Sierra InnovaMass 240i/241i Modbus Instrukcja obsługi

Typ
Instrukcja obsługi

Ten podręcznik jest również odpowiedni dla

InnovaMass
®
240i/241i
Modbus
Preliminary Instruction Manual
Modbus Specification for Models: 240i and 241i
Volumetric & Multivariable Mass Vortex Flow Meter
Part Number: IM-24i-Modbus, V3, November 2020
2
GLOBAL SUPPORT LOCATIONS: WE ARE HERE TO HELP!
CORPORATE HEADQUARTERS
5 Harris Court, Building L Monterey, CA 93940
Phone (831) 373-0200 (800) 866-0200 Fax (831) 373-4402
www.sierrainstruments.com
EUROPE HEADQUARTERS
Bijlmansweid 2 1934RE Egmond aan den Hoef
The Netherlands
Phone +31 72 5071400 Fax +31 72 5071401
ASIA HEADQUARTERS
Second Floor Building 5, Senpu Industrial Park
25 Hangdu Road Hangtou Town
Pu Dong New District, Shanghai, P.R. China
Postal Code 201316
Phone: + 8621 5879 8521 Fax: +8621 5879 8586
IMPORTANT CUSTOMER NOTICE- OXYGEN SERVICE
Unless you have specifically ordered Sierra’s optional O
2
cleaning, this flow meter may not be fit for
oxygen service. Sierra Instruments, Inc., is not liable for any damage or personal injury, whatsoever,
resulting from the use of Sierra Instruments standard mass flow meters for oxygen gas. You are
responsible for cleaning the mass flow meter to the degree required for your oxygen flow application.
However, some models can only be properly cleaned during the manufacturing process.
© COPYRIGHT SIERRA INSTRUMENTS 2019
No part of this publication may be copied or distributed, transmitted, transcribed, stored in a retrieval
system, or translated into any human or computer language, in any form or by any means, electronic,
mechanical, manual, or otherwise, or disclosed to third parties without the express written permission of
Sierra Instruments. The information contained in this manual is subject to change without notice.
TRADEMARKS
InnovaMass
®
, qTherm
®
, Dial-a-Gas™, Dial-a-Pipe™, and MassBalance™ are trademarks of Sierra
Instruments, Inc. Other product and company names listed in this manual are trademarks or trade
names of their respective manufacturers.
3
Warnings and Cautions
Note and Safety Information
We use caution and warning statements throughout this book to draw
your
attention to important information.
Warning!
This statement appears with
information that is important to
protect people and equipment from
damage. Pay very close attention to
all warnings that apply to your
application.
Warning!
Consult the flow meter nameplate for specific flow meter approvals before any hazardous location
installation.
Hot tapping must be performed by a trained professional. U.S. regulations often require a hot tap permit.
The manufacturer of the hot tap equipment and/or the contractor performing the hot tap is responsible
for providing proof of such a permit.
All flow meter connections, isolation valves and fittings for cold/hot tapping must have the same or
higher pressure rating as the main pipeline.
For insertion flow meter installations, an insertion tool must be used for any installation where a flow
meter is inserted under pressure greater than 50 psig.
To avoid serious injury, DO NOT loosen a compression fitting under pressure.
To avoid potential electric shock, follow National Electric Code or your local code when wiring this unit
to a power source. Failure to do so could result in injury or death. All AC power connections must be in
accordance with published CE directives. All wiring procedures must be performed with the power off.
Before attempting any flow meter repair, verify that the line is not pressurized. Always remove main
power before disassembling any part of the mass flow meter.
4
Caution!
Calibration must be performed by qualified personnel. Sierra strongly recommends that you return your
flow meter to the factory for calibration.
In order to achieve accurate and repeatable performance, the flow meter must be installed with the
specified minimum length of straight pipe upstream and downstream of the flow meter’s sensor head.
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four hours at full gas
flow before installing the flow meter.
For insertion flow meter installations, the sensor alignment pointer must point downstream in the
direction of flow.
The AC wire insulation temperature rating must meet or exceed 85°C (185°F)
Receipt of System Components
When receiving a Sierra mass flow meter, carefully check the outside
packing
carton
for damage incurred in shipment. If the carton is damaged, notify the local carrier
and submit a report to the factory or distributor. Remove the packing slip and
check that all ordered components are present. Make sure any spare parts or
accessories are not
discarded with the packing material. Do not return any
equipment to
the factory without first contacting Sierra Customer Service
.
Technical Assistance
If you encounter a problem with your flow meter, review the configuration
information for each step of the installation, operation, and
setup procedures.
Verify that your settings and adjustments are consistent with factory
recommendations.
Installation and troubleshooting information can be found in
the Chapter 6 of this manual.
If the problem persists after following the troubleshooting procedures
outlined in
Chapter 6 of this manual, contact Sierra Instruments by fax or by E-mail
(see
inside front cover). For urgent phone support you may call (800)
866-0200 or
(831) 373-0200 between 8:00 a.m. and 5:00 p.m. PST. In
Europe, contact Sierra
Instruments Europe at
+31 72 5071400
. In the Asia-Pacific region, contact Sierra
Instruments Asia at +
8621 5879 8521.
When contacting Technical Support, make
sure to include this information:
The flow range, serial number, and Sierra order number (all
marked on the meter nameplate)
The software version (visible at start up)
The problem you are encountering and any corrective action
taken
Application information (gas, pressure, temperature and piping
configuration)
5
Table of Contents
Chapter 1 InnovaMass 240i/241i Modbus ............................................................................................. 6
InnovaMass Modbus Introduction ......................................................................................................... 6
Electrical Connections .......................................................................................................................... 7
Instrument Power Connection ............................................................................................................. 7
RS-485 Connection ............................................................................................................................. 7
Connecting the RS-485 to Your InnovaMass ...................................................................................... 8
General 2-Wire Topology RS-485 Network ......................................................................................... 9
Cable ................................................................................................................................................. 10
Terminator ......................................................................................................................................... 10
Line Polarization ................................................................................................................................ 10
Grounding .......................................................................................................................................... 10
Communicating ................................................................................................................................... 11
Data Format Type for Various Registers ........................................................................................... 11
Modbus Registers Overview .............................................................................................................. 12
Registers Explained ............................................................................................................................ 14
Introduction ........................................................................................................................................ 23
Getting Started .................................................................................................................................. 23
Load Firmware ................................................................................................................................... 24
Setup Firmware ................................................................................................................................. 26
Quit .................................................................................................................................................... 27
Troubleshooting ................................................................................................................................. 28
6
Chapter 1 InnovaMass 240i/241i Modbus
InnovaMass Modbus Introduction
Modbus-RTU is a serial communications protocol first published by Modicon in 1979 for use
with its programmable logic controllers (PLCs). It’s simple and robust, royalty free, and it has
since become a de facto standard communication protocol now a commonly available means
of connecting industrial electronic devices in the USA.
Modbus RS-485 allows for communication between many devices (nodes) connected to the
same RS-485 network. Modbus-RTU can be used to connect a supervisory computer with a
remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems. It
supports many data types, Including:
Floating point IEEE 754 (Real)
32-bit integer
8-bit ASCII data
16-bit integer
Mixed data types
Bit fields in integers
Multipliers to change data to/from integer. 10, 100, 1000, 256 ...
The Modbus RS-485 interface discussed in this manual is an option for Sierra’s InnovaMass
240i and 241i Vortex Volumetric Flow and Multivariable Mass Flow. The interface makes it
possible to connect the InnovaMass to a Modbus network and remotely operate it.
For more information about Modbus, visit their website at http://www.Modbus.org/.
Caution!
To fully understand the InnovaMass and its functions it is advised to
also read the InnovaMass instruction manual.
7
Electrical Connections
All electrical connections are made on the terminal board inside the InnovaMass enclosure.
Instrument Power Connection
Power supply requirements for the InnovaMass are the following:
Voltage: 24 VDC +/- 10%,
Amperage: 1.1 A
Modbus RS-485 Connection
Caution!
The InnovaMass is equipped with an optical isolated RS-485 interface.
Grounding the RS485 common (16) would defeat this.
DC Power -
DC Power +
8
Connecting the RS-485 to Your InnovaMass
1. Connect your 2-wire RS-485 network to terminal 13 (A -) and your 2-wire RS-485 to
terrmnal 14 (B +). Occasionally you may find a Modbus device from another
manufacter labeled A+ and B-, in that case the A and B terminals need to be swapped.
2. Connect the RS-485 common (sheild wire) to terminal 15 (Com).
3. The meter’s Modbus Address, Baud Rate, and Parity are set using the Boot loader,
see Boot loader on page 23. You should do this before wiring your meter to the full
Modbus network.
Cabling Summary
1. Use a 24 AWG shielded twisted pair cable, with low capacitance, 120Ω impedance
like Belden 9841.
2. Never put the Modbus wires in the same conduit as AC power. Ideally DC power
wires should be run in separate conduit if possible, to prevent interference issues.
3. Both ends of the RS485 network cable should have 120 Ω resistors to prevent
reflections. Before the network is running you should be able to verify this with a
simple DMM. You should measure about 60Ω total. (Two 120 resistors in parallel)
4. Terminals 13 (A-) & 14 (B+) connections will be connected to the twisted wire pair
in the center of the cable.
5. The cable shield wire needs be connected terminal 15. It’s better if it is not connected
to Earth ground. However, some other Modbus devices on your network may already
Earth grounded this shield. This is still acceptable, but it best that this device is near
the master.
6. Wires between Modbus devices need to be wired in a daisy-chain pattern. They
should never be wired with separate home-runs back to the master in a Star pattern.
When daisy chaining the Modbus A/B wires you should either twist the wires
together and solder or use a crimp ferrule, this would still allow the bus to be
connected even if the meter A/B wires were disconnected.
7. Keep the wires as short as possible inside the enclosure and maintain the wire twist as
much as possible.
8. The meter enclosure should always be Earth grounded. This prevents Electrostatic
and Electromagnetic noise from interfering with the meter’s microprocessor or the
RS485 common
RS485 A
RS485 B
9
Modbus data. In addition, it also provides for safety, EMI, RFI, and ESD protection.
Both the main and remote (if E4 option ordered) enclosures should be connected to
earth ground, see below for more details.
A. External Earthing: The external earthing connections are located on the boss on
the outside of both the main housing and remote housing (E4 option if ordered)
and consist of an 18-8SS pan head Phillips screw (10-24 UNC-2B thread) and a
serrated tooth #10 ring terminal for 16-14 AWG wire.
B. Internal Earthing: The internal earthing connection is located in the main housing
terminal side and consist of an 18-8SS pan head Phillips screw (10-24 UNC-2B
thread) and a serrated tooth #10 ring terminal for 16-14 AWG wire.
General 2-Wire Topology RS-485 Network
Modbus-RTU uses a common 2-wire RS-485 network for its physical layer. RS485 is simple
and robust. For short wire runs and lower baud rates it is very forgiving.
RS-485 only specifies electrical characteristics of the Master and the Slave. It does not
specify or recommend any communications protocol or Data Link layer. Unlike proprietary
RS-485 based field buses; Modbus uses the same Data Link layer used by PCs. This allows
you to be able to use cheap USB to RS485 adapters as a Modbus master.
The RS485 bus needs to be wired in a daisy chain pattern between devices. If stub wires are
necessary, they cannot be more the 10 cm long.
10
Cable
It is recommended to use shielded twisted pair type of cable (reduces radiated and received
EMI). Use a 24 AWG shielded twisted pair cable, with low capacitance like Belden 9841.
Terminator
Reflections in a transmission line can cause communication errors. To minimize the reflection
it is required to place 120Ω terminator resistors at both ends of the cable. Never place a
terminator resistor somewhere along the cable. Some Gateways, PLCs, and other types of
Modbus masters have terminator resistors built-in. If so, do not add another one. Using an
Oscilloscope you can see what a reflection looks like, and how it can confuse the data:
Not terminated Properly Terminated
Line Polarization
RS485 has 3 voltages levels, “1” , “0” , and idle. In noisy environments it may be necessary to
polarize the lines to ensure that the idle stays low so all the slave devices on the network stay
in the listen mode, waiting for their address to be called.
Most master devices have this already built in. In very noisy cases you may need make circuit
do this. However, a commercially available isolated RS485 repeater in the middle of your
wire run will “clean up” the signals and polarize the idle voltage. This is also very useful for
long wire runs. A repeater also allows you to add another 32 devices
Shield Wire Grounding
We use a RS485 chip that has 1,500 Volts of isolation. For electrical noise it’s best to keep
the shield wire isolated from Earth ground and only connect it to terminal 15 and the signal
ground at the Master.
Occasionally, you may have no choice but share the Modbus network with a device that has a
non-isolated RS485 chip. Usually you can get by with this. It is best for this non-isolated
device to be the first device on the network Master. If you still have trouble, you may need to
use an isolated RS485 repeater to separate it from the rest of the network.
Caution!
If you use a shielded 2-wire twisted pair cable you can connect the RS-485
to the shield, but do not also connect it to earth ground.
11
Communicating
Once the flow meter is wired to the network and powered up, it is time to communicate with
it. The factory default settings for the Modbus interface are as follows:
ID code = 1
Baud rate = 19200
Parity = Even
Number of bits = 8
Stop bit = 1
Delay between receiving and transmitting = 8 ms
The above Modbus settings are the factory defaults and can be changed. Changes can be done
through the Boot loader. See Setup Firmware on page 25.
Data Format Type for Various Registers
The following data types are used in 2 byte 16 bit registers:
32 bit real: IEEE 754 floating point, low word first
16 bits un-signed integer: unsigned integer values
16 bits ASCII: ASCII encoded characters, high word = 1
st
character (0x4944 = “ID”)
Modbus Function codes used
If you are using Modbus software that uses register numbers it automatically assigns the
proper function code. If you are using PDU address you’ll need the function codes.
Function
Sub Function
Description
0x03
N/A
Read holding registers
0x04
N/A
Read input registers
0x06
N/A
Write single holding register
0x08
Diagnostics
0x00
Return query data
0x01
Restart communications option
0x02
Return diagnostics Register
0x04
Force listen only mode
0x0A
Clear counters
0x0D
Return bus exception error count
0x0E
Return slave message count
0x11
Return slave busy count
12
Modbus Registers Overview
PDU
Address
Register
Description
Read/
Write
Type
No.
registers*
$00
40001
Actual flow - low word
R
32 bits real
2
$01
40002
Actual flow - high word
R
$02
40003
Actual temp - low word
R
32 bits real
2
$03
40004
Actual temp - high word
R
$04
40005
Actual pressure - low word
R
32 bits real
2
$05
40006
Actual pressure - high word
R
$06
40007
Actual total - low word
R
32 bits real
2
$07
40008
Actual total - high word
R
$08
40009
Alarm status
R
integer
1
$09
40010
Gas name
R
16 bits ASCII
8
~
$10
40017
$11
40018
Gas index
R/W
integer
1
$12
40019
Flow units
R
16 bits ASCII
4
~
$15
40022
$16
40023
Flow unit - index
R/W
integer
1
$17
40024
User full scale low word
R/W
32 bits real
2
$18
40025
User full scale high word
R/W
$19
40026
Totalizer units
R
16 bits ASCII
2
$1A
40027
$1B
40028
Totalizer unit - index
R
integer
1
$1C
40029
Temperature units
R
16 bits ASCII
1
$1D
40030
Temperature unit - index
R/W
integer
1
$1E
40031
Pressure units
R
16 bits ASCII
4
~
$21
40034
$22
40035
Pressure unit - index
R/W
integer
1
$23
40036
Standard Temperature - low word
R/W
32 bits real
2
$24
40037
Standard Temperature - high word
R/W
$25
40038
Standard Temperature - index
R/W
integer
1
$26
40039
Standard pressure - low word
R/W
32 bits real
2
$27
40040
Standard pressure - high word
R/W
$28
40041
Standard pressure - index
R/W
integer
1
$29
40042
Normal Temperature - low word
R/W
32 bits real
2
$2A
40043
Normal Temperature - high word
R/W
$2B
40044
Normal Temperature - index
R/W
integer
1
$2C
40045
Normal pressure - low word
R/W
32 bits real
2
$2D
40046
Normal pressure - high word
R/W
$2E
40047
Normal pressure - index
R/W
integer
1
$2F
40048
Adjust DAC for flow 4mA
R/W
integer
1
$30
40049
Adjust DAC for flow 20mA
R/W
integer
1
$31
40050
Adjust DAC for Temperature 4mA
R/W
integer
1
$32
40051
Adjust DAC for Temperature 20mA
R/W
integer
1
$33
40052
Adjust DAC for pressure 4mA
R/W
integer
1
$34
40053
Adjust DAC for pressure 20mA
R/W
integer
1
$35
40054
Temperature 4mA value low word
R/W
32 bits real
2
$36
40055
Temperature 4mA value high word
R/W
$37
40056
Temperature 20mA value low word
R/W
32 bits real
2
$38
40057
Temperature 20mA value high word
R/W
$39
40058
Pressure 4mA value low word
R/W
32 bits real
2
$3A
40059
Pressure 4mA value high word
R/W
$3B
40060
Pressure 20mA value low word
R/W
32 bits real
2
$3C
40061
Pressure 20mA value high word
R/W
$3D
40062
Alarm active
R/W
integer
1
$3E
40063
Alarm mode
R/W
integer
1
13
$3F
40064
Low alarm flow trig low word
R/W
32 bits real
2
$40
40065
Low alarm flow trig high word
R/W
$41
40066
High alarm flow trig low word
R/W
32 bits real
2
$42
40067
High alarm flow trig high word
R/W
$43
40068
Low alarm temp trig low word
R/W
32 bits real
2
$44
40069
Low alarm temp trig high word
R/W
$45
40070
High alarm temp trig low word
R/W
32 bits real
2
$46
40071
High alarm temp trig high word
R/W
$47
40072
Low alarm pressure trig low word
R/W
32 bits real
2
$48
40073
Low alarm pressure trig high word
R/W
$49
40074
High alarm pressure trig low word
R/W
32 bits real
2
$4A
40075
High alarm pressure trig high word
R/W
$4B
40076
Low alarm total trig low word
R/W
32 bits real
2
$4C
40077
Low alarm total trig high word
R/W
$4D
40078
High alarm total trig low word
R/W
32 bits real
2
$4E
40079
High alarm total trig high word
R/W
$4F
40080
Pipe diameter low word
R/W
32 bits real
2
$50
40081
Pipe diameter high word
R/W
$51
40082
Pipe roughness
R/W
integer
1
$52
40083
Pipe diameter units - index
R/W
integer
1
$53
40084
Flow correction low word
R/W
32 bits real
2
$54
40085
Flow correction high word
R/W
$55
40086
Totalizer enable
R/W
integer
1
$56
40087
Totalizer buck low word
R/W
32 bits real
2
$57
40088
Totalizer buck high word
R/W
$58
40089
Totalizer pulse width
R/W
integer
1
$59
40090
Totalizer reset
R/W
integer
1
$5A
40091
Password
R/W
integer
1
$5B
40092
Standard temperature units
R
16 bits ASCII
1
$5C
40093
Normal temperature units
R
16 bits ASCII
1
$5D
40094
Standard pressure units
R
16 bits ASCII
4
~
$60
40097
$61
40098
Normal pressure units
R
16 bits ASCII
4
~
$64
40101
$65
40102
Pipe diameter units
R
16 bits ASCII
2
$66
40103
$67
40104
Pipe roughness description
R
16 bits ASCII
5
~
$6B
40108
$6C
40109
Alarm status
R
16 bits ASCII
2
$6D
40110
$6E
40111
Alarm active
R
16 bits ASCII
2
$6F
40112
$70
40113
Alarm mode
R
16 bits ASCII
3
~
$72
40115
$73
40116
Serial number
R
16 bits ASCII
4
~
$76
40119
$77
40120
Firmware version
R
16 bits ASCII
4
~
$7A
40123
$7B
40124
Calibration date
R
16 bits ASCII
5
~
$7F
40128
$80
40129
PCA version
R
16 bits ASCII
3
~
$82
40131
14
Registers Explained
The registers are divided into two groups. The first group (40001 40009) represents the
dynamic data that changes the most of the two groups. The second group (40010 40131)
contains the settings in the flow meter.
Register Descriptions
40001: Actual Flow
The actual flow as measured by the instrument.
40003: Actual Temperature
The actual gas temperature as measured by the instrument.
40005: Actual Pressure
The actual pressure as measured by the instrument (if applicable).
40007: Actual Total
The actual flow total as accumulated by the instrument.
40009: Alarm Status
Value representing the status of the alarm:
0 Alarm of Off/Inactive
1 Alarm is On/Active
40010 - 40017: Gas Name
40010-40017 Registers are an ASCII string showing the name of the currently selected gas.
Use register 40018 to select a different gas.
40018: Gas Index
Value indicates which gas is selected on the instrument. The value can range between 0 and 3.
0 is always Air and 1-3 are the alternate gases.
40019: Flow Units
ASCII string shows the currently selected flow engineering unit on the instrument. Use
Register 40023 to select a different flow unit
40023: Flow Unit Index
This value shows which flow unit is selected on the instrument. The value can range between
0 and 159:
Mass Flow Units:
Caution!
Exceeding the numbers of suggested registers will raise an exception
code.
Caution!
To fully understand the registers and their functions, we suggest you also
read the InnovaMass instruction manual.
15
0 - SCFS
1 - SCFM
2 - SCFH
3 - SCFD
4 - SCFY
5 - MSCFS
6 - MSCFM
7 - MSCFH
8 - MSCFD
9 - MSCFY
10 - MMSCFS
11 - MMSCFM
12 - MMSCFH
13 - MMSCFD
14 - MMSCFY
20 - NCFS
21 - NCFM
22 - NCFH
23 - NCFD
24 - NCFY
25 - SM3/sec
26 - SM3/min
27 - SM3/hr
28 - SM3/day
29 - SM3/yr
35 - NM3/sec
36 - NM3/min
37 - NM3/hr
38 - NM3/day
39 - NM3/yr
40 - SLPS
41 - SLPM
42 - SLPH
43 - SLPD
44 - SLPY
50 - NLPS
51 - NLPM
52 - NLPH
53 - NLPD
54 - NLPY
55 - Lbs/sec
56 - Lbs/min
57 - Lbs/hr
58 - Lbs/day
59 - Lbs/yr
100 - Ston/sec
101 - Ston/min
102 - Ston/hr
103 - Ston/day
104 - Ston/yr
105 - Lton/sec
106 - Lton/min
107 - Lton/hr
108 - Lton/day
109 - Lton/yr
110 - Mton/sec
111 - Mton/min
112 - Mton/hr
113 - Mton/day
114 - Mton/yr
115 - Gram/sec
116 - Gram/min
117 - Gram/hr
118 - Gram/day
119 - Gram/yr
120 - Kg/sec
121 - Kg/min
122 - Kg/hr
123 - Kg/day
124 - Kg/yr
Volume Flow Units:
15 - ACFS
16 - ACFM
17 - ACFH
18 - ACFD
19 - ACFY
30 - AM3/sec
31 - AM3/min
32 - AM3/hr
33 - AM3/day
34 - AM3/yr
45 - ALPS
46 - ALPM
47 - ALPH
48 - ALPD
49 - ALPY
60 - Gal/sec
61 - Gal/min
62 - Gal/hr
63 - Gal/day
64 - Gal/yr
65 - MilG/sec
66 - MilG/min
67 - MilG/hr
68 - MilG/day
69 - MilG/yr
70 - ImpG/sec
71 - ImpG/min
72 - ImpG/hr
73 - ImpG/day
74 - ImpG/yr
75 - bbl/sec
76 - bbl/min
77 - bbl/hr
78 - bbl/day
79 - bbl/yr
80 - lit/sec
81 - lit/min
82 - lit/hr
83 - lit/day
84 - lit/yr
85 - MilL/sec
86 - MilL/min
87 - MilL/hr
88 - MilL/day
89 - MilL/yr
90 - m3/sec
91 - m3/min
92 - m3/hr
93 - m3/day
94 - m3/yr
95 - ft3/sec
96 - ft3/min
97 - ft3/hr
98 - ft3/day
99 - ft3/yr
150 - bl/s
151 - bl/m
152 - bl/h
153 - bl/d
Mass Velocity:
125 - SFPS
126 - SFPM
127 - SFPH
128 - SFPD
129 - SFPY
140 - NMPS
141 - NMPM
142 - NMPH
143 - NMPD
144 NMPY
145 - NMPS
146 - NMPM
147 - NMPH
148 - NMPD
149 - NMPY
Actual Velocity:
130 - FPS
131 - FPM
132 - FPH
133 - FPD
134 - FPY
135 - MPS
136 - MPM
137 - MPH
138 - MPD
139 - MPY
154 - In/sec
155 - In/min
156 - In/min
157 - In/hr
158 - In/day
159 - In/yr
16
40024: User Full Scale
Register 40024 is the “4-20 Flow Out” full scale value. Changing this only affects the 4-20
flow output and will not affect the Modbus data.
40026: Totalizer Flow Units
ASCII string shows the currently selected totalizer unit on the instrument. The unit is linked
to the flow unit. Changing the flow unit will change the totalizer unit.
40028: Totalizer Unit Index
Value shows which unit is selected on the instrument (read only). These correspond with the
Flow Unit Index with the integral time stripped off. Examples: 1= SCFM flow unit or SCF
total unit, 2= SCFH flow unit or SCF total unit.
40029: Temperature Unit
ASCII data string shows the currently selected temperature unit on the instrument. Use
Register 40030 to select a different unit.
40030: Temperature Unit Index
Value shows which temperature unit is selected on the instrument:
0 F
1 C
2 K
3 R
40031: Pressure Unit
ASCII string shows the currently selected pressure unit on the instrument. Use register 40035
to select a different unit
40035: Pressure Unit Index
Value shows which pressure unit is selected on the instrument:
0 PSIA
1 PSIG
2 Bar A
3 Bar G
4 KPa A
5 KPa G
6 Kg/Cm2 A
7 Kg/Cm2 G
8 In H2O A
9 InH2O G
10 MM H2O A
11 MM H2O G
40036: Standard Temperature
Value shows the standard temperature.
Warning!
The totalizer only works when Flow units are chosen; it will not work when if
Velocity units are selected.
17
40038: Standard Temperature Unit Index
Value shows which temperature unit is selected as standard temperature:
0 F
1 C
2 K
3 R
40039: Standard Pressure
Value shows the standard pressure.
40041: Standard Pressure Index
Value shows which pressure unit is selected as the standard pressure:
0 PSIA
1 PSIG
2 Bar A
3 Bar G
4 KPa A
5 KPa G
6 Kg/Cm2 A
7 Kg/Cm2 G
8 In H2O A
9 InH2O G
10 MM H2O A
11 MM H2O G
40042: Normal Temperature
Value shows the normal temperature.
40044: Normal Temperature Unit Index
Value shows which temperature unit is selected as the normal temperature:
0 F
1 C
2 K
3 R
40045: Normal Pressure
Value shows the normal pressure.
40047: Normal Pressure Index
Value shows which pressure unit is selected as the normal pressure:
0 PSIA
1 PSIG
2 Bar A
3 Bar G
4 KPa A
5 KPa G
6 Kg/Cm2 A
7 Kg/Cm2 G
8 In H2O A
9 InH2O G
10 MM H2O A
11 MM H2O G
40048: Flow 4MA Tuning
DAC value that represents 4 mA for the flow output
40049: Flow - 20MA Tuning
DAC value that represents 20 mA for the flow output
40050: Temperature - 4MA Tuning
DAC value that represents 4 mA for the temperature output
40051: Temperature - 20MA Tuning
DAC value that represents 20 mA for the temperature output
40052: Pressure - 4MA Tuning
DAC value that represents 4 mA for the pressure output
40053: Pressure - 20MA Tuning
DAC value that represents 20 mA for the pressure output
Caution!
Registers 40048 to 40060 only affect the three 4-20mA outputs on the meter, and
have no effect on the Modbus data.
19
40054: Temperature - 4MA Value
Temperature value that 4mA equals
40056: Temperature - 20MA Value
Temperature value that 20mA equals
40058: Pressure - 4MA Value
Pressure value that 4mA equals
40060: Pressure - 20MA Value
Pressure value that 20mA equals
40062: Alarm Active
Value indicates which alarm is active (see below).
0 - Off
1 - Always On (use this to test the alarm circuit)
16 - Flow
32 - Pressure
64 - Temperature
128 Totalizer
40063: Alarm Mode
Value indicates the mode of the current active alarm (flow, temperature, pressure or
totalizer):
0 Alarm set to “Low” mode
1 Alarm set to “High” mode
2 Alarm set to “Window”
The Window Mode (2) is a combination of both “Low” and “High” alarm modes working
together. You will need to provide both “Low” and “High” threshold values for this mode to
work correctly. Example: If the “Low” is set to 10 and the “High” is set to 20, the alarm will
only be active below 10 and above 20.
40064: Flow Low Alarm Threshold
Value at which the low alarm is triggered
40066: Flow High Alarm Threshold
Value at which the high alarm is triggered
40068: Temperature Low Alarm Threshold
Value at which the low alarm is triggered
40070: Temperature High Alarm Threshold
Value at which the high alarm is triggered
40072: Pressure Low Alarm Threshold
Value at which the low alarm is triggered
Caution!
Only one alarm can be active when the instrument is online.
20
40074: Pressure High Alarm Threshold
Value at which the high alarm is triggered
40076: Total Low Alarm Threshold
Value at which the low alarm is triggered
40078: Total High Alarm Threshold
Value at which the high alarm is triggered
40080: Pipe Diameter
Value of the pipe diameter will be in the units that are currently active.
40082: Pipe Roughness
Value indicates the pipe material:
0 PVC
1 Glass
2 Stainless steel-smooth
3 Stainless steel -normal
4 Stainless steel -rough
5 Carbon steel -smooth
6 Carbon steel -normal
7 Carbon steel -rough
8 Carbon-fiber
9 Cast-iron
10 Concrete
40083: Pipe Diameter Units
Value indicates the current pipe diameter units:
0 Inches
1 Feet
2 Millimeters
3 Meters
40084: Flow Correction
This value is used to alter the flow reading (default = 1.0)
40086: Enable Totalizer
Enable or disable the totalizer:
0 = off
1 = on
40087: Totalizer Units Per Pulse
This is the value that determines when the totalizer output will pulse. Maximum frequency of
the pulse output is 1 Hz.
40089: Totalizer Pulse Output Width
Value which indicates the pulse width of the pulse output:
0 Off
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Sierra InnovaMass 240i/241i Modbus Instrukcja obsługi

Typ
Instrukcja obsługi
Ten podręcznik jest również odpowiedni dla