Low temperature burners - XPO™ burner
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2012 Copyright Maxon Corporation. All rights reserved.
1-2.4-3
E-i-9/12
Available XPO™ ultra low NOx burner sizes
Packaged (PB) versions
External blower (EB) versions
Typical burner data
Fuel: natural gas at 60°F with 1000 Btu/ft3 (st) HHV - sg = 0.6 [1]
Combustion air: 60°F - 21% O2 - 50% humidity - sg = 1.0 [1]
Stated pressures are indicative. Actual pressures are a function of air humidity, altitude, type of fuel and gas quality.
XPO 1 PB 2
XPO 1 PB 4
XPO 2 PB 2
XPO 2 PB 4
XPO 3 PB 2
XPO 3 PB 4 XPO 4 PB 4 XPO 5 PB 4
15%
excess
air
30%
excess
air
15%
excess
air
30%
excess
air
15%
excess
air
30%
excess
air
15%
excess
air
30%
excess
air
15%
excess
air
30%
excess
air
Maximum burner capacity [4] MBtu/h 1.2 1.0 2.35 2.1 3.3 3.0 5.0 4.5 6.6 6.0
Minimum burner capacity [2] MBtu/h 0.3 0.3 0.59 0.59 0.66 0.66 1.0 1.0 1.0 1.0
Turndown ratio [3] 4:1 3.3:1 4:1 3.6:1 5:1 4.5:1 5:1 4.5:1 6.6:1 6:1
[1] sg (specific gravity) = relative density to air (density air = 0.0763 lb/ft3 (st))
[2] Minimum burner capacity will be affected by fuel and applications parameters (heat flux).
[3] Turndown ratio will vary depending on the application heat flux. Lower heat flux (<8000 Btu/in2) will result with lower turndown ratios.
[4] Capacity displayed assumes blower operation on 60Hz electrical supply. Gross output will be reduced by 17% if operated on 50Hz. Fuel and
air pressure should be reduced by 30% while motor power will reduce 40% with 50Hz operation. Turndown ratio will be reduced in kind with
minimum capacity remaining fixed.
Typical burner data
Fuel: natural gas at 60°F with 1000 Btu/ft3 (st) HHV - sg = 0.6 [1]
Combustion air: 60°F - 21% O2 - 50% humidity - sg = 1.0 [1]
Stated pressures are indicative. Actual pressures are a function of air humidity, altitude, type of fuel and gas quality.
XPO 3 EB 2
XPO 3 EB 4 XPO 5 EB 4
15%
excess air
30%
excess air
15%
excess air
30%
excess air
Maximum burner capacity [4] MBtu/h 4.5 4.2 8.8 8.0
Minimum burner capacity [2] MBtu/h 0.75 0.75 1.5 1.5
Turndown ratio [3] 6:1 5.6:1 5.9:1 5.3:1
[1] sg (specific gravity) = relative density to air (density air = 0.0763 lb/ft3 (st))
[2] Minimum burner capacity will be affected by fuel and applications parameters (heat flux).
[3] Turndown ratio will vary depending on the application heat flux. Lower heat flux (<8000 Btu/in2) will result with lower turndown ratios.
[4] Capacity displayed assumes blower operation on 60Hz electrical supply. Gross output will be reduced by 17% if operated on 50Hz. Fuel and
air pressure should be reduced by 30% while motor power will reduce 40% with 50Hz operation. Turndown ratio will be reduced in kind with
minimum capacity remaining fixed.