Raychem HWAT-T55 Instrukcja instalacji

Typ
Instrukcja instalacji
HWAT-T55
nVent.com
EN Operation Manual
FR Manuel D’utilisation
DE Bedienungsanleitung
CZ Návod K Obsluze
PL Instrukcja Obsługi
2 | nVent.com
PRODUCT DESCRIPTION
The nVent RAYCHEM HWAT-T55 thermostat is
designed for RAYCHEM Self regulating cables.
The thermostat is equipped with a line sensor
and is capable of monitoring and controlling
nVent RAYCHEM HWAT-L, M and -R cables for
hot water temperature maintenance in small pipe
networks or branches up to 50 m. The thermostat
ensures maintenance of the desired hot water
pipe temperature.
PRODUCT FEATURES
Temperature control with (pipe) line sensor
DIN-Rail mountable (35 mm)
Manual ON/OFF
Easy-to-read digital display for
temperature and alarm
3 operation modes –ON/ ECO/ OFF
3 Preset-temperatures : 55°C, 50°C, 45°C; for
an easy selection by the user,
pre-set –temperatures can be modified
Built-in timer function for ECO mode
Read-out of actual pipe temperature
Monitors temperature of hot water pipe.
in the event of a sensor failure, the heating
system is switched off.
The HWAT system is controlled and monitored
by a pipe (line) sensor.
VDE approved
EN
nVent.com | 3
INSTALLATION
PRECAUTIONS!
•  Electrical installation and Commissioning must
be done by authorized personnel.
• Note: Local electrical codes must be adhered to.
Do not exceed the maximum ratings for this product.
SENSOR EXTENSION:
If you need to extend the sensor cable, use
a shielded cable type with one end of the shield
connected to a ground terminal near the controller.
Don‘t install the cable in parallel to mains voltage
wires. The sum of the wire resistance may not be
greater than 7,5 Ohms. After the power has been
switched on, the controller will display the actual
sensor temperature.
MOUNTING THERMOSTAT AND HEATING
CABLE:
HWAT-T55 is intended for mounting in a subpanel
of a flat or a building. The thermostat must be
connected to 230 VAC, and the heating cable and
earth connection need to be connected according
to the circuit diagrams. Figure C. If the current load
for K1 is greater than 10A, a connection cable with
2.5 mm² diameter must be used.
Figure
A
4 | nVent.com
(230Vac)
L
L
N
N
10
4 5 6 7 8 9
11 17 18
- +
Power
supply
K2
Alarm
K1
Heating
cable
Thermostat
HWAT-T55
Heating cable
Max
C 16A
30 mA
2A
Figure B
Figure C
nVent.com | 5
SENSOR INSTALLATION:
The NTC line sensor tip will be positioned on the
hot water pipe opposite the installed heating cable,
if possible close to the tap.
Where the pipework has a “T” section and the pipe
splits in 2 directions, the sensor should be installed
on the pipe with the lowest usage.
HWAT-T55 thermostat is compatible with the
HWAT-L, M, R self-regulating cable.
In order to guarantee the life time of the thermostat,
the maximum circuit length of heating cable is 50 m.
FUNCTIONAL DESCRIPTION
If the measured temperature drops below the
control setpoint (minus hysteresis), the control relay
switches the heating pipeline ON. The integrated
alarm relay (SPDT contact) displays an error
message in case of under temperature, sensor break
or short circuit. If malfunctioned, the control relay
will automatically switches off.
Sensor tip
HWAT- Heating cable
Cold
Lead
Sensor Line
Junction Box
55ºC
HWAT-T55
In Sub panel
6 | nVent.com
GETTING STARTED
Step 1 Step 2 Step 3
DISPLAY INFO
A-ECO Mode is activated, when blinking
B-Heating system ON
C-LED Display (Temperature and Alarm)
D-
Increase value (change of pre-set
temperature)
E-Reduce value (change of pre-set
temperatures)
F-Programme mode selection ON/
ECO/OFF
Input hour and
press P to continue
Input minute and
press P to continue
Display shows real
temperature and set
temperature alternating
A
B
D E F
C
P
2 Sec.
nVent.com | 7
SELECTING OPERATION MODE
COMFORT
The thermostat operates continuously. The
thermostat keeps the selected maintain temperature
of 55°C, 50°C or 45°C as long as the power output of
the connected HWAT heating cable is sufficient.
ECO MODE
This mode is developed in order to minimize the
energy consumption in times of few or no tap
activities, mainly during the night. The Eco Mode
reduces the maintain temperature to 50°C for a
defined time duration.
Factory settings values :
Eco mode starting time: 23:00
Eco mode duration: 6 hours
These values can be edited in the parameter
settings.
The Eco Mode can be activated at any time but it is
only active if the selected maintain temperature is
>= 55°C to ensure minimum maintain temperature
of 50°C. It will be indicated by a blinking red light.
OFF MODE
The thermostat will switch OFF the heating cable.
8 | nVent.com
SELECTING MAINTAIN TEMPERATURE
MAINTAIN TEMPERATURE
3 pre-set temperatures to maintain the pipe
temperature are implemented in the HWAT-T55
Thermostat: the default settings are 55°C, 50°C, 45°C.
The pre-set temperatures can be changed in the
parameter settings .
PARAMETER MODE
The factory settings can be changed in the
parameter mode
6 sec
Values can be changed by pressing arrow button up or down
nVent.com | 9
PARAMETER MODE NAVIGATION SET
POINTS FOR PARAMETER
SP1 = Eco mode time block
SP2 = Timer
SP3 = Pre-set-temperatures
SP4 = Sensor correction
EXIT FROM PARAMETER MODE IN
STANDARD OPERATION MODE
10 | nVent.com
SP 2 : TIMER
Input hour
Input minute
Values can be changed by pressing arrow button up or down
Values can be changed by pressing arrow button up or down
PARAMETER SETTINGS
SP 1 : ECO MODE TIME BLOCK
Start time
Default value is 23:00
Value input for full hour
Duration
Default value: 6 hours
Value input from 3 up to 8 hours
nVent.com | 11
SP 3 : PRE-SET-TEMPERATURES
3 pre-set-temperatures can be modified.
Temperature range: 40°C - 60 °C
SP 4 : SENSOR PROBE CORRECTION
The sensor probe output readings can be corrected
from -10 K to +10 K.
Example:
The real pipe temperature, measured with external
thermometer device, is 55°C. The display of the
HWAT-T55 shows only 53°C. A sensor correction of
+2K is needed.
Values can be changed by pressing arrow button up or down
Values can be changed by pressing arrow button up or down
12 | nVent.com
TROUBLE SHOOTING
Display Reasons Remedy
E01 - ERROR 1 Sensor defect Sensor contacts and sensor
resistances need to be
checked; 1)
E02 - ERROR 2 Pipe temperature
exceeds 66°C
Hot water storage
temperature needs to be
checked and changed to
value below 66°C;
Measuring
temperature 5 K
lower than the
maintain temperature
(after reaching
one time)
Hot water storage
temperature needs to be
checked and changed to
value to min. maintain
temperature
E03 - ERROR 3 n/a
E04 -ERROR 4 Device is defect Replace unit
1)  Error eliminating by 6 seconds Press P or interrupt power supply
and connect the thermostat again.If the problem still exists, replace
the unit.
nVent.com | 13
TECHNICAL DATA
Technical data
Supply voltage 230 VAC, +10%/–10%, 50 Hz
Relay output heating cable 230 VAC, max 16A
Power consumption Max. 5VA
Terminal 2,5 mm², screwed
Temperature setting range*
*consider local hygienic
standard
40- 60°C; default value is 55°C
Ambient temperature range
during transportation
–20°C to +50°C
Switching hysteresis +/–2K
Ambient temperature-range
operation
0°C to +40°C
Accuracy +/- 1,5 K including temperature probe
Rated impulse voltage 4.000 V
Programmable parameter Factory settings
3 pre-set-temperature 40°- 60°C 55°C, 50°C, 45°C
Time clock 24 hour display; 12:30
1 min interval
Eco mode duration 3 -8 hours 6 (hours)
Eco mode start point 24 hour display; 23:00
interval per hour
Housing
Color: Black
Housing dimensions 52,5 mm x 87,5mm x 58mm (H/W/D)
Material ABS
IP protection IP 20 ( IP 30 in panel)
Installation DIN rail mounted ; 35mm
Minimum installation
temperature
5°C
Control pollution degree 2
14 | nVent.com
Temperature sensor
Type Line sensor Type 202AT +/-1% NTC
2.0K @ 25°C
Cable length 10 m ( 2–wire)
Probe dimensions Diameter 5 mm, length 20 mm
Cable diameter 4 mm
Exposure temperature 0°C to +70°C
Accuracy-line sensor +/–1K
Sensor resistance Temperature in °C Resistance
KOhm
40 1,2110
45 1,0330
50 0,8854
55 0,7620
60 0,6587
65 0,5713
Approvals
CE; VDE
RoHS & REACH
nVent.com | 15
DESCRIPTION DU PRODUIT
Le thermostat nVent RAYCHEM HWAT-T55 a
été conçu pour les systèmes RAYCHEM. Ce
thermostat, qui est équipé d’une sonde de contrôle,
est capable de surveiller et de réguler les rubans
nVent RAYCHEM HWAT-L, M, R pour le maintien
en température de l’eau chaude sanitaire dans les
réseaux de tuyauteries courts ou les tuyauteries
de dérivation pouvant atteindre 50m. Il assure
le maintien en température des tuyauteries d’eau
chaude sanitaire.
CARACTÉRISTIQUES DU PRODUIT
Régulation de la température au moyen d’une
sonde de contrôle (de tuyauterie)
Montage sur rail DIN (35mm)
Fonction MARCHE/ARRÊT manuelle
Parfaite lisibilité de l’écran d’affichage
numérique de la température et des alarmes
3 modes de fonctionnement: MARCHE/ÉCO/
ARRÊT
3 températures préréglées: 55°C, 50°C et
45°C; faciles à sélectionner pour l’utilisateur;
températures préréglées modifiables
Fonction minuterie intégrée pour le mode ÉCO
Lecture de la température réelle de la
tuyauterie
Surveille la température de la tuyauterie d’eau
chaude sanitaire. En cas de panne de la
sonde, le chauffage est coupé.
Le système HWAT est régulé et surveillé par
une sonde de contrôle (de tuyauterie).
Agrément VDE
FR
16 | nVent.com
INSTALLATION
PRÉCAUTIONS
Figure A
• L’installation électrique et la mise en service doivent être
effectuées par du personnel autorisé.
• Veuillez prêter attention aux consignes de sécurité
locales!
•  Veuillez noter les valeurs nominales maximales!
RALLONGE DE LA SONDE
Si vous devez allonger les câbles de la sonde, utilisez un
câble de type blindé dont une extrémité est raccordée à une
borne de terre à proximité du régulateur. N’installez pas le
câble parallèlement aux conducteurs de tension secteur.
La somme de la résistance des conducteurs ne doit pas
dépasser 7,5Ohms. À la mise sous tension, le régulateur
affiche la température courante de la sonde.
MONTAGE DU THERMOSTAT ET DU RUBAN
CHAUFFANT
Le HWAT-T55 est prévu pour être monté dans un sous-
panneau dans un appartement ou un bâtiment. Le
thermostat doit être raccordé à un câble de 230V c.a., le
ruban chauffant et la mise à la terre doivent être raccordés
selon les schémas électriques (Figure C). Si la charge du
contacteur K1 est supérieure à 10A, un câble de diamètre de
2.5 mm² doit être utilisé.
Dimensions
amovible
nVent.com | 17
(230Vac)
L
L
N
N
10
4 5 6 7 8 9
11 17 18
- +
Alimenta-
tion
électrique
K2
Alarme
K1
Ruban
chauffant
Thermostat
HWAT-T55
Ruban chauffant
Max
C 16A
30 mA
2A
Figure B
Figure C
18 | nVent.com
INSTALLATION DE LA SONDE
La pointe de la sonde CTN sera positionnée sur la tuyauterie
d’eau chaude en face du ruban chauffant installé, si possible
à proximité du robinet.
Dans le cas d’une dérivation en T, il est recommandé
d’installer la sonde derrière la dérivation en T, sur le tuyau qui
est le plus éloigné du stockage d’eau chaude sanitaire.
Le thermostat HWAT-T55 est compatible avec les rubans
chauffants HWAT-L, M et R. Les rubans chauffants
autorégulés sont caractérisés par un courant d’appel au
démarrage. Pour garantir la durabilité du thermostat, la
charge maximale des applications autorégulées, dans les
conditions nominales, est limitée à 50m.
DESCRIPTION FONCTIONNELLE
Si la température courante baisse en dessous du point de
consigne de régulation (moins l’hystérésis), le relais de
régulation met le ruban chauffant en MARCHE. Le relais
d’alarme intégré (contact SPDT) permet de transmettre les
messages d’erreur signalant une sous-température, une
panne de sonde ou un court-circuit en cours. Pendant les
dysfonctionnements de la sonde, le relais de régulation
coupe continuellement le ruban chauffant.
Bulbe de la sonde
Ruban chauffant HWAT
Sortie
froide
Câble de la sonde
Boîte de raccordement
55ºC
HWAT-T55
Dans l’armoire secondaire
nVent.com | 19
MISE EN ROUTE
Étape1Étape2Étape3
INFORMATIONS DE LAFFICHEUR
A- Le mode ÉCO est activé
B- Le chauffage marche
C- Acheur à diodes LED (température
et alarme)
D-
Augmenter la valeur (modication de
la température préréglée)
E- Réduire la valeur (modication de la
température préréglée)
F- Sélection du mode de
programmation: MARCHE/ÉCO/
ARRÊT
Saisissez les
heures et appuyez
sur P pour conti-
nuer.
Saisissez les
minutes et appuyez
sur P pour conti-
nuer.
L’acheur indique par
alternance la tempéra-
ture réelle et le point de
consigne.
(230Vac)
L
L
N
N
10
4 5 6 7 8 9
11 17 18
- +
Alimenta-
tion
électrique
K2
Alarme
K1
Ruban
chauffant
Thermostat
HWAT-T55
Ruban chauffant
Max
C 16A
30 mA
2A
2 Sec.
20 | nVent.com
SÉLECTION DU MODE DE
FONCTIONNEMENT
CONFORT
Le thermostat fonctionne de manière continue. Il maintient la
température de maintien sélectionnée (55°C, 50°C ou 45°C)
tant que la puissance de sortie du ruban chauffant HWAT
connecté est suffisante.
MODE ÉCO
Ce mode a été développé en vue de minimiser la
consommation d’énergie en l’absence d’activité ou pendant
une période d’activité réduite du robinet, principalement
pendant la nuit. Le mode Éco diminue la température de
maintien à 50°C pendant une durée définie.
Valeur des réglages en usine:
Heure de début du mode Éco: 23h00.
Durée du mode Éco: 6heures.
Vous pouvez modifier ces valeurs dans les réglages des
paramètres.
Vous pouvez activer le mode Éco à tout moment, il ne
sera cependant activé que si la température de maintien
sélectionnée est >= 55°C pour assurer une température de
maintien minimale de 50°C. Ce mode est indiqué par un
voyant clignotant rouge.
MODE ARRÊT
Le thermostat met le ruban chauffant hors tension.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

Raychem HWAT-T55 Instrukcja instalacji

Typ
Instrukcja instalacji

w innych językach