Greystone AFS-262-112 Instrukcja instalacji

Typ
Instrukcja instalacji
Air Flow Switch
Installation Instructions
General
The plated housing contains a diaphragm, a calibration spring
and a snap-acting SPST (NC) switch.
The sample connections located on each side of the diaphragm
accept a .25” OD tubing via the integral compression and nut or
barbed fitting.
An enclosure cover guards against accidental contact with the
live switch terminal screws and the set point adjusting screw.
The enclosure cover will accept a .5” conduit connection. The
AFS-460 has a reset button located on the top surface of the
enclosure cover.
Air Sampling Connection
The AFS is designed to accept firm-wall sample lines of .25"
OD tubing by means of ferrule and nut compression connec-
tions. For sample lines of up to 10 feet, .25" OD tubing is ac-
ceptable. For lines up to 20 feet, use .25" ID tubing. For lines up
to 60 feet, use .5" ID tubing. A .25" OD adapter, suitable for
slip-on flexible tubing is available: order part number 18311.
Locate the sampling probe a minimum of 1.5 duct diameters
downstream from the air source. Install the sampling probe as
close to the center of the airstream as possible. Identify the high
pressure inlet (H) and the low pressure inlet (L). Select one of
the five application options listed below and connect the sample
lines as recommended.
Positive Pressure Only:
Connect the sample line to inlet H;
inlet L remains open to the atmosphere.
Negative Pressure Only:
Connect the sample line to inlet L;
inlet H remains open to the atmosphere.
Two Negative Samples:
Connect the higher negative sample
to inlet L. Connect the lower negative
sample to inlet H.
Two Positive Samples
Connect the higher positive sample to inlet
H. Connect the lower positive sample to inlet L.
One Positive and One Negative Sample
Connect the positive sample to inlet H. Connect the negative
sample to inlet L.
Application
The AFS is a general purpose airflow proving switch designed
for HVAC and energy management applications. It may be
used to sense positive, negative or differential air pressure.
Mounting
Select a mounting location which is free from vibration. The
AFS pressure switch MUST be mounted with the diaphragm in
any vertical plane in order to obtain the lowest specified
operating set point. Avoid mounting with the sample line
connections in the “UP” position. Surface mount via the two
3/16” diameter holes in the integral mounting bracket. The
mounting holes are 3 7/8” apart.
Field Adjustment-AFS-222 (-112)
The adjustment range of an AFS-222 Air Switch is 0.05 ±.02"
w.c. to 12.0" w.c. To adjust the set point, t urn the adjusting
screw counterclockwise until motion has stopped.
Next, turn the adjusting screw 4 complete turns in a clockwise
direction to engage the spring. From this point, the next ten
turns will be used for the actual calibration.
Each full turn represents approximately 1.2" w.c.
Please note: To properly calibrate an air switch, a digital
manometer or other measuring device should be used to
confirm the actual set point.
Field Adjustment-AFS-262 (-112)
The adjustment range of an AFS-262 Air Switch is 0.05 ±.02"
w.c. to 2.0" w.c. To adjust the set point, t urn the adjusting
screw counterclockwise until motion has stopped.
Next, turn the adjusting screw 4 complete turns in a clockwise
direction to engage the spring. From this point, the next ten
turns will be used for the actual calibration.
Each full turn represents approximately 0.2" w.c.
Please note: To properly calibrate an air switch, a digital
manometer or other measuring device should be used to
confirm the actual set point.
Field Adjustment-AFS-460
The adjustment range of an AFS-460 Air Switch is 0.4" ± 0.02"
w.c. to 12.0" w.c. To adjust the set point, turn the adjusting
screw counterclockwise until motion has stopped.
Next, turn the adjusting screw four complete turns in a
clockwise direction to engage the spring. From this point, the
next ten turns will be used for the actual calibration.
Each full turn represents approximately 1.16" w.c.
Please note: To properly calibrate an air switch, a digital
manometer or othermeasuring device should be used to confirm
the actual set point.
MODEL AFS-222/AFS-222-112 AFS-262/AFS-262-112 AFS-460
SAMPLE MEDIA Air Air Air
MOUNTING POSITION Diaphragm in any vertical plane Diaphragm in any vertical plane Diaphragm in any vertical plane
FIELD ADJUSTABLE RANGE .05, ±.02” w.c. to 12” w.c. .05, ±.02” w.c. to 2” w.c. .40, ±.06” w.c. to 12” w.c.
SWITCH DIFFERENTIAL Progressive, increasing from
approximately .02± .01” w.c. at
minimum set point to approximately
0.8” w.c. at maximum set point.
Progressive, increasing from
approximately 0.02± 0.01” w.c. at
minimum set point to approximately
0.1” w.c. at maximum set point.
Progressive, increasing from
approximately .06± .01” w.c. at
minimum set point, to
approximately .8”w.c. at maximum
set point.
MAXIMUM PRESSURE .5” (0.03 bar) .5” (0.03 bar) .5” (0.03 bar)
OPERATING TEMPERATURE RANGE -40°C – 82.2°C (-40°F–180°F) -40°C – 82.2°C (-40°F–180°F) -40°C – 82.2°C (-40°F–180°F)
LIFE 100,000 cycles/min. at 5psi max
pressure each cycle and at max
electrical load.
100,000 cycles/min. at 5psi max
pressure each cycle and at max
electrical load.
600 cycles/min. at 5psi max pres-
sure each cycle and at max electrical
load.
ELECTRICAL RATING 300 va pilot duty at 115-277vac, 10
amp, non-inductive, 277 vac, 60Hz.
300 va pilot duty at 115-277vac, 10
amp, non-inductive, 277 vac, 60Hz.
300 va pilot duty at 115-277vac, 10
amp, non-inductive, 277 vac, 60Hz.
CONTACT ARRANGEMENT SPDT SPDT SPDT
ELECTRICAL CONNECTIONS Screw top terminals with cup wash-
ers
Screw top terminals with cup
washers
Screw top terminals with cup
washers
SAMPLE LINE CONNECTIONS Ferrule and nut compression type
connectors that accept 6.35 mm
(.25”) OD rigid tubing or 1/4“
barbed fittings (-112) that accept
flexible tubing.
Ferrule and nut compression type
connectors that accept 6.35 mm
(.25”) OD rigid tubing or 1/4“
barbed fittings (-112) that accept
flexible tubing.
Ferrule and nut compression type
connectors that accept 6.35 mm
(.25”) OD rigid tubing.
AUTOMATIC/MANUAL RESET Automatic Automatic Manual
APPROVALS UL and CSA UL and CSA UL and CSA
Specifications
Dimensions Alarm or Control
C
C NO
NC
NC
NO Alarm
Control
Control
Alarm
To prove excessive airflow or pressure
To prove insufficient airflow or pressure
01/07/09
  • Page 1 1
  • Page 2 2

Greystone AFS-262-112 Instrukcja instalacji

Typ
Instrukcja instalacji

w innych językach