AMX Radia Eclipse RE-DM4 Instrukcja obsługi

Typ
Instrukcja obsługi

Niniejsza instrukcja jest również odpowiednia dla

Installation Guide
RE-DM4 Radia Eclipse 4-Channel Dimmer Module (120 or 240 volts)
Overview
The RE-DM4 RADIA Eclipse 4-Channel Integrated Dimmer Module (120 VAC:
FG706-01; 240 VAC: FG706-02) controls up to six circuits with four 1200-watt onboard
dimmers and two satellite connectors for RDM series dimmer or switch modules
(FIG. 1). The RE-DM4 is designed for use with the RDA series of enclosures in an
AMX Lighting™ modular digital dimming system. The RE-DM4 is controlled by AXLink
or by dry (contact) closures.
Specifications
Suggested Loads
Caution: Pre-Installation Notes
WARNING: This unit should be installed only by qualified electrical personnel, and in
compliance with all national electrical codes, local codes and ordinances.To prevent
possible personal injury or death, disconnect power to the enclosure at the breaker
box before attempting to work with any AMX Lighting modules.
All Class 1 and 2 wiring must be connected to their dedicated terminals.
Class 1 wiring should be connected through the top of the enclosure, and Class
2 wiring through the bottom.
Load conductors must be same size as line conductors, regardless of
connected load.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm)
clearance around the top and bottom.
Test loads for shorts before connecting.
Class 2 wiring must be rated 300V or higher.
For indoor use only.
AC lighting loads only.
This module may require extra power from the AXLink connection or an external
power supply connected to the control card.
For more information, refer to the RE-DM4 instruction manual available at
www.amx.com.
Radia Lighting System Configuration Pages
The AMX Radia Web pages provide a simple interface for users of the Radia Duet
module. The web pages reside on the AMX master when running the Radia Duet
module and may be accessed through Internet Explorer or Mozilla Firefox. The RE-
DM4 may also be configured using NetLinx code or a terminal. For more information,
refer to the RE-DM4 instruction manual available at www.amx.com.
High-Voltage Connections
Each AMX Lighting module has its high-voltage connectors marked on its circuit
board. Line, load, and neutrals are also clearly marked.
Line-in Connections
Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.
With a jumper, Line 1 and Line 2 provides a single 2400 W input (FIG. 3).
FIG. 1 RE-DM4 4-Channel Integrated Dimmer Module
RE-DM4 Specifications
Dimensions (HW) 5.75" x 10.0" (146.05 mm x 254.00 mm)
Weight 4.5 lbs (2.04 kg)
Line Input 120, 240 VAC, single phase, 2W+G, 50/60 Hz, 2400 W,
one feed
120, 120/240, 240 VAC, single phase, 3W+G, 50/60
Hz, 4800 W, dual feed
Output 1200 W max. per channel @120, 240 VAC
2400 W max. total, all four channels on with single
2400 W feed
4800 W max. total, all four channels on with dual
2400 W feeds
Line input #1 goes to dimmer 1 and 3; line input #2
goes to dimmer 2 and 4
All electrical ratings are for continuous duty
Wire rating Use only copper wires rated at 75°C (167°F) min.
Torque terminals To 20 in-lbs (2.3 N/M)
Maximum wire size 10 AWG (4 mm²)
Wire stripping length 0.5" (13 mm)
AXLink Port 4-pin 3.5mm black captive wire connector. AXLink
communication signaling with 12VDC power in.
Aux Power 2-pin 3.5mm green captive wire connector. This is a
12VDC power input that supplies additional power to the
Radia PCB and connected Radia modules.
Dry Contacts Emergency fire alarm relay connection - Closed relay
activates preset 126. Other control is locked out until
relay opens. Supports daisy chaining of up to 20
dimmers for this connection, with a maximum current
requirement of 200mA when daisy-chained.
Failsafe connection - Works with a toggle switch -
opening the switch triggers preset 128, closing the
switch triggers preset 127. Supports daisy chaining of
up to 20 dimmers for this connection with a maximum
current requirement of 200mA when daisy-chained.
BTU/hr 300 single feed (2400 W); 600 dual feed (4800 W)
Mounting
Jumper
Load out
Neutral
Chokes
High
Voltage
Mounting
External +12V
Aux Power
AXLink
DIP Switch
Dry Closures
AXlink Connector
Power Devices
points
Connections
Address
points
4-Pin Connectors
to RDM series
Modules
Line In
Class 1 wiring
Class 2 wiring
RE-DM4 Specifications (Cont.)
Idle current draw 75 mA @ 120 VAC, 50 mA @ 240 VAC, 100 mA @ 13.5
VDC
RDM control current 2 at 200 mA @ 12 VDC with no additional power supply
Certifications FCC
•CE
UL North America
IEC-60950 Safety
Operating Temp Range 0° to 40°C (32° to 104°F)
Included Accessories 2 4-pin 3.5mm captive wire connector (41-5047)
4 #8-32x1/2” F-point mounting screws
Required Enclosures RDA-ENC2 (FG606-10)
RDA-ENC4 (FG606-11)
RDA-ENC6/6B (FG606-12/13/15)
RDA-ENC12B (FG606-14/16)
Dimmed Switched
Incandescent Motors
Neon, cold-cathode Fans
FIG. 2
High-voltage connections
FIG. 3 Line-in Connections
Neutral
Line in
Load
Load
Dual 2400 W Inputs without jumper
Single 2400 W Input with jumper
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
8/07
©2007 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX.
AMX reserves the right to alter specifications without notice at any time.
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com
93-0706-01 REV: C
Low-Voltage Connections
The low-voltage area in the AMX Lighting controllers contain connections and DIP
switches for AXLink, dry closures, and RDM module connectors. On the controller
cards, low-voltage power for the board is supplied either by line power, optional
auxiliary power supply (RDA-PSM), or the +12 VDC pin on the AXLink connector.
WARNING: Disconnect the main power to the AMX Lighting controller at the
breaker box if rewiring the low voltage connections.
Dry Closure Connections
Dry contact closures from other equipment can be connected to the Radia Eclipse
dimmer module to provide direct manual control of lighting loads (FIG. 5).
Each dry contact closure has two pins: ground and contact. To activate each dry
closure, connect the ground and contact.
Setting AXLink Address Numbers
Set the AXLink address number (1-255) for the RE-DM4. This number must match
the device number in your Axcess program.
Note: By turning all switches off, all circuits will go to 100 percent so that the installer
can test the high-voltage connections without having connections to a control
system.
Connecting AXLink
Connect the 4-pin captive-wire AXLink from the RE-DM4 to the Central Controller for
AXLink control of the dimming system.
RE-DM4 4-pin module connector (male)
Lighting Application Drawings
FIG. 4 Low-voltage connections and DIP switches
FIG. 5 Dry Closure Connections
AXLink address DIP switch
Module connector/LED (CH6)
Dry contact closures
Auxiliary power IN
Module connector/LED (CH5)
AXlink connector
RE-DM4
FAILSAFE
GND
EMERGENCY
GND
Failsafe switch
Alarm system
FIG. 6 Connecting AXlink
FIG. 7 RE-DM4 module connector
Central
RE-DM4
Controller
PWR
AXP
AXM
GND
PWR
AXP
AXM
GND
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
FIG. 8 Example A
FIG. 9 Example B
Example A
Single input
Single-phase, four load
120 or 240 VAC 1
Ø
Example B
Dual Input
Single-phase, four load
120, 120/240, or 240 VAC 1
Ø
  • Page 1 1
  • Page 2 2

AMX Radia Eclipse RE-DM4 Instrukcja obsługi

Typ
Instrukcja obsługi
Niniejsza instrukcja jest również odpowiednia dla

w innych językach