the unit
for maintenance and repair operations.
3 SAFETY
3.1 DEFINITION
This document uses the following definitions:
-Dangerous areas: any area inside and/or near to the
unit in which the presence of a person would give rise
to a risk for that person’s health.
-Exposed person: anyone who is wholly or partly inside
a dangerous area.
-Operator/Maintenance man: person or persons au-
thorised to operate, adjust, service, repair or move
the unit.
2.2 ZAKRES ZASTOSOWANIA
2.3 PRZECIWWSKAZANIA
Nie stosuj łatwopalnych produktów w pobliżu
urdzenia.
Nie stosuj w pobliżu urządzenia substancji
mogących przyczynsię do powstania mie-
szanek wybuchowych.
Nie używaj urządzenia w warunkach mogą-
cych stanowić zagrożenie dla środowiska
(patrz punkt 3.5 na stronie 13).
2.4 OPIS OGÓLNY
3 BEZPIECZEŃSTWO
3.1 DEFINICJE
W niniejszej instrukcji zastosowano następujące definicje:
-Obszary niebezpieczne: obszar wewnątrz i/lub w po-
bliżu urządzenia, w obrębie którego zachodzi ryzyko
uszczerbku na zdrowiu osoby w nim przebywającej.
-
Osoba narażona: osoba częściowo lub całkowicie prze-
bywająca w niebezpiecznym obszarze.
-
Operator / konserwator: osoba lub osoby upoważnione
do obsługi, regulacji, serwisowania, naprawy lub prze-
noszenia urządzenia.
Agregaty wody lodowej serii CHA/IK zostały zaprojek-
towane do schładzania wody (mogącej zawierać
inhibilitowany glikol etylenowy) w obiegu zamkniętym.
Jednostki typu pompa ciepła (CHA/IK/WP) moschła-
dzać lub podgrzewwodę w obiegu zamkniętym, w za-
leżności od wybranego cyklu pracy. Wytworzone ciepło
lub chłód może zostać wykorzystane do systemów
klimatyzacji.
Konstrukcja wszystkich urządzeń wykonana jest ze
stopu magnezowo-aluminiowego. Konstrukcja wolno-
stojąca z łatwymi w demontażu panelami, ułatwiającymi
dostęp do wnętrza urządzenia w celu przeprowadzenia
konserwacji i naprawy.
9
CHA/IK
3.2 GENERAL SAFETY REGULATIONS
It is forbidden for unauthorised persons to
approach the unit.
Scrupulously observe the contents of Chap-
ter 9 on page 30 before carrying out each
maintenance operation on the unit.
It is forbidden to remove safety guards and
by-pass safety and emergency devices.
It is forbidden to stand on the unit.
- Only use the unit to do what it was built for.
- The manufacturer declines all responsibility for damage
deriving from improper use or technical modifications
made to the unit.
- Check the safety devices are in perfect working order
on a regular basis.
- Do not dismount, modify or disconnect unit parts.
- When working on the unit, only use suitable tools and
equipment in good condition. Operators must wear
normal personal protection equipment (gloves, helmet,
goggles, etc.).
- Work on the electrical system of the unit may only be
carried out by a qualified electrician.
- Work on the refrigerant circuit may only be carried out
by specialised staff.
3.3 SYMBOLS
Check the state of the plates on a regular basis and
repair them if necessary.
3.3.1 Location of safety signs
5
2
1
6 7
3
4
3.2 OGÓLNE ZASADY BEZPIECZEŃSTWA
Osoby nieupoważnione nie powinny mieć
dostępu do urządzenia.
Przed przystąpieniem do jakiejkolwiek czyn-
ności konserwacyjnej, dokładniej zapoznaj
się z treścią rozdziału 9 na stronie 30.
Zabronione jest demontowanie zabezpieczeń,
obejść serwisowych i urządzeń awaryjnych.
Zabronione jest stawanie na urządzeniu.
- Używaj urządzenia wyłącznie zgodnie z jego przezna-
czeniem.
- Producent nie ponosi odpowiedzialności za uszkodze-
nia powstałe na skutek nieprawidłowego użytkowania
lub modyfikacji urządzenia.
-
Regularnie sprawdzaj czy zabezpieczenia działają
prawidłowo.
- Nie demontuj, nie modyfikuj, ani nie odłączaj elemen-
tów urządzenia.
-
Pracując przy urdzeniu stosuj wyłącznie odpowiednie
narzędzia i sprzęt w bardzo dobrym stanie technicznym.
Operatorzy powinni być zaopatrzeni w standardowe
środki ochrony osobistej (rękawice, kask, gogle itp.).
- Podłączanie instalacji elektrycznej może być wykona-
ne tylko przez wykwalifikowanego elektryka.
- Prace przy obiegu chłodniczym mogą bwykonywa-
ne tylko przez wykwalifikowanych specjalistów.
3.3 OZNACZENIA
Regularnie sprawdzaj stan tabliczek z ostrzeżeniami
i w razie konieczności poddaj je regeneracji.
3.3.1 Rozmieszczenie etykiet ostrzegawczych
11
CHA/IK
3.4 EMERGENCY AND SAFETY DEVICES
An emergency external circuit breaker must
be fitted by the unit installer to disconnect
the unit from the power supply.
3.5 DESCRIPTION OF RESIDUE RISKS
The description of residue risks includes the following
elements:
- the kind of danger the people working on the unit are
subjected to;
- description of the main dangers;
- who is exposed to such dangers;
- the main safety methods used to reduce the risk of
injury.
The following accident prevention instructions, with
reference to the relative areas concerned by residue
risks, must be integrated with all the general indica -
tions contained in the present chapter and with the
accident prevention regulations in force in the country
of installation.
3.5.1 Residue risks near the unit
- Electrocution if the unit is not properly corrected to
the mains power supply and earth circuit.
- Cuts or abrasions caused by sharp surfaces.
- Extraction and subsequent dispersion in the envi -
ronment of substances present in the installation
site.
- Ejection of objects falling on the fan blades.
- Leaking water (in case of malfunction).
- Formation of condensation and ice in front of the unit
while the unit heat pumps are working.
- Alteration of the micro climate (during operation).
- Noise (during operation).
- Leaking oil (in case of malfunction).
- Leaking refrigerant liquid (in case of malfunction).
N.B. Refrigerant liquid is a substance which causes a
greenhouse effect. Its vapours are heavier than
air and can cause suffocation by reducing the
amount of oxygen available for breathing. Rapid
evaporation of the liquid can cause freezing to
occur.
3.4
ZABEZPIECZENIA I URZĄDZENIA AWARYJNE
Awaryjny przerywacz obwodu musi zostać
zamontowany w pobliżu urządzenia w celu
odłączania go od zasilania.
3.5 OPIS POZOSTAŁYCH ZAGROŻEŃ
Opis pozostałych zagrożeń obejmuje następujące ele-
menty:
- typ zagrożenia, na jakie narażeni są użytkownicy;
- opis głównych niebezpieczeństw;
- kto jest na nie narażony;
- podstawowe zasady bezpieczeństwa stosowane
w celu uniknięcia obrażeń.
3.5.1
Pozostałe zagrożenia w pobliżu jednostki
- Porażenie prądem w przypadku nieprawidłowego po-
dłączenia urządzenia do zasilania i uziemienia.
-
Skaleczenie i obtarcia spowodowane ostrymi powierz-
chniami.
- Wyciek do atmosfery substancji obecnych w instalacji.
-
Wydmuchiwane przedmioty, które dostały się na łopatki
wentylatora.
- Wyciek wody (w przypadku awarii).
-
Tworzenie się kondensacji i oblodzenie frontu urzą-
dzenia przy pracujących pompach ciepła.
- Zmiana mikroklimatu (w czasie pracy).
- Hałas (w czasie pracy).
- Wycieki oleju (w przypadku awarii).
- Wycieki czynnika (w przypadku awarii).
N.B. Ciekły czynnik jest substancją powodującą efekt
cieplarniany. Jego opary są cięższe od powietrza
i mogą spowodować uduszenie na skutek redukcji
ilości tlenu niezbędnego do oddychania. Szybkie
odparowanie cieczy me być przyczyną zamar-
znięcia układu.
Poniższe instrukcje, opisujące sposoby zapobiegania
wypadkom, z odniesieniem do właściwych obszarów
narażonych na wystąpienie pozostałych zagrożeń,
muszą być stosowane łącznie z wszystkimi ogólnymi
wskazówkami opisanymi w bieżącym rozdziale oraz z
przepisami bezpieczeństwa obowiązującymi w kraju,
gdzie montowane jest urządzenie.
12
CHA/IK
3.5.2 Measures to take in case of leaking
refrigerant gas
- Product type:
R410a
- First aid measures:
General information:
Do not give anything to people who have fainted.
Inhalation:
take the person out into the open air. Use oxygen
or artificial respiration if necessary. Do not give
adrenaline or similar substances.
Contact with eyes:
carefully rinse with abundant water for at least 15
minutes and see a doctor.
Contact with the skin:
Wash with abundant water and remove all contami -
nated clothing immediately.
- Measures to take in case of accidental leaking:
Personal precautions:
evacuate all staff to safety areas. Make sure the
area is suitably ventilated. Use personal protection
equipment.
Environmental precautions:
to intercept the emission.
Cleaning methods:
to employ absorbent products.
3.5.3 Operations with the panels removed
Some of the following operations and/or controls require
the panels of the unit to be removed in order to access
the inside of the unit.
Before removing an outer panel, except for
the one protecting the electrical panel, the
unit must be disconnected from the mains
power supply.
Please note that some surfaces inside the unit may be
hot (piping, compressor, etc.), cold (compressor, suction
separator, etc.), sharp (coil fins) or moving (fans) even
when the unit is not working.
These operations may only be carried out by
qualified staff wearing safety clothing.
3.5.2 Środki ostrożności w przypadku wycieku
czynnika chłodniczego
- Typ substancji:
R410a
- Pierwsza pomoc:
Informacje ogólne:
nie podawaj żadnych środków omdlałym.
Wdychanie:
wyprowadź osobę na zewnątrz na powietrze. W razie
konieczności podaj tlen lub zastosuj sztuczne oddy-
chanie. Nie podawaj adrenaliny ani podobnych sub-
stancji.
Kontrakt z oczami:
ostrożnie przepłucz oczy obfitą ilością wody przez
co najmniej 15 minut i skontaktuj się z lekarzem.
Kontakt ze skórą:
przemyj obfitą ilością wody i natychmiast zdejmij
skażoną odzież.
- Postępowanie w przypadku wycieku:
Ochrona osobista:
ewakuuj wszystkich w bezpieczne miejsce. Upew-
nij się, że miejsce wycieku zostało odpowiednio wy-
wietrzone. Zastosuj środki ochrony osobistej.
Ochrona środowiska:
powstrzymanie wycieku.
Metoda czyszczenia:
zastosowanie produktów wchłaniających.
3.5.3 Prace przy zdjętych panelach
Niektóre z czynności wymagają demontażu paneli w celu
umożliwienia dostępu do wnętrza urządzenia.
Przed demontażem tylnego panelu, poza
elementem osłaniającym rozdzielnicę, należy
odłączyć urządzenie od źródła zasilania.
Należy zwrócić uwagę, że niektóre powierzchnie
wewnątrz urządzenia mogą być gorące (rurki,
sprężarka itp.), zimne (sprężarka, oddzielacz cie-
czy, itp.), ostre (lamele wymiennika) lub ruchome
(wentylatory) nawet w czasie gdy urządzenie nie
pracuje.
Czynności te mogą być wykonywane wy-
łączenie przez wykwalifikowany personel
wyposażony w odzież ochronną.
13
CHA/IK
Operating checks may require the unit to work (totally
or partially) while a panel is open. In this case the panel
should be removed when the unit is not working.
These checks are particularly dangerous and
may only be carried out by highly qualified
staff.
Proceed as follows:
- Turn off mains power with the main power switch.
- Open the electrical panel and remove the relative fuses
to disconnect the components that do not need to be
working in order to carry out the relative check.
- Close the electrical panel.
- Remove the panel in question.
- Start the unit.
- Carry out the relative check with the greatest of care
and using personal protection equipment.
- After completing the check, stop the unit and put the
panel back in place.
- Turn off mains power and put back any fuses that
were previously removed.
- Close the electrical panel.
Kontrola funkcjonowania może wymagać (całkowitej lub
częściowej) pracy urządzenia z otwartym panelem.
W takim przypadku panel należy zdemontować przed
uruchomieniem urządzenia.
Kontrole szczególnie niebezpieczne i po-
winny być wykonywane przez wysoko wy-
kwalifikowany personel.
Sposób postępowania:
- Odłącz zasilanie za pomocą głównego wyłącznika.
- Otwórz rozdzielnicę i wyjmij odpowiednie bezpieczniki
w celu odłączenia elementów, które nie muszą praco-
wać w czasie przeprowadzania kontroli.
- Zamknij rozdzielnicę.
- Zdemontuj wymagany panel.
- Uruchom jednostkę.
- Przeprowadź kontrolę z zachowaniem maksymalnej
ostrożności oraz stosując środki ochrony osobistej.
- Po zakończeniu kontroli, zatrzymaj jednosti zamon-
tuj panel na swoim miejscu.
- Odłącz główne zasilanie i zamontuj wcześniej wyjęte
bezpieczniki.
- Zamknij rozdzielnicę.
14
CHA/IK
4. INSPECTION AND TRANSPORT
4.1 INSPECTION
Check the condition of the unit on receipt. As the unit was
carefully checked before leaving the factory, any claims
for damages should be addressed to the forwarder. Any
damage should therefore be indicated on the Delivery
Note before signing it.
Please inform the company or the Agent of the nature
of the damage to the unit immediately.
The Customer must always write a report describing
any damage caused to the unit.
4.2 STORAGE
The temperature in the area where the units are stored
must range between -20 and +50°C.
4.3 LIFTING AND TRANSPORT
When unloading and positioning the unit, take great care
not to make sudden and/or violent manoeuvres. Do not
lift the unit by its piping or any other components.
The unit should only be moved as shown in the plate
attached to it.
Attention!
Make sure the unit is securely anchored
before lifting it in order to prevent it from
accidentally overturning or falling.
4.4 UNPACKING
Only unpack the unit when it has reached the installation
site and no longer needs to be moved.
Remove the packing material with care, making sure
not to damage the unit.
Given that various kinds of packing materials are used
(wood, nylon, polystyrene, cardboard, etc.), they should
be separated and delivered to specialised disposal and
recycling companies for environmental reasons.
4. KONTROLA I TRANSPORT
4.1 KONTROLA
Po otrzymaniu urządzenia sprawdź jego stan. Ponieważ
urdzenie zostało dokładnie sprawdzone przed opuszcze-
niem fabryki, wszelkie żądania odszkodowania za ewen-
tualne uszkodzenia powinny być adresowane do firmy
przewozowej. Wszelkie uszkodzenia należy uwzględnić
na Potwierdzeniu Dostawy, przed jego podpisaniem.
Należy niezwłocznie powiadomić naszą firmę lub jej
przedstawiciela o stopniu uszkodzenia urządzenia.
Klient powinien sporządzić raport opisujący wszystkie
uszkodzenia urządzenia.
4.2 PRZECHOWYWANIE
Temperatura w miejscu przechowywania urządzeń musi
mieścić się w zakresie od -20 do +50°C.
4.3 PODNOSZENIE I TRANSPORT
Podczas rozładunku i umiejscawiania urządzenia, zacho-
waj ostrność aby nie wykonywać nagłych i gwałtownych
ruchów. Nie unoś jednostki za jej orurowanie lub inne
elementy. Urządzenie może być przenoszone wącznie
na palecie, jak pokazano na poniższym rysunku.
UWAGA!
Przed rozpoczęciem unoszenia urządzenia
upewnij się, że zosto bezpiecznie zamoco-
wane, aby zapobiec przypadkowemu obróce-
niu i upadkowi urządzenia z wysokości.
4.4 ROZPAKOWANIE
Rozpakuj urządzenie dopiero w docelowym miejscu
montażu, kiedy dalsze przenoszenie urządzenia nie
dzie konieczne. Ostrożnie zdejmij materiały opakowa-
niowe, uważając aby nie uszkodzić jednostki. Ponieważ
zastosowano różnego typu materiały opakowaniowe
(drewno, nylon, polistyren, karton itp.), powinny one
zostać posegregowane, a następnie przekazane do
stosownej placówki gromadzącej dany typ odpadów,
w celu ochrony środowiska naturalnego.
15
CHA/IK
5 INSTALLATION
5.1 CHOOSING THE INSTALLATION SITE
When choosing the installation site the following points
should be considered:
-The weight of the unit:
The supporting surface under the unit must
be perfectly horizontal and able to withstand
its operating weight.
A supporting surface with an appropriate area should
be built. This is particularly important if the unit is in -
stalled on unstable ground (gardens, embankments,
etc.).
The supporting surface must:
lie on suitable foundations and be about 10-15 cm
higher than the surrounding ground;
be horizontal and able to withstand about 200% of
the weight of the unit in operation.
-Spaces:
Make sure that sufficient free space, as in-
dicated on the scale drawing, is left around
the unit.
Less space will make it difficult or impossible to carry
out maintenance operations and/or lead to faults in
the unit due to the reduction in the air flow on the
condenser coil or its recirculation.
Please note that obstacles such as can-
opies, shelters or coverings in general are
not permitted.
Please note that the heat pump units cause ice and
condensation. This water, collected by the drain pan,
must therefore be drained to prevent the floor from
becoming slippery.
People may not enter the unit area unless
they are authorised operators and mainte-
nance personnel.
-Noise:
The unit generates noise while it’s working; do not
install it in reverberating rooms. The unit must be po -
sitioned with the coil side facing the direction where
noise is less critical.
-Prevailing winds:
Wind may alter operating conditions; to minimise its
effects the unit should be positioned with the long side
parallel to the direction of prevailing winds.
-Vibrations:
The shock absorbers, standard, allow to avoid pos -
sible vibrations of the unit.
5 MONTAŻ
5.1 WYBÓR MIEJSCA MONTAŻU
Wybierając miejsce montażu należy wziąć pod uwagę
poniższe punkty.
-Masa urządzenia:
Urządzenie musi być posadowione na dokład-
nie wypoziomowanej powierzchni, będącej
w stanie utrzym masę roboczą urządzenia.
Należy przygotować odpowiednie miejsce i pod-
stawę dla urządzenia. Jest to szczególnie wne
w przypadku montażu na niestabilnym podłożu
(ogród, nabrzeża itp.).
Powierzchnia podporowa:
musi być usadowiona na stabilnym fundamencie około
10-15 cm ponad otaczającym ją terenem.
musi być wypoziomowana i w stanie utrzymać ciężar
równy około 200% masy roboczej urządzenia.
-Wolna przestrzeń:
Zapewnij wystarczającą wolną przestrzeń
wokół urządzenia zgodnie ze schematem.
Mniejsza przestrzutrudni lub uniemożliwi wy-
konanie czynności konserwacyjnych i/lub spo-
woduje nieprawidłowe działanie urządzenia na
skutek ograniczenia przepływu lub recyrkulacji
powietrza przez skraplacz.
Należy zwrócić uwagę, że przeszkody jak
zadaszenia, wiaty lub innego typu osłony
nie są dozwolone.
Należy zauważyć, że jednostki typu pompa ciepła po-
wodują tworzenie się oblodzenia i kondensacji. Wo-
dę zgromadzoną w tacy skroplin należy odprowadzić
aby uniknąć tworzenia się śliskich powierzchni na po-
dłodze.
Dostęp do miejsca montażu powinien być
ograniczony, umożliwiając przebywanie w
jego obszarze jedynie upoważnionym ope-
ratorom i konserwatorom.
-Hałas:
Urządzenie generuje dźwięk w czasie pracy; nie montuj
go w pomieszczeniach odbijających dźwięk.
Urządzenie powinno być skierowane skraplaczem w
stronę, gdzie generowany hałas nie będzie uciążliwy.
-Ochrona przed wiatrem:
Wiatr może pogarszać warunki pracy urządzenia; aby
zminimalizować efekt jego działania, urządzenie powinno
być skierowane dłuższą strorównolegle do kierunku,
z którego przeważnie wieje wiatr.
-Wibracje:
Amortyzatory drgań, stanowiące standardowe wyposa-
żenie urządz, pozwalają ograniczyć mliwe wibracje
urządzenia w czasie pracy.
16
CHA/IK
5.2 WATER CONNECTIONS
5.2.1 General
Please carefully carry out the following instructions and
observe current law when installing the chilled water
circuit.
Attention!
The water pipes must be suitably supported
with brackets in order not to weigh on the
chiller.
- Connect the pipes to the chiller with flexible joints in
order to prevent the transmission of vibrations and to
compensate thermal expansion.
- Install the following components on the pipes:
shut-off valve (moisters) for shutting off the water
mains;
temperature and pressure gauges for routine main-
tenance and inspection purposes;
check points on the inlet and outlet pipes for meas -
uring temperatures if temperature indicators are not
fitted;
metal filter (inlet pipe) with a maximum mesh aperture
of 1 mm to protect the exchanger from waste or
impurities in the pipes;
waterflow control valve
relief valves, fitted in the uppermost parts of the
water circuit, for expelling air;
eventual supplementary expansion tank of a suit-
able size for the quantity of water contained in the
system and the expected temperature range.
an automatic inlet valve for maintaining the pres -
sure of the system and compensating the thermal
expansion of the fluid.
5.2 PRZYŁĄCZA WODNE
5.2.1 Ogólne wytyczne
Wykonując instalację wody lodowej, należy dokładnie
wykonać poniższe instrukcje, zgodnie z obowiązucymi
przepisami.
Uwaga!
Przewody instalacji wodnej muszą być od-
powiednio zamocowane na wspornikach aby
uniknąć przeciążenia agregatu.
- Podłącz przewody do agregatu za pomocą złączek
elastycznych aby zapobiec przenoszeniu wibracji i dla
zrównoważenia rozszerzalności cieplnej.
- Instalację należy wyposażyć w następujące elementy:
zawór odcinający (zasuwa) główny dopływ wody;
manometry temperatury i ciśnienia dla celów rutyno-
wych przeglądów;
punkty kontrolne na wlocie i wylocie instalacji do po-
miaru temperatury, jeli nie zamontowano czujniw.
filtr metalowy (na wlocie) z maksymalną wielkością
oczek siatki 1 mm, dla zabezpieczenia wymiennika
przed odpadami lub nieczystościami obecnymi w
instalacji.
zawór kontrolny przepływu wody;
zawory odpowietrzające, montowane w najwyższym
punkcie obiegu wodnego.
ewentulanie, dodatkowe naczynie wzbior-
cze o wielkci odpowiadacej ilości wody
obecnej w układzie i dla przewidywanego
zakresu temperatur.
oraz automatyczny zawór wlotowy do podtrzymy-
wania ciśnienia w układzie i wyrównywania rozsze-
rzalności cieplnej cieczy.
17
CHA/IK
5.2.2 Evaporator
It is vitally important that the water enters
the unit from the connection point marked
with the “WATER INLET” plate.
Threaded male unions (please refer to the scale draw-
ings which also show the position of the unions).
It is vitally important to connect the water
circuit so that the flow of water to the ex-
changer is always constant under all oper-
ating conditions.
A safety valve, serially supplied, on the water
circuit. In case of serious system faults (e.g.
re) this will allow the system to be drained
in order to prevent the risk of explosions.
Always connect the drain to a pipe with a
diameter not less than that of the valve open-
ing and install the outlet in an area where the
jet cannot cause harm to people.
Attention!
While connecting the water circuit, never
work with naked flames near to or inside
the unit.
5.2.2 Parownik
Istotne jest aby woda była doprowadzana
do urządzenia przez przyłącze oznaczone
tabliczką „WATER INLET” (wlot wody).
ącza skie gwintowane (patrz schematy wskazujące
rozmieszczenie złączy).
Ważne jest aby podłączenie obiegu wodne-
go umożliwiało regularny przepływ wody do
wymiennika niezależnie od warunków pracy.
Zawór bezpieczeństwa montowany seryjnie
na obiegu wodnym. W przypadku poważnej
awarii systemu (np. pożar) zawór ten umo-
żliwi odprowadzenie czynnika z systemu aby
uniknąć eksplozji. Zawsze podłączaj odpływ
do rurki o średnicy nie mniejszej n średnica
przyłącza zaworu oraz montuj wylot w miejscu,
gdzie strumień nie spowoduje obrażeń.
Uwaga!
Podczas poączania obiegu wodnego nigdy
nie używaj otwartego ognia w pobliżu lub
wewnątrz urządzenia.
18
CHA/IK
1 = Połączenia odporne na wibracje
2 = Kulowy zawór odcinający
3 = Zawór kontrolny
4 = Pompa obiegowa
5 = Filtr z siatką
6 = Automatyczny zawór do napełniania wody
7 = Zamknięte naczynie wzbiorcze
8 = Zawór bezpieczeństwa
9= Termometry
10= Automatyczny odpowietrznik
11= Manometr
12= Ręczny odpowietrznik
13= Presostat różnicowy
14= Zawór odcinający na wlocie wody
15= Zawór odcinający na wylocie wody
E = Parownik
1 = Vibration-proof joints
2 = ball shut-off valve
3 = Check valve
4 = Circulation pump
5 = Mesh filter
6 = Automatic water filling valve
7 = Closed expansion tank
8 = Safety valve
9= Thermometers
10= Automatic air purge
11= Pressure gauge
12= Manual air vent
13= Differential pressure switch
14= Water charge shut off valve
15= Water discharge shut off valve
E = Evaporator
5.3 ELECTRICAL CONNECTIONS
5.3.1 General
These operations may only be carried out
by specialised staff.
Before carrying out any operations on elec-
trical components, make sure the unit is dis-
connected from the mains power supply.
Make sure that the mains power supply corresponds to
the rated values of the unit shown on the plate (voltage,
number of phases, frequency).
Schemat podłączania obiegu wodnego
Hydraulic circuit connection diagram
T
T
1
1
8
7
4
9
9
10
10
11
12
13
1415
2
2 3 5
6
E
5.3 INSTALACJA ELEKTRYCZNA
5.3.1 Ogólne wytyczne
Czynności te mogą być wykonywane tylko
przez wykwalifikowany personel.
Przed przyspieniem do czynności związanych
z podzespołami elektrycznymi upewnij s, że
urządzenie zostało oączone od źródła zasilania.
Sprawdź czy źródło zasilania odpowiada wartościom
znamionowym urządzenia podanym na tabliczce zna-
mionowej (napięcie, ilość faz, częstotliwość).
19
CHA/IK
5.3.2 Sygnały zewnętrzne
W przypadku sterowania za pośrednictwem zdalnego
wyświetlacza, podaj sygnał ON na zacisk 16-00, a dla
pracy w sezonie letnim na zacisk 17-00.
Electrical connections must be made carefully follow -
ing the instructions shown on the catalogue attached
to the unit.
The earth connection is obligatory by law. The earth
cable must be connected to the earth bar located in
the electrical panel and marked with PE.
Auxiliary circuit power is supplied by the power line by
means of a transformer located in the electrical panel.
The cross-section of the cable and the line
protections must comply with the indications
shown on the wiring diagram and in the rela-
tive sheet attached to the unit.
Input voltage must not exceed variations of over ±5%
and phase unbalance must always be less than 2%.
Unit operation must always take place within
the above values as otherwise the guarantee
will immediately become null and void.
A possible additional pump must be started
up before starting up the chiller while it must
be stopped after the chiller has stopped (mini-
mum recommended delay: 40 seconds).
5.3.2 External signals
If a remote ON-OFF command is required, connect the
external enable to the contacts shown on the wiring
diagram.
For the electrical connection to the remote On-off contact
and remote Chiller heat pump operation, do not install
drive cables inside the ducts used for power cables; if
it is not possible, a shielded cable must be used.
- In case of control trough remote Display give consent
ON trough contact 16-00 and summer Working trough
17-00.
When making the connections described
in paragraph 5.3.2, carefully follow the in-
dications shown in the wiring diagram and
instructions kit. The connecting cables must
have a minimum cross-section of 1,5 mm².
Instalację elektrycznależy wykonać starannie, zgodnie
z instrukcjami zawartymi w katalogu dołączonym do
urządzenia.
Konieczność uziemienia urządzenia jest ustalona praw-
nie. Przewód uziemiacy musi być podłączony do listwy
uziemiającej w rozdzielnicy, oznaczonej symbolem PE.
Dodatkowy obwód zasilania gwarantowany jest z linii
zasilania za pomocą transformatora znajdującego się
w rozdzielnicy.
Przekrój kabla oraz zabezpieczenia liniowe
muszą być zgodne z oznaczeniami umiesz-
czonymi na schemacie elektrycznym oraz od-
powiedniej karcie dołączonej do urządzenia.
Wahania napięcia wejściowego nie mogą przekraczać
±5%, a niezrównoważenie faz musi być zawsze niższe
niż 2%.
Praca urządzenia musi zawsze odbywać się
przy zachowaniu powyższych wartości, w in-
nym przypadku nastąpi natychmiastowe zer-
wanie umowy gwarancyjnej.
Ewentualna dodatkowa pompa musi być uru-
chamiana przed uruchomieniem agregatu
i zatrzymywana po zatrzymaniu pracy agre-
gatu (minimalne zalecane opóźnienie: 40
sekund).
Wykonując połączenie opisane w rozdziale
5.3.2, dokładnie zapoznaj się z oznaczeniami
na schemacie elektrycznym oraz z zestawem
instrukcji. Minimalny przekrój
przewodów
połączeniowych wynosi 1,5 mm².
Dla połączeń elektrycznych zdalnego włącznika/wyłącz-
nika i zdalnego sterowania pracą pompy ciepła agregatu,
nie montuj przewodów prowadzących wewnątrz kanałów
przeznaczonych dla przewodów zasilających, jeżeli nie
jest to możliwe, należy zastosować przewód ekranowany.
Jeżeli wymagane jest zastosowanie zdalnego włącznika/
wyłącznika, podłącz zewnętrzny sygnał do zacisków,
zgodnie ze schematem połączeń.
20
CHA/IK
6 START UP
6.1 PRELIMINARY CONTROLS
- Make sure that the electrical connections have been
made correctly and that all the terminals have been
well tightened.
-Use a tester to make sure that the voltage on terminals
L1, N, is equal to that shown on the rating plate (permit -
ted tolerance ±5%). If voltage is subject to frequent
variations, please contact technical main office in order
to decide on suitable protection devices.
- Use a leak tester, if necessary to make sure there are
no leaks of refrigerant liquid.
- Check that the heating elements of the sump are cor -
rectly powered.
The heating elements must be turned on
at least 12 hours before start up; this takes
place automatically when the main power
switch is closed (position I).
To check if the heating elements work correctly, make
sure that the lower part of the compressor is 10÷15°C
higher than room temperature.
- Check the water circuit is correctly connected (the indi -
cations on the unit rating plate must be observed).
- Make sure that the water circuit has been cleaned
beforehand: the water circuit should be washed, by -
passing the unit, and then the system filter checked
for dirt.
- The units are despatched with the relief valves and
drains open. Special plates show where they are lo -
cated. They must be closed during installation before
the water circuit is filled.
- Make sure the water circuit has been well vented to
eliminate any air residues; this operation is carried
out by gradually loading and opening the relief valves
fitted to the uppermost part of the unit by the installer
(please consult section 5.2 for further information).
6 ROZRUCH
6.1 WSTĘPNE SPRAWDZENIE
- Upewnij się, czy instalacja elektryczna zosta prawidło-
wo wykonana i czy wszystkie zaciski zostały solidnie
dociśnięte.
-
Użyj miernika aby upewnsię, że napięcie na zaciskach
L1, N jest zgodne z danymi na tabliczce znamionowej
(dopuszczalna tolerancja ±5%). Jeżeli napięcie podda-
wane jest częstym wahaniom, skonsultuj sz dorad
technicznym w celu dobrania odpowiednich zabezpieczeń.
-
W razie konieczności zastosuj wykrywacz wycieków aby
upewnić się, że w systemie nie ma wycieków czynnika.
- Sprawdź czy elementy grzewcze karteru są prawidło-
wo zasilane.
Grzałka karteru powinna b załączona przy-
najmniej 12 godzin przez uruchomieniem
urządzenia; następuje to automatycznie po
załączeniu głównego wyłącznika (wyłącznik
w pozycji I).
Aby sprawdzić poprawność funkcjonowania elementów
grzewczych upewnij się, że temperatura w dolnej części
spżarki jest o 10-1C wyższa od temperatury w po-
mieszczeniu.
- Sprawdź poprawność podłączenia obiegu wodnego
(zgodnie z oznaczeniem na tabliczce znamionowej).
- Upewnij się, że obieg wodny został uprzednio oczysz-
czony: obieg wodny powinien zostać umyty, z pomi-
nięciem urządzenia, a następnie należy sprawdzić stan
zabrudzenia filtra.
- Urządzenia dostarczane są z otwartymi zaworami od-
powietrzającymi i otworami spustowymi. Specjalne ta-
bliczki informują o ich rozmieszczeniu. Muszą zostać
zamknięte na czas montażu przed napełnieniem obiegu
wodnego.
- Upewnij się, że obieg wodny został wystarczająco od-
powietrzony; czynność tą wykonuje się przez stopniowe
zamykanie i otwieranie zaworów odpowietrzających,
znajdujących się w najwyższym punkcie urządzenia
(więcej informacji znajduje się w punkcie 5.2).
21
CHA/IK
- W przypadku zastosowania wody z roztworem gli-
kolu, skontaktuj się z punktem serwisowym.
- In case of use of glycol water contact service cen -
tre.
Attention!
Before starting up the unit, make sure that
all the external panels are in place and fixed
with screws.
Uwaga!
Przed uruchomieniem urządzenia upewnij
się, że wszystkie panele zewnętrzne są za-
mocowane na miejscu śrubami.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Clint CHA IK 18÷31 Instrukcja obsługi

Typ
Instrukcja obsługi

w innych językach