EUROSTER 11W Instrukcja obsługi

Typ
Instrukcja obsługi
EUROSTER 11W USER MANUAL 1
EUROSTER 11W
Installation and operation manual
MANUFACTURER: P.H.P.U. AS, ul. Polanka 8a/3, 61-131 Poznań, Poland
Manual version: 11.05.2013.
1. INTRODUCTION
In order to ensure proper operation of the controller and of the CH system, please read this
manual carefully.
2. APPLICATION
EUROSTER 11W is a state-of-the-art microprocessor-based controller designed for
interoperation with Central Heating (CH) coal- and pulverized coal-fired boilers in systems
equipped with furnace blowers.
The controller measures the temperature of water in the boiler and adjusts the air flow to the
furnace and controls the operation of the CH circulation pump.
EUROSTER 11W controller is equipped with an ANTI-STOP function that prevents
seizing of an idle pump rotor. It automatically turns the pump on for 30 seconds every
14 days when the heating season is over.
Keep the controller turned on to allow the function operation after the heating season.
3. CONTROLLER FUNCTIONS
ensure smooth adjustment of the blower rotational speed
ensure optimum operation of the boiler
prevent boiler condensation (sweating)
prevent boiler overheating thermal protection
provide frost protection
provide the Anti-Stop function protection of the blower and pump against seizure
ensure comfortable presetting with a knob
perform operation tests of the pump and of the blower
provide temperature readings correction
EUROSTER 11W USER MANUAL 2
4. VISIBLE ELEMENTS
1. 230 V 50 Hz power cable of the controller
2. 230 V 50 Hz power cable of the CH pump
3. 230 V 50 Hz power cable of the blower
4. Thermal protection cable
5. Input for temperature sensor cable
6. Power switch
7. LCD
8. Knob
The display backlight turns off by default after one minute following the end of the controller
operation. The controller enables turning permanent backlight on. (section 8)
5. CONTROLLER INSTALLATION
Hazardous voltage is present inside the controller and on its output cables.
Therefore, it is absolutely forbidden to install the device prior to
disconnecting its power supply. Such installation must be performed by
qualified technicians only. Do not install a controller showing signs of any
mechanical damage.
a) mounting the controller:
using a pair of screws mount the controller box on a wall or any other supporting
structure (screw anchors with screws are supplied with the controller);
using fasteners fix controller cables to the wall.
b) fixing the sensor:
do not immerse the sensor in liquids nor install them at flue gas outlets to the
stack;
fix the sensor on the boiler in a point specially designed for that purpose or on an
unshielded outlet pipe of the CH boiler (as close to the boiler as possible);
using hose clip tighten the sensor to the pipe and cover it with thermal insulation.
c) connecting the power cable to the pump:
connect the yellow or yellow-green wire (protective cable) with the terminal ( );
connect the blue wire to the terminal (N);
connect the brown wire to the terminal (L);
d) connecting the power cable to the blower:
connect the yellow or yellow-green wire (protective cable) with the terminal ( );
connect the blue wire to the terminal (N);
connect the brown wire to the terminal (L);
e) checking the connection:
check whether the cables have been connected correctly and tighten the covers of
terminal boxes.
f) connecting the controller:
after securing the cables against any accidental rupture, connect the power cable
to a 230 V / 50 Hz socket with an earthing pin.
g) connecting the thermal protection
fix a bimetallic circuit breaker along with a temperature sensor on the boiler in a point
specially designed for that purpose or on an unshielded outlet pipe of the CH boiler (as
close to the boiler as possible);
put the bimetallic circuit breaker against the pipe (the side without 90°C label
facing the pipe), using hose clips fix it tight to the pipe and cover with thermal
insulation.
EUROSTER 11W USER MANUAL 3
Caution! Failure to meet the above requirements may result in malfunction of
the thermal protection.
Caution! The voltage of the thermal protection cable is 230 V. In case of
damage to the cable or its extension make sure to disconnect power supply
from the controller.
Ambient temperature in a place of the controller installation should not exceed
40 °C.
6. DISPLAY DESCRIPTION
Active elements of the display are presented below:
1. Name of the set parameter displayed while previewing or changing the setting
2. Boiler temperature sensor icon
3. Manual operation mode icon lit while the temperature is manually adjusted
4. Alarm icon blinks in case of alarm
5. Furnace status display see the description below
6. Blower icon lit at the time of blower operation
7. CH pump icon lit at the time of pump operation
8. Menu item number lit while previewing or changing the setting
9. Boiler temperature / Value of the displayed parameter
The furnace status is displayed in the form of animation.
Firing-up the boiler has not yet reached its preset temperature:
-> -> ->
Operation the furnace temperature is near to the preset (within the hysteresis range):
<->
EUROSTER 11W USER MANUAL 4
Blow-throughs the furnace temperature has exceeded the preset by more than at least a half
of the hysteresis value
<->
Overheating the furnace temperature > 90 °C
<->
Shutdown failure to reach the preset temperature of the boiler within an hour or the
temperature of the furnace dropped below the shutdown temperature (setting No. 10).
7. TURNING THE CONTROLLER ON
Turn the controller power switch (5) into the "I" position.
A device firmware version number and its compilation date are sequentially displayed
for 2 seconds after turning on.
The Anti-Stop function turns the pump on for 30 seconds “AS” letters are blinking on
the display.
The system status is presented at the display.
Adjust the controller settings when turning the controller on for the first time (section
9).
8. RESTORING FACTORY SETTINGS / PERMANENT LIGHT-UP OF THE DISPLAY
Proceed as follows to restore factory settings, if needed:
Keep the knob pressed and turn the controller off and on. "Fd" (Factory defaults) will
be displayed and once the knob is released, 0 will appear.
Use the knob to select the number (0 or 1) and confirm.
Selecting 0 enables to change screen backlight functions without restoring factory
defaults. Selecting 1 restores factory settings.
"bl" (Backlight) will be displayed and once the knob is released, 0 will appear.
Use the knob to select the required number (0 or 1) and confirm. Selecting 0 results in
automatic screen backlight switch off after 1 minute of finishing operating the
controller, and selecting 1 results in permanent backlight of the display.
Control and possibly correct the remaining controller settings.
In case of lack of confirmation within 5 seconds, the controller resumes operation without
introducing changes.
9. CONTROLLER SETTINGS
After being switched on the controller shows the system status. Turn the knob right to enter
the setting preview and change mode.
The controller configuration is specified below: Turn the knob in order to choose the required
parameter. The controller will show the value (at the top) and number (at the bottom). In
order to change the value of the displayed parameter, push the knob (the parameter value will
start blinking), set the required value and confirm the selection by pressing the knob. If the
current value should not be changed (cancellation of changes), do not push the knob, but wait
EUROSTER 11W USER MANUAL 5
10 seconds for the setting to stop blinking.
Setting windows are numbered for convenient operation of the controller.
The user can change the following parameters:
1. Boiler target temperature
It is the temperature of the boiler to be maintained by the controller.
2. Hysteresis of the blower operation
This is a temperature range in which the controller linearly adjusts the blower power.
The narrower the temperature range, the smaller the system temperature fluctuations.
However, a too narrow range may result in the temperature oscillation the controller
will alternately heat up and cool down the boiler.
At the time of installation, set the maximum hysteresis value. Then wait for the system
to reach the preset temperature. If, under such conditions, the blower operates at a
power level between settings No. (3) and (4), the hysteresis may be reduced.
3. Minimum power of the blower
This is the lowest power at which the blower may operate. It should be set at minimum
value at which the blower rotor starts to rotate. This value should be selected
experimentally using the blower test function (setting No. 11).
4. Maximum power of the blower
This is the highest power at which the blower may operate. The value should be
selected experimentally so that the boiler temperature maintained by the controller is
as close to the preset temperature as possible.
5. Blow-through time
This is a period of the blower operation in the blow-through mode. The blower is turned
on in order to remove combustion gases from the boiler. The blow-through time should
be long enough to effectively exhaust the gases via the stack and short enough to
prevent the boiler temperature rise.
6. Time interval between successive blow-throughs
This is the time passing between the end of the blow-through cycle and the start of a
new cycle. It should be set so that to prevent the boiler temperature rise, but on the
other hand to avoid explosive combustion of the gases generated in the boiler.
7. CH pump operation temperature
The conditions of turning the pump on and off are specified in section 12.
8. CH pump hysteresis
This is a differential temperature at which the controller turns the pump on and off.
The conditions of turning the pump on and off are specified in section 12.
9. Temperature readings correction
This is a value added to or subtracted from the measured temperature value. It enables
to compensate for the difference in readings between the sensor placed on the pipe and
the thermometer installed on the boiler.
10. Shutdown temperature
This is a temperature below which the controller turns the boiler off (the boiler furnace
is most probably shut down). A too high shutdown temperature preset may cause the
controller to turn the boiler off by mistake.
11. Blower operation / test
Displays the current status of the blower calculated by the controller (0-100 %).
Press the knob to activate testing of the output. Press the knob again or leave it
inactive for 10 seconds to resume automatic operation.
12. Pump operation / test
Displays the current status of the pump calculated by the controller (0 or 1).
Press the knob to activate testing of the output. Press the knob again or leave it
inactive for 10 seconds to resume automatic operation.
ATTENTION: In case the set values preclude the correct operation of the controller,
the alarm icon will appear on the display, and the colliding settings will be displayed
alternately. After a few seconds the last correct configuration is restored.
EUROSTER 11W USER MANUAL 6
All the settings are listed below:
Setting
Value
Numbe
r
Name
Default
Maximum
Unit
1.
Boiler target temperature
50
80
°C
2.
Hysteresis of the blower
operation
6
10
°C
3.
Minimum power of the blower
45
100
%
4.
Maximum power of the blower
100
100
%
5.
Blow-through time
10
120
s
6.
Time interval between
successive blow-throughs
6
30
min.
7.
CH system temperature
40
80
°C
8.
CH pump hysteresis
4
10
°C
9.
Temperature readings
correction
0
5
°C
10.
Shutdown temperature
35
50
°C
11.
Fan test operation
- 1)
100
(operation)
%
12.
Pump test operation
- 1)
1 (operation)
-
1) Displayed values are calculated by the algorithm.
10. FIRING-UP
During firing-up in order to heat up the boiler as fast as possible the blower is operated at its
highest power level.
The firing-up procedure may be initiated exclusively when the controller is in the
shutdown mode the blower is not running and the flame icon is not displayed.
Firing-up can be initiated in two ways:
turn the controller knob all the way to the left, then press it and hold down until the
blower is started;
turn the controller power off and on.
Firing-up is terminated if:
the boiler temperature is lower than the set temperature (1) by at most a half of the
hysteresis value (2);
within 1 hour the boiler has not reached the set shutdown temperature (setting
No. 10).
If for any reason the temperature of the shutdown boiler exceeds the set shutdown
temperature (setting No. 10), e.g. by self firing-up, then the controller will automatically
resume the normal operation mode, i.e. the pumps will not be turned off.
11. FUELING
Turn the blower off for the time the furnace is loaded with new fuel. For this purpose turn the
knob all the way to the left while the controller is in the operating mode (flame icon displayed),
then press the knob and hold it down until the flame icon disappears. The blower icon and the
hand icon are blinking alternately, which means that the blower was turned off manually; all
other algorithms are operating normally.
Proceed as above to turn the blower on. After turning the blower on again, the controller
initiates the firing-up mode (turns the pump off) in order to fire up the new batch of fuel as
soon as possible. If the fire goes out, the controller will turn the blower off.
EUROSTER 11W USER MANUAL 7
ATTENTION: The controller will not turn the blower on automatically if it was
previously manually turned off by the user.
12. CONTROLLER OPERATION
The boiler temperature is maintained by adjusting the amount of air blown and by controlling
the CH pump.
In the firing-up mode when the temperature is low and the boiler may sweat, the blower is
operating with its full power (determined by setting No. 4). Thus the firing-up period is as
short as possible.
If the boiler temperature is close to the set temperature, within the hysteresis range, the
controller adjusts the air flow smoothly. The range of the blower power control is limited by
two settings: the minimum blower power (3) and the maximum blower power (4).
Exceeding the boiler temperature results in turning into the blow-through operation. In this
operation mode the blower is started only to remove combustion gases out of the furnace.
Blow-through cycle parameters should be set so that the boiler temperature drops to the level
at which the blower operates with a linear rotational speed adjustment.
If the boiler temperature exceeds the alarm temperature, the blower is turned off
permanently. Display blinking indicates overheating.
The boiler temperature drop below the shutdown temperature setting (setting No. 10) turns
the blower off. The pump operates according to the setting (No. 7).
The CH pump is turned on if the boiler temperature exceeds the preset value by a half of the
set hysteresis T boiler TCH + HCH /2
The CH pump is turned off if the boiler temperature drops below the preset value by a half of
the preset hysteresis T boiler TCH - HCH /2
Power Alarm Temperature
In case the temperature measured by the boiler sensor exceeds the alarm temperature
(90 °C), the blow-throughs are turned off, and additionally the thermal protection feature
interrupts the blower power supply until the temperature drops to 60 °C.
Frost protection
The frost protection function is activated when the temperature of the sensor falls to 4 °C. If
the boiler sensor (CH) reaches such temperature, the CH pump is activated and "AF" letters
(Anti-Freeze) are displayed.
13. ANTI-STOP
Each time the controller is turned on, the ANTI-STOP function immediately turns the pump on
for 30 seconds (also after restoring factory defaults or change of the backlight type); later the
operation is repeated every 14 days. "AS" letters are blinking on the display while the function
is active.
Any alarm generated while the ANTI-STOP function is active (overheating or sensor damage)
suspends the function operation until the alarm is over.
14. TROUBLESHOOTING
Device does not work
Burnt fuse or ROM failure send the device to the service.
The display blinks along with the sensor icon, "Sh" or "OP" letters appear
Sensor circuit shorted (Sh) or opened (OP) check the adequate sensor cable or send the
device along with the sensors to the service.
Pump or blower does not work
Wrong connection make sure that the icons are displayed. If yes, then check the
connections.
Setting error check whether the blower is not turned off manually (section 11), check the
settings. Restore factory settings (section 8).
Thermal protection activation wait for the temperature decrease.
EUROSTER 11W USER MANUAL 8
Blower operates continuously
Time interval between blow-throughs (setting No. 6) set at 0 adjust the value.
Boiler is overheating
The blow-through time setting (5) is too long or the time interval between blow-throughs is too
short (setting No. 6) adjust the value.
The blower power too high adjust the preset values of the power of the blower (3) and (4);
throttle back the blower.
Controller emits a buzzing sound
Loose coils in the interference filter does not impact the correct operation of the device.
Controller knob operates erratically
Pulse generator damage send the device to the service.
15. SIMPLIFIED DECLARATION OF EU CONFORMITY
P.H.P.U. AS AGNIESZKA SZYMAŃSKA-KACZYŃSKA hereby declares that the type of EUROSTER
11W equipment conforms to the following directives: 2014/35/EU (LVD), 2014/30/EU (EMC),
2011/65/EU (RoHS).
The complete text of the Declaration of EU conformity is available at the following Internet
address: www.euroster.pl
16. TECHNICAL DATA
Controlled device
CH pump and blower
Supply voltage
230 V 50 Hz
Maximum pump output load
2 A 230 V 50 Hz
Maximum blower output load
0.5 A 230 V 50 Hz
Maximum power consumption
1.6 W
Temperature measurement range
from 0 °C to +110 °C
CH temperature adjustment range
from +20 °C to +80 °C
Boiler temperature adjustment range
from +40 °C to +80 °C
Temperature adjustment accuracy
1 °C
Hysteresis range
from 2 °C to 10 °C
Visual signalization
backlit LCD
Operation temperature
from +5 °C to +40 °C
Storage temperature
from 0 °C to +65 °C
Ingress protection rating
IP40
Color
black
Mounting method
wall-mounted, screw anchors
Weight of the controller with cables
0.70 kg
Length of cables
1.5 m
Standards, approvals, certificates
Conformity to EMC, LVD and RoHS
Warranty period
2 years
Dimensions (width / height / depth) mm
150 / 90 / 52
It is recommended to use fans equipped with a reactive power compensation circuit.
Feeding the controller (also in the emergency mode) with a non-sinusoidal voltage
may result in increased energy losses in the pumps and in the fan, and contribute to
malfunction of the whole system.
17. KIT CONTENTS
a) controller with 1 temperature sensor
b) sensor hose clip
c) screw anchors
d) manual
e) mounting template
EUROSTER 11W USER MANUAL 9
18. CONNECTION DIAGRAM
The following diagram is simplified and does not cover all the elements necessary for the
correct operation of the system.
1. EUROSTER 11W
2. CH boiler
3. Blower
4. Thermal protection
5. Temperature sensor
6. CH pump
7. Heat consumer radiator
19. ELECTRONIC WASTE MANAGEMENT INFORMATION
This product is designed and manufactured of high quality materials and
components suitable for reuse.
The crossed out wheelie bin symbol located at the product means that the
product is subject to selective collection in accordance with the provisions
of the Directive 2012/19/EU of the European Parliament and of the Council.
Such marking informs that the electrical and electronic equipment and
batteries may not be disposed of together with other household waste after
their service life. The user is obliged to take the used devices and batteries
to a point of collection of waste electrical and electronic equipment and batteries. The entities
collecting such equipment, including the collection points, shops, and municipal entities, set up
an appropriate system enabling handover of such equipment and batteries.
The proper disposal of waste equipment and batteries contributes to prevention
of consequences hazardous to the health of persons and nature, resulting from the possible
presence of hazardous components in the equipments and batteries and from inaccurate
storage and processing of such equipment and batteries. The guidelines regarding disposal of
the batteries are included in the user manual.
A household plays an important role in contributing to reuse and recovery including recycling,
of the waste equipment. The attitudes influencing protection of the common good of clean
environment are shaped at this level. Households are also one of the larger users of small
equipment and its rational management at this stage impacts the recovery of recyclables.
Inaccurate disposal of this product may be penalised in accordance with national legislation.
EUROSTER 11W USER MANUAL 10
WARRANTY CERTIFICATE
EUROSTER 11W
Warranty terms:
1. The warranty is valid for 24 months from the device sale date.
2. Claimed controller together with this warranty certificate must be supplied to the
seller.
3. Warranty claims shall be processed within 14 business days from the date the
manufacturer has received the claimed device.
4. The device may be repaired exclusively by the manufacturer or by other party
clearly authorized by the manufacturer.
5. Warranty becomes invalidated in case of any mechanical damage, incorrect
operation and/or making any repairs by unauthorized persons.
6. This consumer warranty does not exclude, restrict nor suspend any right of the
Buyer ensuing if the product would not meet any of the sale contract terms.
..................................................................................................................................
sale date
serial number/date of
manufacture
stamp and signature
service: telephone No.
65-571-20-12
Business entity that issued this warranty certificate is: P.H.P.U. AS Agnieszka
Szymańska-Kaczyńska, Chumiętki 4, 63-840 Krobia, Poland
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

EUROSTER 11W Instrukcja obsługi

Typ
Instrukcja obsługi

w innych językach