PowerWalker VFI 30000 TP 3/3 BI Instrukcja obsługi

Kategoria
Zasilacze bezprzerwowe (UPS)
Typ
Instrukcja obsługi

Niniejsza instrukcja jest również odpowiednia dla

PowerWalker VFI 3/3 Series
VFI 30000TP/40000TP 3/3 BE/BI
380/400/415V 50/60Hz
(3-phase input/output)
User Guide
EN, PL
EN
©2013 BlueWalker GmbH
All Rights Reserved
The contents of this manual are the copyright of the publisher and may not be
reproduced (even extracts) unless permission granted. Every care has been
taken to ensure the accuracy of the information contained in this manual, but
no liability can be accepted for any errors or omission. The right to make design
modications is reserved.
4.1 Delivery check………………………………………………………………………
4.2 Unpacking and visual inspection………………………………
4.3 Planning before installation………………………………………………………
4.4 Cabinet installation…………………………………………………
4.5 Maintenance Bypass Switch (MBS) …………………………………………
User Guide UPS 30/40kVA B, 380/400/415V, 50/60 Hz
(3-phase input/3-phase output)
614-09946-01
Safety instructions.....……………………………………………………....………..
1.1 Safety caution.....………………….....………………….....………………….....
1.2 Audience caution.....………………….....………………….....………………
1.3 CE marking.....………………….....………………….....……………….....
1.4 User precaution.....………………….....………….....……………
1.5 Environment.....……………….....……………….....……………….....
1.6 Inquiries.....……………….....……………….....……………….....……
Introduction..........................................…………………………….....………………
2.1 System description.....………………….....………………….....………………
2.2 Basic system configuration.....……………….....……………….....……
2.3 Panel fi
gure.....………………….....……………….....………………….....
2.4 Exterior figure.....………………….....……………….....………………….....
Technical data…………………………………………….……………….....…………
3.1 Standards……………………………………………………………
3.2 Environment……………………………………………………………
3.3 Dimensional drawings…………………………………………………
3.4 Characteristics………………………………………………
3.5 AC input……………………………………………………………………………
3.6 DC circuit……………………………………………………………………………
3.7 AC output……………………………………………………………………………
3.8 Battery and charger………………………………………………………………
Mechanical installation......………………………………………………
1.
2.
3.
4.
01
01
01
02
02
03
03
04
04
05
05
06
08
08
08
08
09
09
09
10
11
11
11
13
14
14
10
PDF created with pdfFactory Pro trial version www.pdffactory.com
Contents
EN
Recycling the used UPS or battery………………………………………………
Maintenance……………………………………………………………………………
Parallel systems………….…………………………………………………
8.
9.
10.
Electrical installation…………………………………..............………………………
5.1 Electrical Preparations……………………………………………………………
5.2 Installation and wire connection diagram………………………………………
5.3 Suggested cable and protective devices……………………………………
5.4 Internal Battery Installation……………………………………………
5.5 Connecting the external battery………………………………………………
5.6 Connections between battery c
abinet and UPS………………………………
5.7 Handling the batteries……………………………………………………………
5.
Software and connectivity……………………………………………………………
User operations………………………………………………………
6.
7.
7.1 Single machine operation…………………………………………
7.2 Parallel machine operation………………………………………………………
8.1 Battery Maintenance………………………………………………………………
8.2 Regular service/intervals…………………………………………………………
8.3 Cooling fan…………………………………………………………………………
11.
Display reference Table…………………………………………………………
21
21
21
24
26
34
35
37
40
40
48
51
51
53
54
56
57
36
53
PDF created with pdfFactory Pro trial version www.pdffactory.com
1
1 Safety instructions
Warning!
Operations inside the UPS must be performed by a service engineer from the manufac-
turer or from an agent authorised by the manufacturer.
1.1 Safety caution
Use the optional Maintenance Bypass Switch (MBS) for service inside the UPS when in-
stalled to the system. Remember to open battery cabinet(s) breaker. Always ensure by mea-
suring with a multimeter that no dangerous voltages are present. For detailed MBS opera-
tion instructions please see 4.5.
This user manual contains important safety instructions and operating instructions. Please
read the user manual carefully before operating or working on the UPS and save it for refer-
ence in the future.
The UPS operates with external AC mains, battery cabinet(s) or bypass power. It contains
components that carry hazardous voltages and high currents, The properly installed enclo-
sure is earthed and IP20 rated against electrical shock and foreign objects. The user is not
permitted to open it. Failure to observe this could result in electric shock risk.
Only qualied personnel is allowed to install and service the UPS.
1.2 Audience caution
The intended audiences of this manual are people who plan the installation, install, com-
mission, and use or service the UPS. The manual provides guidelines to check delivery,
installing and commissioning of the UPS. The reader is expected to know the fundamentals
of electricity, wiring, electrical components and electrical schematic symbols. This manual is
written for a global reader.
2
EN
1.3 CE marking
The product has the CE marking in compliance with the following European directives:
LVD Directive (Safety) 2006/95/EEC
EMC Directive 2004/108/EEC
The only user operations permitted are:
Start up and shut down the UPS, excluding the commissioning start-up.Use of the LCD con-
trol panel and Emergency Power Off (EPO) switch.Use of optional connectivity modules and
their software.The user must follow the precautions and only perform the described opera-
tions.Any deviations from the instructions could be dangerous to the user or cause acciden-
tal load loss.
Warning!
The user is not permitted to open any screws excluding connectivity plates and the
Emergency Power Off (EPO) switch. Failure to recognise the electrical hazards could
prove fatal.
Note!
This product for commercial and industrial application in the second environment Instal-
lation restrictions or additional Measures may be needed to prevent disturbances.
1.4 User precaution
Caution!
Read the manual before operating or working on the UPS.
3
1.5 Environment
The UPS must be installed according to the recommendations in this manual.Under no cir-
cumstances the UPS should be installed in an airtight room, in the presence of ammable
gases, or in an environment exceeding the specication.Excessive amount of dust in the
operating environment of UPS may cause damage or lead to malfunction. The UPS should
be always protected from the outside weather and sunshine. The recommended operating
temperature is from +15 to +20 Celsius degrees.The recommended operating humidity:20%
to 90%.
1.6 Inquiries
Address any inquiries about the UPS and battery cabinet(s) to the local office or agent
authorized by the manufacturer. Please quote the type code and the serial number of the
equipment.
4
EN
2 Introduction
2.1 System description
PowerWalker VFI 3/3 Series products are high-efficiency and high-performance, double
conversion, pure-online and three phase input and three phase output UPS, with unit
capacity ranging between 20KVA-40KVA. Categorized by capacity, the products can be
further divided into 20KVA, 30KVA and 40KVA. This series not only provides perfect solu-
tion for power source protection and successfully solves problems such as blackout, boost,
brownouts, sags, decaying, oscillation, high voltage impulse, voltage uctuations, surges,
harmonic distortion, disturbances, frequency uctuation etc, but also enhances adaptability
to complicated working environments so that the application elds is well extended to com-
puter equipments, communication equipments and other controlling equipments with good
adaptability to complicated industrial environments as well. Therefore, this series products
can be applied in a diversied multi-industries eld such as telecommunications, nancing,
transportation, government, manufacturing and energy sectors.
PowerWalker VFI 3/3 Series products are also capable of ECO mode. ECO mode means
UPS load is powered by bypass AC supply while in case of abnormal AC supply the load
will be supplied by accumulator battery after conversion through inverter. As the energy
conversion efciency reaches as high as 98% and transfer time less than 10ms under ECO
mode when there is normal AC supply, the energy saving effect of UPS is remarkable.
Remark: ECO mode is applicable only to single unit.
The product described in this manual is an Uninterruptible Power Supply (UPS). It is a true
online, continuous duty, double conversion, solid state, three-phase system, providing con-
ditioned and uninterruptible AC power to protect the end-user's load.
5
2.2 Basic system conguration
2.3 Panel gure
6
EN
2.4 Exterior view
AC: This light and inverter light will turn "green" when UPS is powered by Rectier Input;
Inverter: This light will turn "green" when UPS load is through the inverter;
Battery: This light will turn "yellow" when UPS is powered by batteries;
Bypass: This light will turn "green" when UPS load is powered by Bypass Input;
Fault: If the UPS worked under fault condition,this light would turn on and stay “red” with
continuous warning tone being given off in case of UPS abnormal function;or ash “red” with
intermittent warning tone being given off.
LCD: Display UPS commands.
:Conrm/Enter; press this button to select a menu or conrm an operation.
:PageDown; press this button to switch to next screen display under the same menu.
:PageUp; press this button to return to next screen display under the same menu.
Esc: Escape; press this button to return to previous menu or cancel a certain operation.
Remark: Refer to Chapter 12 for detailed information of LED in accordance with UPS
condition.
Exterior gure of PowerWalker VFI 30000TP 3/3 BE/BI, 40000TP 3/3 BE/BI UPS
Intelligent slot
Extended slot
PARALLEL
Fan
SERVICE
RS232
RS485
EPO
AS400
LCD panel
Button
LED indicator
light
Front view Rear view
7
CHGR FAN
Front view(door open)
Battery trays
8
EN
W
×
D
×
H (mm)
3 Technical data
3.1 Standards
Product IEC62040-3:1999 and EN62040-3:2001
UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
Safety IEC62040-1:2008,EN62040-1:2003 and EN60950-1:2005
EMC IEC62040-2:2006 and EN62040-2:2005
3.2 Environment
0
℃ ~
+40
(with batteries)
Working Temperature 0
+40
Storage Temperature
Relative Humidity 5%
90%, no condensation allowed
3.3 Dimensional drawings
Altitude derating coefcient See user operations section for more detail information
-30
℃ ~
+65
(without batteries)
Vibration
IEC68-2-6; max. 0.3mm (2 to 9Hz), max. 1m/s2 (9 to 200Hz) sinusoidal
Gross Weight (Kg)
UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
470*700*1752.5 Without package
974*743*2008 With package
195 Without batteries
515 With batteries
255 Without batteries
575 With batteries
Net Weight (Kg)
470*700*1752.5 Without package
974*743*2008 With package
195 Without batteries
515 With batteries
255 Without batteries
575 With batteries
UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
9
3.5 AC input
3.4 Characteristics
VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
Noise (ISO 7779) <57dB at 75% load
Efciency-nominal load
Up to 92%
Voltage (L-N) 121V-274 Volts without using battery
Rectier input 3 phases + N
Bypass input 3 phases + N
Frequency 40-70 Hz
Rated input voltage
380V/400 V/415V
Power factor 0.99
Input distortion < 5% THD(I)
Rated input current 43A/41A/40A 57A/54A/52A
VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
Battery charging current (A)
±
4.5A
3.6 DC circuit
Battery number 2
×
16
Positive battery +192V DC
Negative battery -192V DC
Cut off voltage
Battery nominal volt-
age
154
±
2V DC(when load
2kw)
176
±
2V DC(when load
2kw)
10
EN
3.7 AC output
3.8 Battery and Charger
Internal battery package Panasonic LC-RW 1245W / CSB HR 1234WF2
Dimensions 94*151*64.5/pc(Panasonic) 94*151*65/pc(CSB)
Strings 2 x 16
Charger Input Protection 8 A fuse
Rated Charge Voltage
±
216V Default for Integrated bettery
Initial Charging Current 4.5A
Battery Leakage < 3.5mA
Battery protection
125A Breaker
Stored energy time
up to 860s At Rated liner Load,25
up to 540s At Rated liner Load,25
Restored energy time <8Hours Up to 90% charge
30A Fuse*3 For PCBA level 30A Fuse*2*3 For PCBA level
Max discharging current
87A Ubat=308VDC,Full RCD load 116A Ubat=308VDC,Full RCD load
Frequency 50/60HZ
Active power 24KW 32KW
Number of phases 3-phases + N
VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
Overload
capability
(Mains
available)
Voltage (L-N) 220/230/240 VAC
110%<Load<=125%
10 minutes minimum,
then transfer to bypass and alarm
125%<Load<=150%
Load>150%
1 minutes minimum,
then transfer to bypass and alarm
0.5 seconds minimum,
then transfer to bypass and alarm
10 minutes minimum,
then transfer to bypass and alarm
1 minutes minimum,
then transfer to bypass and alarm
0.5 seconds minimum,
then transfer to bypass and alarm
110%<Load<=125%
125%<Load<=150%
Load>150%
Overload
capability
(battery
available)
VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
11
4 Mechanical installation
4.1 Delivery check
The UPS and accessories are delivered on a specically designed pallet that is easy to
move with a forklift or a pallet jack. Keep the UPS always in upright position and do not drop
the equipment. Do not stack the pallets.
The UPS is delivered with the following items:
1. Winpower disc
2.RS-232 serial cable
3.User Guide
4.Key
5.Battery kit(wires & trays)(Only for model without batteries)
Check that there are no signs of shipping damages. The equipment should be transported in
the upright position.
Unpack the equipment by removing the packing and shipping materials. Make a visual
inspection. Remove the equipment from the pallet and make sure that the oor surface is
solid and suitable for the wheeling and heavy weight.
Remove cover plate
Remove side plate
Remove stufng and x
4.2 Unpacking and visual inspection
Note!
A claim for shipping damage must be filed immediately and the carrier must be in-
formed within 7 days of receipt of the equipment. The packing materials should be
stored for further investigation.
12
EN
Check the information on the type designation label of the equipment to verify that the unit is
of the correct type. The type designation label includes ratings, a CE marking, a type code,
a part number and a serial number. The serial number is important when making inquiries. It
allows individual recognition of the equipment.
13
Preparation for installation.
1. Avoid extremes of ambient temperature; excessive dust, moisture or vibration; ammable
gases; and corrosive or explosive atmospheres.
2.Altitude for normal UPS function should not exceed 1000m.
3.The battery cabinet should work within a temperature range from15
to 25
.
4.The maximum ambient temperature for normal UPS performance should not exceed
40
.
The equipment must be installed in upright position. The equipment requires space to front
and back to enable cooling airow. Service and maintenance require more than 500mm
clearance on right hand side. All cooling air enters at front and exits at unit rear. The re-
quired minimum clearance from unit rear to an obstruction is 400mm. Because the service
and user access is in the front there should be reserved enough space (min 800mm).
4.3 Planning before installation
14
EN
Caution!
UPS cabinet(s) can fall over if the installation brake pads are not used. Both rear and
front pads must be used to secure the UPS cabinet to the oor.
Use a 19mm wrench in clockwise direction to screw the brake pad down to the ground,
keeping the machine from moving.
4.5 Maintenance Bypass Switch(MBS)
The operation of the MBS is allowed for a service engineer from the manufacturer or from
an agent, authorised by the manufacturer. The full UPS wiring diagram with a MBS switch is
presented in the installation part of the manual.
Warning!
All operations inside the unit must be performed only by a service engineer from the
manufacturer or from an agent, authorised by the manufacturer.
4.4 Cabinet installation
The required distance for UPS units should allow for service access. The same applies to
the battery cabinet(s) that should be installed next to the UPS cabinet(s).
Note!
Please use stabilizing devices to x the UPS prior to the installation.
15
The normal positions of the MBS switches.
The switching sequence for circuit breaker from normal position to maintenance position:
16
EN
The maintenance positions of the MBS switches
2.Use LCD to turn the UPS from normal mode to bypass mode:
Switch-off action (press ESC to exit above picture)
Transfer UPS from normal mode to maintenance bypass mode:
1.The normal start position should be following:
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122

PowerWalker VFI 30000 TP 3/3 BI Instrukcja obsługi

Kategoria
Zasilacze bezprzerwowe (UPS)
Typ
Instrukcja obsługi
Niniejsza instrukcja jest również odpowiednia dla