VX-3000 Series
VX-3150DS
Power Supply Manager
DC power supply to all system componentsCombination of built-in power source unit with a high-performance
chargerAutomatical switch to auxiliary battery power if the AC power supply is downVX-3150DS: EN 54-4 certi-
fied, Certificate No: 1134-CPR-137
Order no: VX-3150DS-EB
Specifications
Power source 220 - 230 V AC, 50 / 60 Hz
Power consumption Approx. 1460 W max. (at rated output with charging), 460 W (EN 60065)
Outputs
DC power output:
8 x 31 V (19 – 33 V) 25 A max. each, M4 screw terminal, distance between barriers: 11 mm
3 x 31 V (19 – 33 V) 5 A max. each, removable terminal block (3 x 2 pins)
1 x 24 V (16 – 25 V) 0.3 A max., removable terminal block (1 x 2 pins
Charging method Temperature compensated trickle charging
Charging output voltage 27.3 V ±0.3 V (at 25 ˚C), Temperature correction coefficient: -40 mV/ ˚C
Battery connection
One each positive and negative terminal, applicable cable diameter: AWG 6 – AWG 0 (AWG 1/0) (16 mm2 – 50 mm2)Line resistance
within 4 mΩ / total
Control connector
RJ45 female connector for connecting the system and cascade connectionShielded Twisted-pair straight cable (TIA/EIA-568A
standard)
DS LINK IN/OUT Type of control signal: Battery check, AC power status, DC power status, charging circuit failure, battery failure, and communication
Panel indicator AC power IN 1, Charging (Green), Battery power (Green), Battery connect (Green), Battery condition (Green)
Weight 9,0 kg
Certificates EN 54-4
Dimensions (W x H x D) 482 x 132,6 x 400,5 mm
Dimensions (ø x D) x 400,5 mm
Gross weight 14,1 kg
Finish Steel plate, surface-treated, 30% gloss, paint, black
Operating humidity 90 % RH or less (no condensation)
Operating temperature -5 °C to +45 °C