Series 490W Hydronic Differential Pressure Manometer -
Hydronic Application Software
Specications - Installation and Operating Instructions
Bulletin TE-490W-QS
Series 490W Hydronic Differential Pressure Manometer is the most accurate
and easy to operate manometer on the market. By using wireless transducers and
a versatile handheld, a single operator can monitor and balance a hydronic system
in less time than traditional hydronic balancers. The Series 490W utilizes mobile
technology to communicate via a Bluetooth connection with the transducers to
monitor differential pressure and ow on up to three different valves. Being wireless
means there are no hoses to carry, snag on equipment or needing to be drained. The
490W includes Dwyer’s Hydronic Application Software that contains valve charts for
numerous manufacturers, which converts differential pressure to ow directly on the
screen.
INCLUDED WITH THE 490W
1. Handheld test instrument with Dwyer Hydronic App preloaded onto device
2. Pressure transducers (4 per kit) with case
3. Installation and operating manual
4. 1/4˝ SAE 45° x 1/4˝ Male NPT straight adapter (2 per kit)
5. 1/4” Female elbow x 1/4˝ Male NPT tting (2 per kit)
6. Piercing gauge adapters [2 per size] (6 per kit)
-1/8˝ DIA x 1-1/2˝ length
-1/8˝ DIA x 3˝ length
-1/16˝ x 1-1/2˝ length
7. 490W fabric carrying case
8. Piercing gauge adapters and ttings case (2 per kit)
9. Charger cable and power adapter for handheld test instrument
Gorilla
®
is a registered trademark of Corning, Incorporated
SPECIFICATIONS
Wireless Distance: Up to 65´ (19.8 m).
Service: Compatible gases & liquids.
Wetted Materials: 316 SS, PTFE, brass.
Accuracy: 2% of reading, ±1 psi.
Compensated Temperature Range: 14 to 140°F (-10 to 60°C).
Pressure Hysteresis: ±0.25% FS.
Pressure Range: See chart.
Process Temperature Limits: -4 to 185°F (-20 to 85°C).
Display: 5˝ Gorrilla
®
glass 3, touch screen, 1280x720.
Resolution: 0.01 psi.
Process Connections: Two 1/4˝ male NPT.
Power Requirements: CR2050 or CR2032 lithium battery, user replaceable.
Weight: 2 lb (907 g).
Agency Approvals: CE, FCC.
3-17/64 [83]
6-17/64
[159]
[16]
1.000
2.940
.944
HEX
MODEL CHART
Model English Range Metric Range Maximum Range Available Engineering Units
490W-6-HKIT/NIST 0 to 50 psi, 0 to 200 psi 0 to 344.7 kPa, 0 to 1379 kPa 100 psi (6.89 bar), 400 psi (27.58 bar) psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
REPLACEMENT TRANSDUCERS
A-490W-1
A-490W-2
A-490W-3
A-490W-4
A-490W-5
A-490W-6
0 to 15 psi
0 to 30 psi
0 to 50 psi
0 to 100 psi
0 to 500 psi
0 to 200 psi
1.034 bar
2.069 bar
3.447 bar
6.895 bar
34.47 bar
13.79 bar
30 psig
60 psig
100 psig
200 psig
1000 psig
400 psig
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.
psi, ft w.c., in w.c., Pa, kPa, hPa, cm w.c., mm w.c.