Danfoss TP9000 Instrukcja instalacji

Kategoria
Termostaty
Typ
Instrukcja instalacji
TP9000
Electronic Programmable Room Thermostat
plus Domestic Hot Water Timer
Installation Guide
Danfoss Heating
MAKING MODERN LIVING POSSIBLE
TP9000
2
For a large print version of these instructions
please call Marketing on 0845 121 7400.
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other
printed material. All trademarks in this material are property of the respective companies.
Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss Heating
3
GB
PL
GR
GB
TP9000
Electronic Programmable Room Thermostat
plus Domestic Hot Water Timer
1.0 Basics
1.0 Product specifi cation ...................................................................4
1.1 Installation .......................................................................................5
1.2 Wiring ................................................................................................7
2.0 Installer advanced programming options
2.1 Installer advanced programming options ...........................9
2.2 Service Interval Timer ..................................................................9
2.3 Entering Installer Advanced Programming Mode ............9
Installation Instructions
TP9000
4
GB
PL
GR
GB
Please note: This product should only be installed by a
qualifi ed electrician or competent Heating installer, and should
be in accordance with the current edition of the IEEE wiring
regulations.
Specifi cation 230V model 24V model
Power supply 230 Vac, ±15%,
50/60 Hz
24 Vac, ±15%,
50/60 Hz
Switching action
2 x SPDT internally linked, Type 1BS
Unit switch rating 230 Vac, 3(1)A 24Vac, 3(1)A
Memory Backup Retained for life of product
Heat Temperature Range
Setting
5°C - 30°C
Factory Set Calendar
Clock
Automatic Summer/Winter time
change
Remote Sensor Inputs
(‘A models only)
Can be set by installer for remote sen-
sor, limited sensor, window contact,
tele-switch or outdoor sensor
Programme resolution ± 1 minute
Timing Accuracy ± 1 minute
Dimensions, mm (W, H, D) 135 x 88 x 32mm
Design standard EN 60730-2-7 +EN60730-2-9
Control Pollution Situ-
ation
Degree 2
Rated Impulse Voltage 2.5 kV
Ball Pressure Test 75°C
1.0 Product specifi cation
1.0 Basics
Danfoss Heating
5
GB
PL
GR
GB
1.1 Installation
Remove wallplate from unit by unscrewing the two screws on
the bottom edge of the unit.
From the top left hand corner of the wallplate, there must be
clearances of at least 140 mm to the right, 15mm to the left,
30mm above and 100mm below in order to mount the plug-on
module.
The wallplate must be securely mounted either directly to the
wall using suitable wood screws or to a fl ush mounted 1-gang
electrical accessory box using M3.5 screws.
Cable access can either be from behind for concealed cabling, or
from below for surface cabling. If surface cable is used, cut out
cable access slot on plug-on module prior to mounting.
For wiring connections refer to diagram on page 7.
The TP9000 is double insulated and does not require an earth
connection, however a parking terminal is provided on the
wallplate. This is clearly marked with an Earth symbol.
Prior to mounting the plug-on module, DIL switches on the
rear of the plug-on module must be set. See diagram below for
available options.
Mount plug-on module to wallplate by locating tabs on top of
wallplate in apertures on rear of module, hinge down and press
rmly to wallplate before tightening securing screws on bottom
of wallplate.
1
2
Keyboard disabled
Reset disabled Reset enabled
Keyboard enabled
OFF
ON
Sw. No.
Prior to mounting the unit the 2 DIL switches on the rear of the
unit have to be moved to the required position. The factory
presets are shown below.
TP9000
6
GB
PL
GR
GB
IMPORTANT: The supply to this unit should by wired via a double
pole isolation switch in accordance with BS EN60730-1, i.e. one
which provides air gaps of at least 3mm in both poles of the mains,
and incorporates a 3 amp fuse. It is strongly recommended that solid
conductors be used.
Clearance for
screwdriver
access
Surface fixed cable
bottom entry knockouts
Rear entry
cable access
N &
looping
terminals
Wall or
Plaster box
fitting
Terminal block
Outline of unit
30mm minimum
C/L
!
Thermostat and Remote Room Sensor:
Fix at a height of approximately 1.5m from the fl oor, away from
draughts or heat sources such as radiators, open fi res or direct
sunlight.
Danfoss Heating
7
GB
PL
GR
GB
1.2 Wiring
NOTE:
The TP9000 does not have voltage free contacts, therefore it is NOT
suitable for connection to extra low voltage equipment (i.e. > 50
Volts).
Remote Sensor to be wired with 1mm 2 core double insulated cable
only. Cable length should not exceed 50 metres. Sensor cable should
NOT be run parallel to mains cable.
Remote sensor inputs
The TP9000 incorporates an input which can be used to connect one
of the following:
1) remote room temperature sensor
2) limit sensor, for example, fl oor temperature sensor (sold as
accessory).
3) window contacts, card reader contacts, outdoor sensor (sold as
accessory) or teleswitch contacts.
See Installer Advanced Programming Options for set-up
instructions.
TP9000
8
GB
PL
GR
GB
Remote sensor inputs
Terminals 5 and 6 are the designated remote sensor inputs. These can
be found on the top right hand side of the wallplate.
5
6
Window or
teleswitch
contact
(NO or NC)
5
6
Teleswitch
contact (NC)
Window
contact (NC)
5
6
Confi gured for
remote room,
limit or outdoor
sensor
Confi gured for
window contact or
other contact such
as teleswitch
Confi gured for
window contact
and other contact
such as teleswitch
Danfoss Heating
9
GB
PL
GR
GB
2.0 Installer advanced
programming options
TP9000 incorporates a number of advanced features which can be set
by the user. These are accessed via a User Advanced Programming
Mode, please refer to User Advanced Programming in the user
instructions for details (see page 23)
2.1 Installer advanced programming options
TP9000 incorporates an additional number of advanced features
which can be set by the installer to improve the operating effi ciency
of the system and where required, to change the user functionality
of the product. These are accessed via an Installer Advanced
Programming Mode. These settings are optional and need only be
made if there is a demand for the enhanced functions.
2.2 Service Interval Timer
Instructions on how to access this feature are available from our
customer support desk. Please note these are only issued to boni-fi de
Heating installers.
2.3 Entering Installer Advanced Programming
Mode
To access the Installer Advanced Programming Mode follow the
steps below:
a) Press and hold
V and PROG for 3 seconds
to enter User Advanced Programming, the
display will change to fi gure opposite.
b) Press and hold
V, Λ and PROG for 5 seconds
to enter Installer Advanced Programming, the
display will change to fi gure opposite.
TP9000
10
GB
PL
GR
GB
c) Use + and - keys to scroll backwards and forwards between
options then
V and Λ keys to change the option settings. The
ashing digit on the right hand of the display indicates the
number of the selected option. The large characters display the
option value selected.
d) To return to RUN, press and hold PROG until the display returns
to RUN mde.
Option 30 - Set upper limit of temperature range
This allows the upper limit of the thermostat
setting range to be electronically limited. Press +
until Option 30 is displayed, use V and Λ to select
required setting.
Setting 40 - 5°C (factory setting is 30°C)
Option 31 - Set lower limit of temperature range
This allows the lower limit of the thermostat
setting range to be electronically limited. Press +
until Option 31 is displayed, use V and Λ to select
required setting.
Setting 5 - 40°C (factory setting is 5°C)
Option 32 - Enable Off at lower limit
This enables an OFF function to be selected if a
set point below the lower limit is selected. Press +
until Option 32 is displayed, use
V and Λ to select
required setting.
Setting 0 Disabled
Setting 1 Enabled (factory setting)
Option 33 - Enable On at upper limit
This enables an ON function to be selected if a set
point above the upper limit is selected. Press +
until Option 33 is displayed, use
V and Λ to select
required setting.
Setting 0 Disabled (factory setting)
Setting 1 Enabled
Danfoss Heating
11
GB
PL
GR
GB
Option 34 - Select On/Off or Chrono-proportional
This allows the thermostat to be set to run in On/Off
mode or for a chrono-proportional cycle rate to be
selected. Press + until Option 34 is displayed, use V
and Λ to select required setting.
0 On/Off
3 3 cycles per hour
6 6 cycles per hour (factory setting)
9 9 cycles per hour
12 12 cycles per hour
Option 35 - Set integration time (Option 34 set to 3, 6, 9 or 12)
(seek advice prior to adjusting)
This adjusts the integration time of the PI
algorithm to increase control accuracy. It is only
active if option 34 has been set to Chrono 3, 6,
9 or 12. It should only be adjusted after seeking
advice from the manufacturer. Press + until
Option 35 is displayed, use
V and Λ to select
required setting.
2.5 Integration time set to 2.5% (factory setting)
5 Integration time set to 5%
10 Integration time set to 10%
Option 36 - Set temperature override rule
This establishes the degree of temperature override
available to the user. Press + until Option 36 is
displayed, use
V and Λ to select required setting.
Setting 0 No limit (factory setting)
Setting 1 Limited to ±2°C
Setting 2 No override allowed
TP9000
12
GB
PL
GR
GB
Option 37 - Set time duration of override rule
(Option 36 set to 1 or 2)
This establishes the duration of a temperature
override available to the user. Press + until Option 37
is displayed, use V and Λ to select required setting.
Setting 0 Next event (factory setting)
Setting 1 1 hour
Setting 2 2 hours
Setting 3 3 hours
Setting 4 4 hours
Option 40 - Number of Events per Day (Heating)
This sets the thermostat to operate with either 2,
4 or 6 switching events per day or to run it in stat
mode. Press + until option 40 is displayed, use Λ or
V to select required setting.
1 Stat mode
2 Two switching events per day
4 Four switching events per day
6 Six switching events per day (factory setting)
Option 41 - Operating Mode (Heating) (option 40 set to 2, 4, or 6)
This sets the thermostat to operate using either
5/2 day or 24 hour mode. Press + until option 41 is
displayed, use Λ or V to select required setting.
7 7 Day programming (factory setting)
5-2 or A-B 5-2 Day programming or A-B programming
24 24 hour programming
Option 60 - Number of events per day (Hot Water)
This sets the number of Hot Water on/off switching
times per day. Press + until option 60 is displayed,
use Λ or V to select required setting.
Setting 1 1 on/off event per day
Setting 2 2 on/off events per day
Setting 3 3 on/off events per day (factory setting)
Danfoss Heating
13
GB
PL
GR
GB
Option 61 - Hot Water Event - Days per week
This sets the schedule of Hot Water on/off switching
times per week. Press + until Option 61 is displayed,
use V and Λ to select required setting.
24 24 Hour
5-2 Either 5+2 day or A+B days depending on user APM
setting
7 7 Day (factory setting)
Option 70 - Keyboard disable rules
This establishes the degree of functionality of the
keyboard available to the user. It is only active if DIL
switch 1 is set to “Disabled”. Press + until Option 70
is displayed, use V and Λ to select required setting.
Setting 0 Normal lock: Programming functions locked (factory
setting)
Setting 1 Full lock: All keys are disabled
Option 71 - Random start rules (24V/230 Volt models only)
This enables a random start on power-up following
a power cut to reduce load on the electrical network.
Random delay is in the range of 2 - 90 seconds. Press
+ until Option 71 is displayed, use V and Λ to select
required setting.
Setting 0 Disabled (factory setting)
Setting 1 Enabled
Option 72 - Owner site reference number
This enables multi-site owners to store a site
reference number in the thermostat. Press + until
Option 72 is displayed, use V and Λ to select
required setting.
Setting Any value between 00 and 99 can be set
Factory setting is 00
TP9000
14
GB
PL
GR
GB
Option 73 - Owner thermostat reference number
This enables site owners to store a thermostat
reference number in the thermostat. Press +
until Option 73 is displayed, use V and Λ to select
required setting.
Setting Any value between 000 and 999 can be set
Factory setting is 000
Option 74 - Date format for calendar clock
This allows date format to be chosen. Press +
until Option 74 is displayed, use V and Λ to
select required setting.
Setting 0 European format (dd/mm/yy), (Factory setting)
Setting 1 North American format (mm/dd/yy)
Option 80 - Enable/Disable + Hrs Boost
Enables or disables the +Hrs button. use V and
Λ to select required setting. Press + until Option
80 is displayed, use V and Λ to select required
setting.
Setting 0 +Hrs Boost button disabled
Setting 1 +Hrs Boost button enabled (factory setting)
Option 81 - Thermostat calibration bias
This allows the thermostat calibration to be
biased by up to ±1.5°C. Press + until Option 81 is
displayed, use V and Λ to select required setting.
Setting Any value between ±1.5 in 0.5°C steps (Factory setting is
0°C)
Danfoss Heating
15
GB
PL
GR
GB
Option 90 - Defi ne remote sensor type
This allows type of remote sensor input type to
be defi ned. Press + until Option 90 is displayed,
use V and Λ to select required setting.
Setting 0 No remote sensor fi tted
Setting 1 Remote room or duct sensor fi tted, internal sensor disabled
(factory setting)
Setting 2 Remote limit sensor fi tted, refer to option 93 to defi ne
set-point
Setting 3 Confi gured as digital input for window, card reader or
teleswitch, refer to option 94 to defi ne o/c or s/c.
Setting 4 Outdoor sensor fi tted internal sensor active, outdoor
sensor used for display purposes only
Option 93 - Set limit sensor set-point
(option 90 set to 2)
This allows the thermostat limit sensor to be set,
typical application is fl oor Heating. Press + until
Option 93 is displayed, use V and Λ to select
required setting. If the temperature sensed by
the limit sensor exceeds the limit setting the
output will be turned off until the temperature
has dropped by 2°C. “F10” will fl ash in the display
while the output is disabled.
Setting Any value between 20 - 50°C (Factory setting is 27°C)
Option 94 - Confi gure digital input switch type, A models only,
(option 90 set to 3)
This allows switch type of digital input to be
confi gured. Press + until Option 94 is displayed,
use V and Λ to select required setting.
Setting 0 Contacts NC, open circuit contact to force unit into
thermostat mode, short circuit contacts to return to
normal operation
Setting 1 Contacts NO, short circuit contacts to force unit into
thermostat mode, open circuit contacts to return to
normal operation (Factory setting)
TP9000
16
GB
PL
GR
PL
TP9000
Programowalny termostat pokojowy do układów
C.O. i C.W.U.
1.0 podstawowy
1.0 Instrukcja montażowa ..............................................................17
1.1 Montaż ........................................................................................... 18
1.2 Przewody ....................................................................................... 20
2.0 Zaawansowane funkcje programowane
przez instalatora
2.1 Zaawansowane funkcje programowane
przez instalatora ........................................................................ 22
2.2 Wskaźnik czasu następnego przeglądu
serwisowego ................................................................................ 22
2.3 Wejście w tryb zaawansowanych funkcji
programowanych przez instalatora ..................................... 23
Instrukcja montażu
Danfoss Heating
17
GB
PL
GR
PL
Uwaga: Urządzenie to powinno być instalowane jedynie przez
wykwalifi kowanego elektryka lub uprawnionego instalatora
urządzeń grzewczych. Montaż powinien spełniać wymagania
stawiane przez aktualne przepisy Instytutu Inżynierów
Elektryków i Elektroników (IEEE wiring regulations).
1.0 Podstawowy
Dane techniczne Model 230V Model 24V
Zasilanie 230 V~, ±15%,
50/60 Hz
24 V~, ±15%,
50/60 Hz
Przełączanie
Dwa pojedyncze przełączniki dwupozy-
cyjne, wewnętrznie połączone, typ 1BS
Dane przełącznika
urządzenia
230 V~, 3(1)A 24V~, 3(1)A
Podtrzymanie pamięci Na cały okres użytkowania urządzenia
Zakres ustawień tempera-
tury
5°C - 30°C
Zegar kalendarzowy
ustawiony fabrycznie
Automatyczna zmiana czasu z letniego
na zimowy i na odwrót
Sygnały wejściowe ze
zdalnego czujnika (tylko
modele A)
Mogą być ustawiane przez instalatora dla
zdalnego czujnika, czujnika z ogranicze-
niem, styku okiennego, teleprzełącznika
lub czujnika zewnętrznego
Skok czasowy programow-
ania
± 1 minuta
Dokładność regulatora
czasowego
± 1 minuta
Wymiary, mm (szerokość,
wysokość, grubość)
135 x 88 x 32mm
Zgodność z normą EN 60730-2-7 +EN60730-2-9
Poziom zakłóceń Stopień 2
Znamionowe napięcie
impulsowe
2.5 kV
Temperatura próby
twardości metodą Brinella
75°C
TP9000
18
GB
PL
GR
PL
1.1 Montaż
Zdjąć płytkę ścienną z urządzenia po uprzednim odkręceniu
dwóch śrub na dolnej krawędzi.
Aby zamontować moduł nasadzany, od górnego lewego rogu
płytki ściennej musi być odstęp co najmniej 140 mm w prawo,
15 mm w lewo, 30 mm w górę i 100 mm w dół.
Płytka ścienna musi być odpowiednio przymocowana, albo
bezpośrednio do ściany przy pomocy wkrętów do drewna lub
do jednobiegunowej puszki instalacyjnej przy pomocy śrub
M3,5.
Przewody można podłączyć albo od tyłu (gdy biegną w ścianie),
albo od dołu (gdy nie są schowane). Przed podłączeniem
przewodu znajdującego się na powierzchni ściany należy
wyciąć w module nasadzanym odpowiedni otwór na jego
przeprowadzenie.
Sposób podłączenia przewodów przedstawiono na diagramie
na stronie 20.
Model TP9000 jest podwójnie izolowany i nie wymaga
uziemienia. Istnieje jednak możliwość podłączenia przewodu
uziemiającego do płytki ściennej – miejsce podłączenia jest
wyraźnie oznaczone symbolem uziemienia.
Przed zainstalowaniem modułu nasadzanego należy ustawić
przełączniki DIL (dwupozycyjne) z tyłu modułu. Możliwe
warianty pokazano na diagramie poniżej.
Założyć moduł nasadzany na płytkę ścienną przez wsunięcie
wypustek na górze płytki do otworów z tyłu modułu, obrócić
go do pozycji pionowej i docisnąć mocno do płytki przed
dokręceniem śrub zabezpieczających na dole płytki.
Danfoss Heating
19
GB
PL
GR
PL
WAŻNE: Zasilanie tego urządzenia powinno odbywać się poprzez
dwuobwodowy przełącznik izolacyjny zgodny z normą BS EN60730-1,
tzn. taki, który t wor zy co najmniej trzymilimetrowe szczeliny powietrzne
na obu obwodach (fazowym i zerowym) przewodu zasilającego i
posiada bezpiecznik trzyamperowy. Zaleca się stosowanie przewodów
jednożyłowych.
Miejsce na
włożenie
śrubokręta
Miejsce na samodzielnie
wykonywane dolne otwory dla
przewodów zewnętrznych
Miejsce na podłączenie
przewodów od tyłu
Otwory na wkręty
mocujące do
ściany lub płyty
gipsowej
Zespół złączy
Obrys urządzenia
Minimum 30 mm
C/L
Złącza pętlowe N
(zerowe) i uzie-
mienia
!
1
2
Klawiatura nieaktywna
Resetowanie nieaktywne resetowanie aktywne
klawiatura aktywna
Wyłączony
ączony
Numer przełącznika
o Przed zamontowaniem urządzenia przełączniki DIL znajdujące
się z tyłu muszą być ustawione w wymaganym położeniu.
Poniżej pokazano ustawienia fabryczne.
TP9000
20
GB
PL
GR
PL
Termostat i zdalny czujnik pokojowy:
Zamocować na wysokości około 1,5 m od podłogi, z dala od
ciągów powietrza i źródeł ciepła, takich jak grzejniki i kominki,
oraz miejsc bezpośrednio nasłonecznionych.
1.2 Przewody
UWAGA:
Model TP9000 nie posiada styków beznapięciowych, dlatego NIE
można go podłączać do urządzeń o bardzo niskim napięciu (tzn. <
50 V).
Zdalny czujnik powinien być podłączany wyłącznie za pomocą
jednomilimetrowego, dwużyłowego, podwójnie izolowanego
przewodu. Długość przewodu nie powinna przekraczać 50 m.
Przewód czujnika NIE powinien być prowadzony równolegle do
przewodu zasilającego.
Układy elektroniczne
Zdalny czujnik
Wyłączony
ciepła woda
użytkowa
Wyłączony
ogrzewanie
ączony
ciepła woda
użytkowa
ączony
ogrzewanie
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Danfoss TP9000 Instrukcja instalacji

Kategoria
Termostaty
Typ
Instrukcja instalacji