H3C S5560S-52P-EI Instrukcja instalacji

Kategoria
Przełączniki sieciowe
Typ
Instrukcja instalacji
H3C S5560S-EI & S5130S-HI Switch Series
Installation Guide
New H3C Technologies Co., Ltd.
http://www.h3c.com
Document version: 6W106-20200509
Copyright © 2020, New H3C Technologies Co., Ltd. and its licensors
All rights reserved
No part of this manual may be reproduced or transmitted in any form or by any means without prior written
consent of New H3C Technologies Co., Ltd.
Trademarks
Except for the trademarks of New H3C Technologies Co., Ltd., any trademarks that may be mentioned in this
document are the property of their respective owners.
Notice
The information in this document is subject to change without notice. All contents in this document, including
statements, information, and recommendations, are believed to be accurate, but they are presented without
warranty of any kind, express or implied. H3C shall not be liable for technical or editorial errors or omissions
contained herein.
Environmental protection
This product has been designed to comply with the environmental protection requirements. The storage, use,
and disposal of this product must meet the applicable national laws and regulations.
Preface
H3C S5560S-EI & S5130S-HI Switch Series Installation Guide describes the appearance,
installation, power-on, maintenance, and troubleshooting of the H3C S5560S-EI and S5130S-HI
Switch Series.
This preface includes the following topics about the documentation:
Audience.
Conventions.
Documentation feedback.
Audience
This documentation is intended for:
Network planners.
Field technical support and servicing engineers.
Network administrators working with the S5560S-EI and S5130S-HI switch series.
Conventions
The following information describes the conventions used in the documentation.
Command conventions
Convention
Description
Boldface Bold
text represents commands and keywords that you enter literally as shown.
Italic Italic text represents arguments that you replace with actual values.
[ ] Square brackets enclose syntax choices (keywords or arguments) that are optional.
{ x | y | ... }
Braces enclose a set of required syntax choices separated by vertical bars, from which
you select one.
[ x | y | ... ]
Square brackets enclose a set of optional syntax choices separated by vertical bars,
from which you select one or none.
{ x | y | ... } *
Asterisk marked braces enclose a set of required syntax choices separated by vertical
bars, from which you select a minimum of one.
[ x | y | ... ] *
Asterisk marked square brackets enclose optional syntax choices separated by vertical
bars, from which you select one choice, multiple choices, or none.
&<1-n>
The argument or keyword and argument combination before the ampersand (&) sign
can be entered 1 to n times.
# A line that starts with a pound (#) sign is comments.
GUI conventions
Convention
Description
Boldface
Window names, button names, field names, and menu items are in Boldface. For
example, the
New User
window opens; click
OK
.
>
Multi-level menus are separated by angle brackets. For example,
File
>
Create
>
Folder
.
Symbols
Convention
Description
WARNING!
An alert that calls attention to important information that if not understood or followed
can result in personal injury.
CAUTION:
An alert that calls attention to important information that if not understood or followed
can result in data loss, data corruption, or damage to hardware or software.
IMPORTANT:
An alert that calls attention to essential information.
NOTE:
An alert that contains additional or supplementary information.
TIP:
An alert that provides helpful information.
Network topology icons
Convention
Description
Represents a generic network device, such as a router, switch, or firewall.
Represents a routing-capable device, such as a router or Layer 3 switch.
Represents a generic switch, such as a Layer 2 or Layer 3 switch, or a router that
supports Layer 2 forwarding and other Layer 2 features.
Represents an access controller, a unified wired-WLAN module, or the access
controller engine on a unified wired-WLAN switch.
Represents an access point.
Represents a wireless terminator unit.
Represents a wireless terminator.
Represents a mesh access point.
Represents omnidirectional signals.
Represents directional signals.
Represents a security product, such as a firewall, UTM, multiservice security
gateway, or load balancing device.
T
T
T
T
Convention
Description
Represents a security module, such as a firewall, load balancing, NetStream, SSL
VPN, IPS, or ACG module.
Examples provided in this document
Examples in this document might use devices that differ from your device in hardware model,
configuration, or software version. It is normal that the port numbers, sample output, screenshots,
and other information in the examples differ from what you have on your device.
Documentation feedback
You can e-mail your comments about product documentation to info@h3c.com.
We appreciate your comments.
1-1
Contents
1 Preparing for installation ·········································································· 1-3
Safety recommendations ································································································································ 1-4
Examining the installation site ························································································································· 1-4
Temperature and humidity ······················································································································ 1-4
Cleanliness ·············································································································································· 1-5
EMI ·························································································································································· 1-5
Laser safety ············································································································································· 1-5
Installation tools ·············································································································································· 1-6
2 Installing the switch ·················································································· 2-6
Installing the switch in a 19-inch rack·············································································································· 2-7
Installation methods ································································································································ 2-7
Installation accessories ··························································································································· 2-9
Rack-mounting the switch by using front mounting brackets ································································ 2-10
Rack-mounting the switch by using front and rear mounting brackets ·················································· 2-11
Mounting the switch on a workbench ············································································································ 2-14
Grounding the switch ···································································································································· 2-15
Grounding the switch with a grounding strip ························································································· 2-15
Grounding the switch with a grounding conductor buried in the earth ground ······································ 2-17
Installing and removing a power module······································································································· 2-18
Installing a PSR75-12A/PSR150-A1/PSR150-D1 power module ························································· 2-18
Removing a PSR75-12A/PSR150-A1/PSR150-D1 power module ······················································· 2-19
Installing a PSR180-56A/PSR360-56A/PSR560-56D/PSR720-56A/PSR1110-56A power module ····· 2-20
Removing a PSR180-56A/PSR360-56A/PSR560-56D/PSR720-56A/PSR1110-56A power module ··· 2-21
Connecting the power cord ··························································································································· 2-22
Connecting the power cord for a PSR75-12A/PSR150-A1 power module ··········································· 2-23
Connecting the power cord for a PSR150-D1/PSR560-56D power module ········································· 2-24
Connecting the power cord for a PSR180-56A/PSR360-56A/PSR720-56A/PSR1110-56A power module
······························································································································································ 2-25
Installing and removing an expansion module ······························································································ 2-26
Installing an expansion module ············································································································· 2-26
Removing an expansion module ··········································································································· 2-27
Verifying the installation ································································································································ 2-27
3 Accessing the switch for the first time ···················································· 3-28
Setting up the configuration environment ····································································································· 3-28
Connecting the serial console cable ············································································································· 3-28
Connecting the Micro USB console cable ····································································································· 3-29
Setting terminal parameters ·························································································································· 3-31
Powering on the switch ································································································································· 3-31
4 Setting up an IRF fabric ········································································· 4-33
IRF fabric setup flowchart ····························································································································· 4-33
Planning IRF fabric setup ······························································································································ 4-34
Planning IRF fabric size and the installation site ··················································································· 4-34
Identifying the master switch and planning IRF member IDs ································································ 4-34
Planning IRF topology and connections································································································ 4-34
Identifying IRF physical ports on the member switches ········································································ 4-35
Planning the cabling scheme ················································································································ 4-36
Configuring basic IRF settings ······················································································································ 4-40
Connecting the IRF physical ports ················································································································ 4-40
Verifying the IRF fabric setup ························································································································ 4-40
5 Maintenance and troubleshooting ·························································· 5-42
Power module failure ···································································································································· 5-42
Fan tray failure ·············································································································································· 5-42
Configuration terminal display issues············································································································ 5-42
1-2
No display ············································································································································· 5-42
Garbled display ····································································································································· 5-43
6 Appendix A Chassis views and technical specifications ························· 6-44
Chassis views ··············································································································································· 6-44
S5560S-28F-EI ····································································································································· 6-44
S5560S-52F-EI ····································································································································· 6-45
S5560S-28P-EI ····································································································································· 6-46
S5560S-52P-EI ····································································································································· 6-47
S5560S-28S-EI ····································································································································· 6-48
S5560S-52S-EI ····································································································································· 6-49
S5560S-28S-PWR-EI ···························································································································· 6-50
S5560S-52S-PWR-EI ···························································································································· 6-51
S5130S-28C-HI ····································································································································· 6-52
S5130S-28S-HI ····································································································································· 6-53
S5130S-52C-HI ····································································································································· 6-54
S5130S-52S-HI ····································································································································· 6-55
S5130S-28S-PWR-HI ··························································································································· 6-56
S5130S-28S-UPWR-HI ························································································································· 6-57
S5130S-52S-PWR-HI ··························································································································· 6-58
S5130S-28C-PWR-HI ··························································································································· 6-59
S5130S-52C-PWR-HI ··························································································································· 6-60
Technical specifications ································································································································ 6-61
S5560S-EI series ·································································································································· 6-61
S5130S-HI series ·································································································································· 6-66
7 Appendix B FRUs and compatibility matrixes········································· 7-73
Compatibility matrixes ··································································································································· 7-73
Power modules ············································································································································· 7-74
Expansion modules ······································································································································· 7-75
8 Appendix C Ports and LEDs ·································································· 8-76
Ports ······························································································································································ 8-76
Console port ·········································································································································· 8-76
Management Ethernet port ··················································································································· 8-76
USB port ················································································································································ 8-76
10/100/1000BASE-T autosensing Ethernet port ··················································································· 8-77
SFP port ················································································································································ 8-77
SFP+ port ·············································································································································· 8-80
Combo interface ···································································································································· 8-82
LEDs ····························································································································································· 8-82
System status LED ································································································································ 8-82
Power module status LED ····················································································································· 8-82
Mode LED (MODE) ······························································································································· 8-83
10/100/1000BASE-T autosensing Ethernet port LED ··········································································· 8-83
SFP/SFP+ port LED ······························································································································ 8-84
Management Ethernet port LED ··········································································································· 8-84
Input status LED and output status LED on the power module ···························································· 8-84
Expansion slot LED ······························································································································· 8-84
Port status LED on the expansion module ···························································································· 8-85
9 Appendix D Cooling system ··································································· 9-86
1-3
1 Preparing for installation
This document is applicable to the S5560S-EI switch series and the S5130S-HI switch series. Table
1-1 describes models of the S5560S-EI series and the S5130S-HI series.
Table 1-1 Switch models
Series Model Product code
S5560S-EI
S5560S-28F-EI
LS-S5560S-28F-EI
LS-S5560S-28F-EI-GL
S5560S-52F-EI
LS-S5560S-52F-EI
LS-S5560S-52F-EI-GL
S5560S-28P-EI
LS-S5560S-28P-EI
LS-S5560S-28P-EI-GL
S5560S-52P-EI
LS-S5560S-52P-EI
LS-S5560S-52P-EI-GL
S5560S-28S-EI
LS-S5560S-28S-EI
LS-S5560S-28S-EI-GL
S5560S-52S-EI
LS-S5560S-52S-EI
LS-S5560S-52S-EI-GL
S5560S-28S-PWR-EI
LS-S5560S-28S-PWR-EI
LS-S5560S-28S-PWR-EI-GL
S5560S-52S-PWR-EI
LS-S5560S-52S-PWR-EI
LS-S5560S-52S-PWR-EI-GL
S5130S-HI
S5130S-28S-HI
LS-S5130S-28S-HI
LS-S5130S-28S-HI-GL
S5130S-52S-HI
LS-S5130S-52S-HI
LS-S5130S-52S-HI-GL
S5130S-28C-HI
LS-S5130S-28C-HI
LS-S5130S-28C-HI-GL
S5130S-52C-HI
LS-S5130S-52C-HI
LS-S5130S-52C-HI-GL
S5130S-28S-PWR-HI
LS-5130S-28S-PWR-EI
LS-5130S-28S-PWR-EI-GL
S5130S-28S-UPWR-HI LS-5130S-28S-UPWR-HI
S5130S-52S-PWR-HI
LS-5130S-52S-PWR-EI
LS-5130S-52S-PWR-EI-GL
S5130S-28C-PWR-HI
LS-5130S-28C-PWR-EI
LS-5130S-28C-PWR-EI-GL
S5130S-52C-PWR-HI
LS-5130S-52C-PWR-EI
LS-5130S-52C-PWR-EI-GL
1-4
Safety recommendations
To avoid any equipment damage or bodily injury caused by improper use, read the following safety
recommendations before installation. Note that the recommendations do not cover every possible
hazardous condition.
Before cleaning the switch, remove all power cords from the switch. Do not clean the switch
with wet cloth or liquid.
Do not place the switch near water or in a damp environment. Prevent water or moisture from
entering the switch chassis.
Do not place the switch on an unstable case or desk. The switch might be severely damaged in
case of a fall.
Ensure good ventilation of the equipment room and keep the air inlet and outlet vents of the
switch free of obstruction.
Make sure the operating voltage is in the required range.
To avoid electrical shocks, do not open the chassis while the switch is operating or when the
switch is just powered off.
When installing the switch, wear an ESD wrist strap and make sure it makes good skin contact
and is reliably grounded.
Examining the installation site
The switch must be used indoors. You can mount your switch in a rack or on a workbench, but make
sure:
Adequate clearance is reserved at the air inlet and outlet vents for ventilation.
The rack or workbench has a good ventilation system.
Identify the hot aisle and cold aisle at the installation site, and make sure ambient air flows into
the switch from the cold aisle and exhausts to the hot aisle.
Identify the airflow designs of neighboring devices, and prevent hot air flowing out of the
neighboring device from entering the device.
The rack is sturdy enough to support the switch and its accessories.
The rack or workbench is reliably grounded.
To ensure correct operation and long service life of your switch, install it in an environment that meets
the requirements described in the following subsections.
Temperature and humidity
Maintain temperature and humidity in the equipment room as described in "Appendix A Chassis
views and technical specifications."
Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical
property change of materials, and metal corrosion.
Lasting low relative humidity can cause washer contraction and ESD and cause problems
including loose mounting screws and circuit failure.
High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the switch.
For the temperature and humidity requirements of different switch models, see "Technical
specifications."
1-5
Cleanliness
Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points, especially when indoor relative humidity is low. In the worst
case, electrostatic adsorption can cause communication failure.
Table 1-2 Dust concentration limit in the equipment room
Substance Concentration limit (particles/m³)
Dust
3 x 10
4
(no visible dust on the tabletop over three days)
NOTE:
Dust diameter 5 μm
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion
and premature aging of components, as shown in Table 1-3.
Table 1-3 Harmful gas limits in the equipment room
Gas Maximum concentration (mg/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
EMI
All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in the following ways:
A conduction pattern of capacitance coupling.
Inductance coupling.
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE)
to filter interference from the power grid.
Keep the switch far away from radio transmitting stations, radar stations, and high-frequency
devices.
Use electromagnetic shielding, for example, shielded interface cables, when necessary.
To prevent signal ports from getting damaged by overvoltage or overcurrent caused by lightning
strikes, route interface cables only indoors.
Laser safety
WARNING!
Disc
onnected optical fibers or transceiver modules might emit invisible laser light. Do not stare into
beams or view directly with optical instruments when the switch is operating.
2-6
The switch is a Class 1 laser device.
Installation tools
No installation tools are provided with the switch. Prepare installation tools yourself as required.
ESD wrist strap
Flat-blade screwdriver
Phillips screwdriver
Needle-nose pliers
Diagonal pliers
Crimping tool
Marker
2 Installing the switch
CAUTION:
Keep the tamper
-
proof seal on a mounting screw on the chassis cover intact, and if you want to open
the chassis, contact H3C for permission. Otherwise, H3C shall not be liable for any consequence.
2-7
Figure 2-1 Hardware installation flow
Installing the switch in a 19-inch rack
Installation methods
Table 2-1 Installation methods for the S5560S-EI and the S5130S-HI switches
Chassis
Installation
methods
Installation requirements
Installation
procedure
S5560S-28F-EI
S5560S-52F-EI
S5560S-28P-EI
S5560S-52P-EI
Using front
mounting
brackets
Install the front mounting brackets at the
port side or the power module side.
See
"Rack-mounting the
switch by using front
mounting brackets."
Start
Install the switch
Ground the switch
Connect power cords
Verify the installation
Turn on the circuit breakers
Operating correctly?
Turn off the circuit
breakers
Troubleshoot the
switch
No
End
Connect interface connectors and
cables
Select and install power modules
Yes
Expansion module required?
Install the expansion module
Operating correclty?
Troubleshoot the
switch
Yes
No
No
2-8
Chassis
Installation
methods
Installation requirements
Installation
procedure
S5560S-28S-EI
S5560S-52S-EI
S5130S-28S-HI
S5130S-52S-HI
S5130S-28C-HI
S5130S-52C-HI
S5560S-28S-PWR-
EI
S5560S-52S-PWR-
EI
S5130S-28S-PWR-
HI
S5130S-28S-UPW
R-HI
S5130S-52S-PWR-
HI
S5130S-28C-PWR-
HI
S5130S-52C-PWR-
HI
Using front and
rear mounting
brackets
Install the front mounting brackets at
the port side or power module side.
Install the rear mounting brackets
according to the rack depth.
If the rack depth is in the range of
429 to 595 mm (16.89 to 23.43 in),
orient the bracket with the wide
flange inside the rack.
If the rack depth is in the range of
274 to 440 mm (10.79 to 17.32 in)
and the distance from the rear rack
posts to the inner surface of the
cabinet door is longer than 153 mm
(6.02 in), orient the bracket with the
wide flange outside the rack.
To use PSR1110-56A power modules,
do not install the switch in a rack with a
depth of 600 mm (23.62 in)
See
"Rack-mounting the
switch by using front
and rear mounting
brackets."
Figure 2-2 Procedure for rack-mounting the switch by using the front mounting brackets
Figure 2-3 Procedure for rack-mounting the switch by using the front and rear mounting
brackets
NOTE:
If a rack shelf is available, you can put the switch on the rack shelf, slide the switch to an appropriate
location, and attach the switch to the rack by using the mounting brackets.
Attach the front
mounting brackets to the
two sides of the switch
Identify the mounting position (port
side or power side) for the
mounting brackets
Mount the switch in the rack
Attach the front
mounting
brackets to the
two sides of the
switch
Attach the load
bearing screws to
the switch
Attach the
rear
mounting
brackets to
rack posts
Identify the mounting
position (port side or
power side) for the
mounting brackets
Mount the switch in
the rack
2-9
Installation accessories
Table 2-2 Installation accessories for the S5560S-EI and the S5130S-HI switches
Installation accessories
S5560S-28F-EI
S5560S-52F-EI
S5560S-28P-EI
S5560S-52P-EI
S5560S-28S-EI
S5560S-52S-EI
S5130S-28S-HI
S5130S-52S-HI
S5130S-28C-HI
S5130S-52C-HI
S5560S-28S-PWR-EI
S5560S-52S-PWR-EI
S5130S-28S-PWR-HI
S5130S-28S-UPWR-HI
S5130S-52S-PWR-HI
S5130S-28C-PWR-HI
S5130S-52C-PWR-HI
Front mounting brackets (Figure 2-4) Provided Provided
Rear mounting brackets and shoulder screws (Figure
2-5)
N/A Provided
Figure 2-4 Front mounting bracket
(1) Screw hole for attaching the bracket to the switch
(2) Screw hole for attaching the bracket to the rack
Figure 2-5 Rear mounting bracket and shoulder screw
(1) Screw hole for attaching the bracket to the rack
(2) Shoulder screw
1
2
1
2
2-10
Rack-mounting the switch by using front mounting brackets
Attaching the front mounting brackets to the switch
1. Determine the mounting position for the front mounting brackets. You can install the front
mounting brackets at the port side or the power module side.
2. Attach the front mounting brackets to the chassis:
a. Align the round holes in the wide flange of one front mounting bracket with the screw holes
in the chassis. See Figure 2-6 and Figure 2-7.
b. Use M4 screws (provided with the switch) to attach the front mounting bracket to the
chassis.
c. Repeat the proceeding two steps to attach the other front mounting bracket to the chassis.
Figure 2-6 Attaching the front mounting bracket to the port side
Figure 2-7 Attaching the front mounting bracket to the power module side
Mounting the switch in the rack
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Make sure the front mounting brackets have been attached securely to the two sides of the
switch.
3. One person supports the chassis bottom with one hand, holds the front part of the chassis with
the other hand, and pushes the chassis into the rack.
4. The other person uses M6 screws and cage nuts (user supplied) to attach the switch to the rack.
Make sure the switch is installed evenly and securely in the rack.
2-11
Figure 2-8 Mounting the switch in the rack (front mounting brackets at the port side)
Figure 2-9 Mounting the switch in the rack (front mounting brackets at the power
module side)
Rack-mounting the switch by using front and rear mounting
brackets
Attaching the front mounting brackets and shoulder screws to the switch
You can attach the front mounting brackets at the port-side or power module-side mounting position.
The following uses port-side mounting as an example. The power-side mounting is similar.
To attach the front mounting brackets and shoulder screws to the switch:
1. Align the round holes in the wide flange of one front mounting bracket with the screw holes in
the port-side mounting position on one side of the chassis. See Figure 2-10.
2-12
2. Use M4 screws (supplied with the switch) to attach the front mounting bracket to the chassis.
3. Repeat the proceeding two steps to attach the other front mounting bracket to the chassis.
4. Unpack the shoulder screws. Attach a shoulder screw to one of the two installation positions as
red-marked in Figure 2-10 at both sides of the chassis.
Figure 2-10 Attaching the front mounting brackets and shoulder screws to the chassis
Attaching the rear mounting brackets to the rack
1. Determine the switch installation position in the rack.
2. Install cage nuts in the rack posts.
3. Orient the rear mounting brackets with the wide flange inside or outside the rack as required.
4. Use M6 screws to attach the rear mounting brackets to the rear posts, as shown in Figure 2-11.
Do not fully tighten the M6 screws before mounting the switch in the rack.
Figure 2-11 Attaching the rear mounting brackets to a rack with the wide flange inside the
rack
2-13
Figure 2-12 Attaching the rear mounting brackets to a rack with the wide flange outside the
rack
Mounting the switch in the rack
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Make sure the front mounting brackets and shoulder screws are securely attached to the two
sides of the switch.
3. Attach cage nuts to the rack posts.
4. One person supports the chassis bottom with one hand, holds the front part of the chassis with
the other hand, and pushes the chassis into the rack gently.
Make sure the shoulder screws make close contact with the upper edges of the rear mounting
brackets, as shown in Figure 2-13.
5. The other person aligns the oval holes in the front brackets with the mounting holes in the front
rack posts, and attaches the front mounting brackets with M6 screws to the front rack posts.
Make sure the switch is installed securely in the rack.
2-14
Figure 2-13 Mounting the switch in the rack (with the wide flange of the rear mounting
brackets inside the rack)
Figure 2-14 Mounting the switch in the rack (with the wide flange of the rear mounting
brackets outside the rack)
Mounting the switch on a workbench
IMPORTANT:
Reserve a minimum of 10 cm (3.9 in) of clearance around the chassis for heat dissipation.
Do not place heavy objects on the switch.
2-15
To mount the switch on a workbench:
1. Verify that the workbench is sturdy and reliably grounded.
2. Place the switch with bottom up, and clean the round holes in the chassis bottom with dry cloth.
3. Attach the rubber feet to the four round holes in the chassis bottom.
4. Place the switch with upside up on the workbench.
Grounding the switch
WARNING
!
Correctly connecting the grounding cable is crucial to lightning protection and EMI protection.
As a best practice to guarantee the grounding effect, ground the switch by connecting the
grounding cable provided with the switch to the grounding strip in the equipment room.
The power input end of the switch has a noise filter, whose central ground is directly connected to the
chassis to form the chassis ground (commonly known as PGND). You must securely connect this
chassis ground to the earth to minimize the potential for system damage, maximize the safety at the
site, and minimize EMI susceptibility of the system.
You can ground the switch in one of the following ways, depending on the grounding conditions
available at the installation site:
Grounding the switch with a grounding strip
Grounding the switch with a grounding conductor buried in the earth ground
NOTE:
The power and grounding terminals in this section are for illustration only.
For more information about lightning protection, see H3C Lightning Protection Guide.
Grounding the switch with a grounding strip
WARNING
!
Connect the grounding cable to the grounding
strip
in the equipment room. Do not connect it to a fire
main or lightning rod.
If a grounding strip is available at the installation site, connect the grounding cable to the grounding
strip.
Connecting the grounding cable to the chassis
1. Remove the grounding screw from the rear panel of the switch chassis.
2. Use the grounding screw to attach the ring terminal of the grounding cable to the grounding
screw hole. Fasten the screw.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91

H3C S5560S-52P-EI Instrukcja instalacji

Kategoria
Przełączniki sieciowe
Typ
Instrukcja instalacji

w innych językach