Installation Instructions
IMPORTANT: Turn off power before
installing or removing connector.
Product to be used in accordance with
local and national codes.
1. Strip wires 5/8” (15.9 mm).
2. Align any frayed strands or
conductors.
3. Place stripped wires together with
ends of insulation even.
4. Push conductors firmly into connector
and twist onto wire until tight. Wipe
sealant in and around conductors
and connector opening while
tightening. Do not over torque.
5. Position conductors as shown in
Figure A and close lid. Note: When
installing 2 - #18 conductors,
position to exit out same side.
See Figure B.
6. Do not reuse.
Figure A Figure B
Catalog # Selling Unit
63315 Bag of 10
63350 Box of 100
Direct Bury Twist-on with Strain Relief
Max. Voltage: 600V
Connector Size: 1.75” x 2.28”
Wire Type: Copper/Copper
Wire Range: Min #22/Max #6
Silicone Sealant: -45°F to 400°F
UL Designation: MSR
Measurements (Inches):
A - 2.28 B - 1.05
C - 1.75 D - 0.70
A
B
C
D
Integrated twist-on connector.
No additional wire connector needed.
Strain Relief Lid
PRODUCT SPECIFICATIONS
& MEASUREMENTS
* UL 486D Listed as a sealed wire
connector system. For use in damp,
wet, raintight, direct bury and
submersible locations. Not to be
used in continuous submersion
applications.
DryConn
®
DBSR
®
Yellow
Selected 600V Wire Combinations
2 #18 1 - 3 #10 1 #14 w/3 - 4 #18
1 - 4 #12 2 #14 w/2 - 4 #16 1 #12 w/2 - 4 #18
3 #14 w/1 - 2 #16, #18, #20 or #22 1 #8 w/1 - 2 #16, #18, #20 or #22 2 #12 w/1 - 2 #14, #16 or #18
4 - 6 #16 5 #14 w/1 #18 2 - 5 #14
1 #8 w/1 #12 1 #12 w/1 - 4 #14 or #16 3 #10 w/1 #18
1 #10 w/1 - 5 #16 3 #12 w/1 #14 1 #10 w/1 - 3 #14
Contact factory for a complete list of wire combinations at 800.633.0232.