Eaton 5SC 1000i Installation and User Manual

Kategoria
Zasilacze bezprzerwowe (UPS)
Typ
Installation and User Manual

Niniejsza instrukcja jest również odpowiednia dla

5SC 500i
5SC 750i
5SC 1000i
5SC 1500i
User's guide
English - Français
Deutsch - Italiano
Español - Português
Русский - Polski
619-00470-02-i (en)
ENGLISH
Copyright © 2013 EATON
All rights reserved.
Service and support:
Call your local service representative
5SC 500i
5SC 750i
5SC 1000i
5SC 1500i
Installation
and user manual
619-00470-02-i (en)
Page 2
Certication Standards
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Information, advice, help.
UPS directives:
• Safety: IEC 62040-1: 2008
• EMC: IEC 62040-2: 2005
• Performance: IEC 62040-3: 2010
CE mark (EN 62040-1: 2008 and EN 62040-2: 2006 (C1))
Class B emission level CISPR 22: 2005 + A2 2006 (EN 55022)
Harmonics emission: IEC 61000-3-2 edition 3.2: 2009
Flickers emission: IEC 61000-3-3 edition 2: 2008
The EC Declaration of Conformity is available upon request for products with a CE mark.
For copies of the EC Declaration of Conformity, contact Eaton Power Quality or check Eaton website:
www.powerquality.eaton.com
619-00470-02-i (en)
Page 3
ENGLISH
Contents
1. Introduction ....................................................................................... 4
1.1 Environmental protection ...................................................................................................4
2. Presentation ...................................................................................... 5
2.1 Standard installation ..........................................................................................................5
2.2 Rear panels ........................................................................................................................ 5
2.3 Control panel .....................................................................................................................6
2.4 LCD description .................................................................................................................6
2.5 UPS setting through the LCD ............................................................................................6
3. Installation ........................................................................................ 7
3.1 Unpacking and contents check ..........................................................................................7
3.2 Communication ports ........................................................................................................8
4. Operation........................................................................................... 9
4.1 Start-up and Normal operation ...........................................................................................9
4.2 Starting the UPS on Battery ..............................................................................................9
4.3 UPS Shutdown ..................................................................................................................9
4.4 Operation on Battery Power ..............................................................................................9
4.5 Return of AC Input Power .................................................................................................. 9
5. Maintenance ................................................................................... 10
5.1 Troubleshooting ................................................................................................................ 10
5.2 Battery-module replacement ........................................................................................... 11
6. Appendices ...................................................................................... 12
6.1 Technical specications ....................................................................................................12
619-00470-02-i (en)
Page 4
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The 5SC range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).
Before installing 5SC, please read the booklet presenting the safety instructions.
Then follow the instructions in this manual.
To discover the entire range of EATON products and the options available for the 5SC range,
we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
1.1 Environmental protection
EATON has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50 % of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packingmaterialsarerecyclableandbeartheappropriateidenticationsymbol
01
PET
Materials Abbreviations Number in
the symbols
Polyethylene terephthalat PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing centre for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
01
PET
619-00470-02-i (en)
Page 5
ENGLISH
2. Presentation
2.1 Standard installation
D
H
W
Description Weights (kg/lb) Dimensions (mm/inch)
D x W x H
5SC 500i 6.60 / 14.60 240 x 150 x 210 / 9.4 x 5.9 x 8.3
5SC 750i 10.40 / 22.90 340 x 150 x 210 / 13.4 x 5.9 x 8.3
5SC 1000i 11.10 / 24.50 340 x 150 x 210 / 13.4 x 5.9 x 8.3
5SC 1500i 15.20 / 33.50 410 x 150 x 210 / 16.1 x 5.9 x 8.3
2.2 Rear panels
5SC 500i 5SC 750i
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
5SC 1000i 5SC 1500i
INPUT
OUTPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
(1) USB communication port
(2) RS232 communication port
(3) Outlets for connection of critical equipment
(4) Socket for connection to AC-power source
(5) Ground screw
619-00470-02-i (en)
Page 6
2. Presentation
2.3 Control panel
The UPS has a three-button LCD. It provides useful information about the UPS itself, load status, events,
measurements and settings.
AVR
%
Min
Hz
kVA
kW
6
7
8
6
ON/OFF button
7
Scroll down
8
Mute alarm
2.4 LCD description
16
15
14
17
11
10
9
12
13
9
UPS ON
10
AVR mode
11
Battery mode
12
Internal fault
13
Output load level
14
Battery level
15
Input measurements
16
Output measurements
17
Measuring unit
2.5 UPS setting through the LCD
Release scroll down button to select menu
5s 2s
2s
2s
Output voltage Alarm
Sensitivity
(1)
Example of setting
Save the new value
10s 5s 5s
• LCD will shut off if there is no activity for 3 minutes.
(1) In low sensitivity mode (Lo) UPS will tolerate more uctuations in power and will go on battery power less
often. If the connected load is sensitive to power disturbances, keep the sensitivity as Standard (Std).
619-00470-02-i (en)
Page 7
ENGLISH
3. Installation
3.1 Unpacking and contents check
1
2
3
4
5
6
(1) 5SC UPS
(2) Quick start and safety instructions
(3) User manual and IPSS (Intelligent Power Software Suite) CDROM
(4) 2 connection cables for the protected equipment
(5) RS232 communication cable
(6) USB communication cable
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
619-00470-02-i (en)
Page 8
3. Installation
3.2 Communication ports
Connection of RS232 or USB communication port
The RS232 and USB communication ports cannot operate simultaneously.
2
1
5
6
1. Connect the RS232 (5) or USB
(6) communication cable to
the serial or USB port on the
computer equipment.
2. Connect the other end of the
communication cable (5) or
(6) to the USB (1) or RS232 (2)
communication port on
the UPS.
The UPS can now communicate
with EATON power management
software.
Page 9
ENGLISH
4. Operation
4.1 Start-up and Normal operation
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. Press the
button on the UPS front panel for at least 2 seconds.
3. Check the UPS front panel display for active alarms.
If the
indicator is on, do not proceed until all alarms are cleared.
Correct the alarms and restart if necessary.
4. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected.
4.2 Starting the UPS on Battery
Before using this feature, the UPS must have been powered by utility power with output enabled at
least once.
To start the UPS on battery:
1. Press the
button on the UPS front panel until the UPS front panel display illuminates.
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
2. Check the UPS front panel display for active alarms. Resolve any active alarms before continuing.
See "Troubleshooting" on page 10.
4.3 UPS Shutdown
To shut down the UPS:
1. Press the
button on the front panel for three seconds.
The UPS starts to beep. The UPS then transfers to Standby mode, and the
indicator turns off.
4.4 Operation on Battery Power
Transfer to battery power
• The connected devices continue to be supplied by the UPS when AC input power is no longer available.
The necessary energy is provided by the battery.
• The
indicator illuminates solid.
• The audio alarm beeps every ten seconds.
The connected devices are supplied by the battery.
Low-battery warning
• The indicator illuminates solid.
• The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment because
automatic UPS shutdown is imminent.
End of battery backup time
• All the LEDs go OFF.
• The audio alarms stops.
4.5 Return of AC Input Power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart
function has been disabled) and the load is supplied again.
619-00470-02-i (en)
Page 10
5. Maintenance
5.1 Troubleshooting
Operation status Possible cause Action
Overload
Power requirement exceeds the
UPS capacity (greater than 105 % of
nominal).
Remove some of the equipment
from the UPS.The UPS continues
to operate, but may shutdown
if the load increases.The alarm
resets when the condition becomes
inactive.
Short-circuit fault
A short-circuit occurred. Check device connection or
integrity.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
Battery fault
The batteries in the UPS are
disconnected.
Verify that all batteries are properly
connected.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
The end of battery life is reached. Contact your service representative
for battery replacement.
Fan fault
The UPS has a fan fault. Check that no object is blocking the
fan.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
Charger fault The UPS has a charger fault. The UPS does not charge the
battery anymore.
Note the alarm message and
the UPS serial number, and then
contact your service representative.
619-00470-02-i (en)
Page 11
ENGLISH
5. Maintenance
5.2 Battery-module replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety precautions
are required before servicing the battery components:
• remove watches, rings, bracelets and all other metal objects from the hands and arms,
• use tools with an insulated handle.
Battery tray removal on tower models
This operation must be performed when the UPS is switched OFF, and unplugged from AC source.
A
A - Remove the front panel.
B
B - Disconnect the battery block by
separating the two connectors
(never pull on the wires).
C
C - Remove the plastic protection cover
in front of the battery (one screw).
D
D - Pull the plastic tab to remove
the battery block and replace it.
Mounting the new battery module
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by EATON.
Take care to firmly press together the two parts of the connector during remounting.
619-00470-02-i (en)
Page 12
6. Appendices
6.1 Technical specications
5SC 500i 5SC 750i 5SC 1000i 5SC 1500i
Output Power
@ 230 V
500 VA
350 W
750 VA
525 W
1000 VA
700 W
1500 VA
1050 W
AC Input power
•Rated input voltage Single phase 220-240 V
•Input voltage range 184 to 276 V
• Input frequency
range
45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
•Voltage 220/230/240 V (-10/+6 %)
(1)
•Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•Standard 1 x 12 V
9 Ah
2 x 12 V
7 Ah
2 x 12 V
9 Ah
3 x 12 V
9 Ah
Environment
• Operating
temperature range
0 to 35 °C / 32 to 95 °F
• Storage
temperature range
-15 to +40 °C / 5 to 104 °F
•Relative humidity 0 to 90 % (without condensation)
•Noise level < 40 dBA in normal mode
(1) Adjustable to 220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger Inverter
Battery
619-00470-02-i (en)
619-00470-02-i (fr)
FRANÇAIS
Copyright © 2013 EATON
Tous droits réservés.
SAV et assistance :
Contacter votre représentant SAV local
Manuel d'installation
et d'utilisation
5SC 500i
5SC 750i
5SC 1000i
5SC 1500i
Page 2
Normes de certication
Symboles spéciaux
Les symboles ci-après sont des exemples de symboles utilisés sur l'ASI ou les accessoires pour vous
avertir d'informations importantes :
RISQUE DE CHOC ELECTRIQUE - Observer l'avertissement associé au symbole de risque
de choc électrique.
Consignes à suivre impérativement.
Ne pas jeter l'ASI ni les batteries de l'ASI dans les ordures ménagères.
Ce produit contient des batteries au plomb scellées à éliminer conformément aux instructions
du présent manuel.
Pour plus d'informations, contacter votre centre local de recyclage/réutilisation de déchets dangereux.
Ce symbole indique que vous ne devez pas jeter des équipements électriques ou électroniques usagés
dans les ordures ménagères. Pour plus d'informations, contacter votre centre local de recyclage/
réutilisation de déchets dangereux.
Informations, conseils, aide.
Directives relatives aux systèmes ASI :
• Sécurité: IEC62040-1:2008
• CEM: IEC62040-2:2005
• Performances: IEC62040-3:2010
Marquage CE (EN 62040-1 : 2008 et EN 62040-2 : 2006 (C1))
Niveau d'émission classe B CISPR 22 : 2005 + A2 2006 (EN 55022)
Emission d'harmoniques : IEC 61000-3-2 édition 3.2 : 2009
Emission de scintillements : IEC 61000-3-3 édition 2 : 2008
La déclaration de conformité CE est disponible sur demande pour les produits avec un marquage CE.
Pour obtenir une copie de la déclaration de conformité CE, contacter le service Qualité de l'énergie de
la société Eaton ou consulter le site Web d'Eaton : www.powerquality.eaton.com
619-00470-02-i (fr)
619-00470-02-i (fr)
Page 3
FRANÇAIS
Table des matières
1. Introduction ....................................................................................... 4
1.1 Respect de l'environnement ..............................................................................................4
2. Présentation ...................................................................................... 5
2.1 Position standard ...............................................................................................................5
2.2 Faces arrière ......................................................................................................................5
2.3 Panneau de commande et d'afchage ..............................................................................6
2.4 Description de l'écran LCD ................................................................................................ 6
2.5 Réglage de l'ASI à l'aide de l'afcheur LCD ......................................................................6
3. Installation ........................................................................................ 7
3.1 Déballage et vérication du contenu .................................................................................7
3.2 Ports de communication .................................................................................................... 8
4. Fonctionnement................................................................................ 9
4.1 Mise en service et fonctionnement normal ....................................................................... 9
4.2 Démarrage de l'ASI sur batterie ........................................................................................9
4.3 Arrêt de l'ASI .....................................................................................................................9
4.4 Fonctionnement sur batterie .............................................................................................9
4.5 Retour du réseau électrique ..............................................................................................9
5. Maintenance ................................................................................... 10
5.1 Dépannage ...................................................................................................................... 10
5.2 Remplacement du module batterie ................................................................................. 11
6. Annexes ........................................................................................... 12
6.1 Spécications techniques ................................................................................................12
619-00470-02-i (fr)
Page 4
1. Introduction
Nous vous remercions d'avoir choisi un produit EATON pour la sécurité de vos applications.
La gamme 5SC a été élaborée avec le plus grand soin.
Pour exploiter au mieux les performances de votre ASI (Alimentation Sans Interruption),
nous vous conseillons de prendre le temps de lire ce manuel.
Avant l’installation de 5SC, lire le livret qui présente les consignes de sécurité à respecter.
Suivre ensuite les instructions du présent manuel.
Nous vous invitons à découvrir l'offre de EATON ainsi que les options de la gamme 5SC en visitant
notre site Web : www.eaton.com/powerquality, ou en contactant votre représentant EATON.
1.1 Respect de l'environnement
La société EATON s’est engagée dans une politique de protection et de préservation de l’environnement.
Nos produits sont développés selon une démarche d’éco-conception.
Substances
Ce produit ne contient ni de CFC, ni de HCFC, ni d’amiante.
Emballage
Pour améliorer le traitement des déchets et faciliter le recyclage, séparer les éléments de l’emballage.
• Le carton est composé de plus de 50% de carton recyclé.
• Les sacs et sachets sont en polyéthylène.
• Lesmatériauxconstituantl’emballagesontrecyclablesetmarquésdusymboled’identication
01
PET
.
Matériaux Abréviations Numéro dans
les symboles
Polyéthylène Téraphthalate PET 01
Polyéthylène Haute Densité HDPE 02
Polyvinyle Chloride PVC 03
Polyéthylène Basse Densité LDPE 04
Polypropylène PP 05
Polystyrène PS 06
Suivre les règlementations locales en vigueur pour l’élimination de l’emballage.
Fin de vie
LasociétéEATONs’estengagéeàtraiterlesproduitsenndevieselonlesrèglementationslocales.
EATONtravailleavecdessociétésenchargedelacollecteetdel’éliminationdenosproduitsenndevie.
Produit
Le produit est composé de matériaux recyclables. Son démantèlement et sa destruction doivent se faire
en accord avec les règlementations locales en vigueur concernant les déchets.
Leproduitenndeviedoitêtredéposédansuncentredetraitementdesdéchetsélectriques
et électroniques.
Batterie
Leproduitcontientdesbatteriesauplombquidoiventêtretraitéessuivantlesrèglementationslocales
en vigueur concernant les batteries.
Pour suivre ces règlementations et éliminer la batterie de manière propre, il est possible de l’extraire
du produit.
01
PET
Page 5
FRANÇAIS
2. Présentation
2.1 Position standard
P
H
L
Description Poids (kg/lb) Dimensions (mm/inch)
P x L x H
5SC 500i 6.60 / 14.60 240 x 150 x 210 / 9.4 x 5.9 x 8.3
5SC 750i 10.40 / 22.90 340 x 150 x 210 / 13.4 x 5.9 x 8.3
5SC 1000i 11.10 / 24.50 340 x 150 x 210 / 13.4 x 5.9 x 8.3
5SC 1500i 15.20 / 33.50 410 x 150 x 210 / 16.1 x 5.9 x 8.3
2.2 Faces arrière
5SC 500i 5SC 750i
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
5SC 1000i 5SC 1500i
INPUT
OUTPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
(1) Port de communication USB
(2) Port de communication RS232
(3) Prises pour le raccordement des équipements critiques
(4) Prise pour le raccordement au réseau électrique d’alimentation
(5) Vis de mise à la terre
619-00470-02-i (fr)
Page 6
2. Présentation
2.3 Panneau de commande et d'afchage
L'ASIcomporteunafcheurLCDàtroisboutons.Celui-cifournitdesinformationsutilessurl'ASIlui-même,
l'état de charge, les événements, les mesures et les paramètres.
AVR
%
Min
Hz
kVA
kW
6
7
8
6
Bouton MARCHE/ARRÊT
7
Défilement
8
Désactivation d'alarme
2.4 Description de l'écran LCD
16
15
14
17
11
10
9
12
13
9
ASI en fonctionnement
10
Mode AVR
11
Mode batterie
12
Défaut interne
13
Niveau de charge en sortie
14
Niveau de batterie
15
Mesures en entrée
16
Mesures en sortie
17
Unité de mesure
2.5 Réglage de l'ASI à l'aide de l'afcheur LCD
Relâcher le bouton de défilement pour sélectionner le menu
5s 2s
2s
2s
Output voltage Alarm
Sensitivity
(1)
Exemple de réglage
Enregistre la nouvelle valeur
10s 5s 5s
• L'afcheurLCDs'éteintaprès3minutesd'inactivité.
(1) En mode faible sensibilité (Lo) l'onduleur tolère plus de uctuations de l'alimentation secteur et bascule moins
souvent sur batterie. Si la charge connectée est sensible aux perturbations de l'alimentation, laissez la sensibilité
sur Normal (Std).
619-00470-02-i (fr)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124

Eaton 5SC 1000i Installation and User Manual

Kategoria
Zasilacze bezprzerwowe (UPS)
Typ
Installation and User Manual
Niniejsza instrukcja jest również odpowiednia dla

w innych językach