Eureka AHC-812 Instrukcja obsługi

Typ
Instrukcja obsługi
AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
Dual Channel 240VAC Time Clock
- Programmable Electronic Time Clock
- Dual Channel Time Clock
- Power Reserve; 4 Years with Lithium Battery
- Lock Functions with Pin Codes
- Automatic Summer / Winter Time
- Random or Holiday Programming
- Built-in Lithium Battery / Power Failure Memory
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
Properties
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
Dimensions for AHC-812
Product Range Eureka Digital Time Clock
Rated Supply Voltage 230~240 VAC
Rated Frequency 50 / 60Hz
Consumption Max. 10mA
Switching Power 16A, 250V; cosϕ=1
10A, 250V; cosϕ=0.6
Min. 100mA, 24V AC/DC
Incandscent Lamp Load 2300W
Halogen Lamp Load 2300W
Flourescent Lamp Load Non-compensated
Series compensated 1000W
Parallel compensated 400W (4f)
Compact Flourescent Lamp Load 9x7 W
7x11 W
7x20 W
9x23 W
Timing Basis Quartz
Working Precision 1 ± Sec / Day at 20°C
Power Reserve Approx. 4 years with Display
Enclosure Material High-temperature resistant, Self-extinguishing Thermoplast
Protection Class 11 in compliance with EN60730-1
Degree of Protection IP 20 in compliance with EN60529
Ambient Temperature -10°C ~ +50°C
Properties
INSTRUCTION MANUAL
SAFETY INFORMATION
The connection and installation of electrical must be performed by a skilled electrician only. Any
intervention into or modifications to the appliance shall lead to the lapse of all warranty rights.
DESCRIPTION Of FRONT PANEL
Display of special function:
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
The timer is delivered in so-called sleep
mode.
To increase the power reserve, the switch
changes to the sleep mode after approx. 10
minutes.
Setting the timer is possible before
mounting and connection to the mains
voltage. Briefly press the "Menu" key to
activate the timer.
Basic Settings
Select language with the right and left arrow
and press ”OK” to confirm. Set the year,
month, day, hour and minute with the
arrows and press ”OK” after each selection.
The timer is now ready for programming.
FIRST CONTACT PROGRAMME OVERVIEW
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
PROGRAMMING THE SWITCHING TIMES
Memory Locations
There is a total of 44 memory locations available.
Each switching time per channel occupies one
memory location. If the same time setting is used for
several days, they only occupy one location.
E.g.
Channel 1 ON 06.30 Monday
= 1 location
Channel 1 ON 07.00 Monday to friday
= 1 location
Programming example
1. Select PROG by pressing the ”Menu” key.
2. press the "OK" key.
3. Select NEW by pressing the "OK" key.
4*. Select channel C1 or C2 by pressing "+" or "-". press the ”OK” key to confirm.
5. Select ON/OFF by pressing "+" or "-". press the ”OK” key to confirm.
6. Set the hours by pressing the ”+” or ”-” key. press the ”OK” key to confirm.
7. Set the minutes by pressing the ”+” or ”-” key. press the ”OK” key to confirm.
To store one day of the week only
1. Select weekday by pressing ”+” or ”-”. press the ”OK” key to confirm.
2. Select STORE by pressing ”+” or ”-”. press the ”OK” key to confirm.
To copy to other days of the week
1. Select COPY by pressing ”+” or ”-”. press the ”OK” key to confirm.
2. Select weekday by pressing ”+” or ”-”. press the ”OK” key to confirm.
3. To leave out a day of the week, skip by pressing the ”+” key.
4. finally select STORE by pressing ”OK”.
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
INDIVIDUAL DELETIONS
OVERRIDE PERMANENT ON OR Off
Via the automatic menu Auto only
Channel 1
Channel 2*
press the two keys
for approx.
1 sec.
Manual preselection:
press keys simultaneously.
Channel C1 switches alternately
between ON or Off.
Symbol
appears. Manual
preselection is corrected again by
the stored programme.
Manual preselection:
press keys simultaneously.
Channel C2 switches alternately
between ON or Off.
Symbol
appears. Manual
preselection is corrected again by
the stored programme.
press the two keys
for approx.
2 sec.
permanent ON
Off
permanent
ON
Off
Cancellation of manual preselection/permanent switching:
Briefly press the keys shown above.
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
PERMANENT ON OR OFF, RANDOM OR HOLIDAY PROGRAMME
Effect of the random programme:
The random programme causes the timer to switch between
programmed pairs of switches (ON and Off). The random on
and off times range between approx. 10 mins. and 120 mins.
The random time always begins with Off.
Symbol flashes when the random programme is effective.
Read the text display first
In the menu Man, choose the function; manual, permanent,
random or holiday programme by pressing the "+" or "-" key.
Confirm your selection by pressing the "OK" key.
To cancel a function:
Select the function Clear.
Store your selection by pressing "OK".
Effect of the holiday programme:
The holiday programme has the effect that the timer does not switch on the connected consumer
unit between the programmed start and finish.
Start and finish of the programme is always midnight on the day it is programmed. If the
holiday programme is active, the corresponding channel and holiday symbol are displayed
flashing on menu.
19.30 h ON 6.00 h Off
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
PULSE PROGRAMME
Up to 44 pulse memory locations can be preset.
The pulse times can be used in combination with the other switching times or on
their own.
Example:
ON 07.00 Off 16.30
pulse Off 09.00, 11.00, 13.00, 15.00 during 59 seconds pulse ON
17.30, 19.30, 21.00 during 10 seconds
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
CYCLE PROGRAMME
The max. number of programmes with cycle function is 18.
Only channel 1 can be used with cycle function.
The pulse and pause duration can be set with different time settings with max.
99 minutes and 59 seconds. The cycle programme always begins with a switch on.
The symbol flashes when the cycle programme is active.
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
SETTING/CORRECTING THE DATE FOR SUMMER TIME
Automatic summer/winter time
The timer is pre-programmed with the European summer time which starts at the last Sunday in
March and ends at the last Sunday in October. The time is always 02.00.
If you wish to alter the current settings, press “Menu”, select DAT/TIME and go through all the
date and time settings until ”SUM/WIN” is displayed. press ”OK” to confirm and follow the
instructions on the display.
TO RESET THE TIMER
Reset date, language selection and any manual preselection.
When resetting the timer this does NOT delete any switching times. To delete
the switching times, see “Individual Deletions”.
press the ”Res” key with a pointed object for about 1 second. for
further instructions see ”Basic Settings”.
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
PIN CODE
The device can be locked against unauthorized use with a 4 digit code number.
Select the Manual menu using "+" or "-".
Confirm with the "OK" button.
Selection WITH PIN
Select WITH PIN using "+" or "-".
Confirm with the "OK" button. Make note of any desired 4 digit number.
Select the first digit of your 4 digit code using "+" or "-".
Confirm the entered digit with "OK".
Select further digits as described using "+" or "-".
Confirm each selected digit with the "OK" button.
The device is locked 60 sec. after the last keystroke and can only be operated after the correct
pIN code is entered.
Selection WITHOUT PIN
Select WITHOUT PIN using "+" or "-". Confirm with
the "OK" button.
If a PIN code has been activated, the
timer can no longer be activated
without a valid PIN code after a RESET
Catalogue number: AHC-812
2 Channel 240VAC 24 Hour 7 Day Digital Time Clock
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
Eureka Digital Time Clocks
January 2022
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Eureka AHC-812 Instrukcja obsługi

Typ
Instrukcja obsługi

w innych językach