EDWARDS 171-4Z-D4 Instrukcja instalacji

Typ
Instrukcja instalacji
4/15/2015
171-4Z-D4 Installation Instructions Addendum
DPDT; 2 Independent SPDT Contacts
Each SPDT Switch is independent and will not switch simultaneously.
MAXIMUM Electrical Ratings
Circuit 1, Switch
SPDT
Load Rating AC 100 VA
DC 80 W
Switch Voltage AC 120V (@ 0.8A)
DC 28 V
Switching Current AC 3 A (@ 33V)
DC 3 A
Circuit 2, Switch
SPDT
Load Rating AC 100 VA
DC 80 W
Switch Voltage AC 120V (@ 0.8A)
DC 28 V
Switching Current AC 3 A (@ 33V)
DC 3 A
Sense Range
Nominal Sense Range 1.2” (3.0cm)
Nominal Break Range: 1.5” (3.8cm)
(As measured on a non-ferrous surface)
Circuits are independent and will not switch simultaneously.
Contact Resistance 1.0 ohm
10 Watt minimum switching current required.
Circuits shown with magnet actuator away from switch:
Circuit 1
COM N.O.
N.C
Circuit 2
COM N.O.
N.C